D+H RZN 4300-E Instructions For Use Manual

Smoke vent control panel in conjunction with group plug-in unit

Advertisement

Instruction for use
This system is designed to protect lives and safeguard valuable property!
Wiring, installation and functional testing only by qualified electrician.
The green pilot lights on the vent buttons must be lit up at all times, otherwise refer to "Troubleshooting".
Rectify power failure without delay. Emergency power supplied for 72 hours.
230V AC
power supply
Wind/ rain
detector
D+H Mechatronic AG • Georg-Sasse-Str. 28-32 • D-22949 Ammersbek • Tel.(+4940) 60565-219 • Fax (+4940) 60565-264
Smoke Vent Control Panel RZN 4300-E
in conjunction with group plug-in unit GE 514
Annual function check by manufacturer or
duly authorized specialist.
INSTALLATION/ MAINTENANCE
Drive-
group
Smoke
Smoke
or thermal
vent
detector
button
Alarm
Display
panel
Detector
contacts
Control
contact
of external
system
Vent
button

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RZN 4300-E and is the answer not in the manual?

Questions and answers

Summary of Contents for D+H RZN 4300-E

  • Page 1 230V AC Display power supply panel Detector contacts Control Wind/ rain contact detector of external system Smoke Vent Smoke or thermal button vent detector button D+H Mechatronic AG • Georg-Sasse-Str. 28-32 • D-22949 Ammersbek • Tel.(+4940) 60565-219 • Fax (+4940) 60565-264...
  • Page 2: Sample Configuration

    - smoke-vent button 2 per control panel up Ground short cuircut panels to max. current of 64 A monitoring. - fire detectors (only with extended - extern control over control panel). 2/10 RZN 4300-E/ GE 514 Rev.:1.2...
  • Page 3 - vent buttons Connection of: - vent button panels - wind/rain detectors - temperatur controls - vent button panels - Temp. - max. - - temperatur controls - timer indicators - BMS 3/10 RZN 4300-E/ GE 514 Rev.:1.2...
  • Page 4: Installation Information

    Both the lines must Guarantee be switched off for „Alarm Reset“. You will get 2 years guarantee for all D+H products from date of verified handing over of the system up to maximal 3 years after date of delivery, when mounting and starting has been carried out by a D+H authorized distributor.
  • Page 5 The vent opens completely then close it again. after the vent button has Activate fire detectors with D+H smoke-detector test unit been pressed once. or cigarette smoke. Response time-lag approx. 20 sec. The red LED must light up, and the smoke vent must If DIP switch 2 is OFF, the vents will only open as open.
  • Page 6: Maintenance

    Respective current D+H maintenance instruction is tal voltmeter and a calibrated thermometer with side decisive. stationary chart. D+H authorized expert companies are specially trained by D+H for carrying out this maintenance compentently, Surroundings and therefore they are automatically provided with rele- temperature in Load voltage vant maintenance instructions.
  • Page 7: Troubleshooting

    LED lights up; vent cannot close. Pilot light extinguishes during Check terminal resistor or module between Fault in MOT group. closing operation after approx. 20 terminals 5 and 6. sec.; red LED lights up. 7/10 RZN 4300-E/ GE 514 Rev.:1.2...
  • Page 8: Electrical Connection

    Electrical Connection 8/10 RZN 4300-E/ GE 514 Rev.:1.2...
  • Page 9 Electrical Connection Parallel connection of smoke - vent buttons Smoke-vent button Smoke-vent button 1st line 2nd line RT 42 RT 42 10kW 7x 0,8 5x 0,8 10k * *Shunt connection by customer 9/10 RZN 4300-E/ GE 514 Rev.:1.2...
  • Page 10: Sample Installations

    Remember 4 wires for branch! Remember 4 wires for branch! 10/10 RZN 4300-E/ GE 514 All sizes in millimetre • Rights to technical modifications reserved. Reprinting and phototechnical Rev.:1.2 reproduction also in extracts has to be expressively authorized by D+H Mechatronic AG.

Table of Contents