Warning
This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and
wiring.
This is an OPEN TYPE Controller. The DVPPF01-S should be kept in an enclosure away from airborne dust, humidity,
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tool or key to open
the enclosure, so as to avoid the hazard to users or any damage to the module. DO NOT touch terminals when power
on.
Introduction
Functions
• Cyclical data exchange process
• Support the SYNC and FREEZE for data synchronization between master and slaves
• Support Auto Baud rate detection
• Support 12MHz baud rate in DP network
• Cyclical data size is fixed to 4 bytes input and 4 bytes output
• Support GSD file configures by using configuration tools
Product Profile
6
4
Model name
3
Extension port
x16
7
2
Power/NET LED
x16
1
Extension hole for mounting unit or module
DIN rail clip
Extension clip
4
8
Address switch
5
Profibus connector
6
Specifications
DP Connection
Interface
DB9 pin connector
Transfer method
High speed RS-485
Transfer cable
2-wire twisted shielded cable
Electrical isolation
500V DC
Communication
Message types
DPV0, cyclical data exchange process
Device ID
09B9 HEX
GSD file
EATN09B9.GSD
Model name
DVPPF01-S
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps
Baud rates
(auto detected)
1.5Mbps, 3Mbps, 6Mbps, 12Mbps
Environmental Specification
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Noise immunity
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation: 0° C ~ 55° C (temperature), 50 ~ 95% (humidity), Pollution degree 2
Environment
Storage: -25° C ~ 70° C (temperature), 5 ~ 95% (humidity)
Vibration/shock
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)
resistance
IEC 61131-2 & IEC 68-2-27 (TEST Ea)
Approvals
Installation & Configuration
Dimensions
POWER
NET
1
x16
0
x16
Dimensions are in millimeter and [inch]
Installing the DVPPF01-S with the PLC Controller
ENGLISH
Open the extension cover with a screwdriver.
Use a screwdriver to lift and unfasten the fixing clip.
Plug the Profibus connector to the socket of
Connect the DVPPF01-S to extension port of PLC
DVPPF01-S, and tighten screw to secure the
controller and fasten the fixing clip.
connector.
POWER
POWER
s
s
RUN
NET
X0
ERROR
BAT.LOW
X1
1
x16
X2
X3
RUN
X4
0
x16
X5
X6
X7
STOP
C0
Y0
C1
Y1
C2
Y2
Y3
0
1
Cable Length and Baud Rate
The Maximum cable length in a segment depends on the transmission speed. Profibus-DP communicates at
speeds from 9.6kbps to 12Mbps over distances from 100 to 1,200 meters.
Baud rate (bps)
9.6k
19.2k
93.75k
187.5k
500k
1.5M
Length (m)
1,200
1,200
1,200
1,000
400
200
Check the extension I/O by WPL software:
Connect to PLC MPU
Once connection is successful, software will check if 32
inputs/outputs is detected
PIN Definition of DP Connector
PIN
Definition
Content
PIN
Definition
1
--
N/C
6
2
--
N/C
7
Data receiving/sending
3
RxD/TxD-P
8
RxD/TxD-N
P (B)
4
--
N/C
9
Data reference
5
DGND
potential (C)
MAC ID Setting
Address
Content
1...0x7D
Valid Profibus address
0 or
Invalid Profibus address. NET LED will rapidly blink with RED when
0x7E...0xFF
node address is at 0, 0x7E...0xFF
Setting of DVPPF01-S Connect to Profibus-DP
Connection example:
PC Master
POWER
RUN
ERROR
BAT .LO W
R UN
STO P
0
1
DVPPF01-S provides fixed 4 bytes input data and 4 bytes output data to user in Profibus-DP system. 4 bytes
input data are transmitted from DVPPF01-S module to Profibus-DP Master, it are mapping to Y20-Y57 in PLC
controller when DVPPF01-S is the first extension unit of PLC. 4 bytes output data are transmitted from
Profibus-DP Master, and it are also mapping to X20-X57 in PLC controller.
Data Mapping
Following is a ladder program example:
M1000
MOV
MOV
MOV
MOV
This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11
registers in PLC controller. And, PLC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57,
these 4 bytes data will send to DVPPF01-S, and DVPPF01-S will send these data to DP master.
Troubleshooting
NET LED
LED status
Indication
OFF
No power supply
Verify DVPPF01-S is powered on
Check whether the switch setting is valid
Red blinking
Invalid Profibus address setting
Setting range of slave: 1-125
(rapidly)
via switch
Set the valid value and re-power
Communication link to
Red blinking
PROFIBUS, and no cyclical
--
3M
6M
12M
data exchanged
100
100
100
Verify that DP network installation is OK
Verify that PLC is working
Red ON
No connection to Profibus
Verify that switch address setting match with configuration in
DP master
Green
Reserved
--
blinking
Cyclic data exchange in
Green ON
--
progress and OK
Power LED
LED status
Indication
Corrective actions
Green ON
Power on
--
OFF
No power
Verify that PLC controller is powered on
注 意 事 項
Content
VP
Positive voltage
9
5
(Open Type)
--
N/C
Data receiving/sending
N (A)
--
N/C
6
1
產 品 簡 介
功 能 說 明
'
x16
SYNC
FREEZE
'
x16
DP
12MHz
4 bytes
GSD file
各 部 介 紹
4
3
x16
2
x16
Profibus network
1
DVP-PS01
DVP-12SA
4
DVP-PF01
5
s
P OWER
s
N ET
X0
X 1
1
x16
X2
X3
X4
x16
0
X5
X6
X7
C0
規 格
Y0
C1
Y1
C 2
Y2
Y3
DP
連 線
DB9
RS-485
2
500V DC
通 訊
DPV0,
ID
09B9 HEX
GSD
DELT09B9.GSD
DVP-PF01
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps
1.5Mbps, 3Mbps, 6Mbps, 12Mbps
K4X20
D10
環 境 規 格
K4X40
D11
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
D20
K4Y20
Analog & Communication I/O: 1KV
D21
K4Y40
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
0°C ~ 55°C
/
-25°C ~ 70°C
/
IEC 61131-2, UL 508
安 裝 與 設 定
Corrective actions
外 觀 圖
POWER
NET
繁 體 中 文
/
(
)
4 bytes
6
/
7
NET
/
DIN
/
8
6
Profibus
50 ~ 95%
2
5 ~ 95%
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)
1
x16
0
x16
: mm [inches]

Advertisement

loading

Summary of Contents for Delta Electronics Network Device DVPPF01-S

  • Page 1 Communication Message types Device ID GSD file Model name Baud rates (auto detected) Environmental Specification Noise immunity Environment Vibration/shock resistance Approvals Installation & Configuration Dimensions Installing the DVPPF01-S with the PLC Controller Warning ENGLISH Open the extension cover with a screwdriver. This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and wiring.