FPA-5000 | FPA-1200 | AVENAR panel 8000 | Content | en AVENAR panel 2000 | AVENAR keypad 8000 Content For your safety Touch Screen Operation Maintenance Use in accordance with standards Knowledge required for staff For your information What's new?
Page 4
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Content AVENAR panel 2000 | AVENAR keypad 8000 Diagnosis Remote keyboard Operation and display Connection to remote control unit Alarm Types of alarm Entry delays Day and night modes Alarm message to the central unit Optical 8.4.1...
Page 5
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Content | en AVENAR panel 2000 | AVENAR keypad 8000 11.4.2 Using the status bar Cancel/uncancel the 11.5 buzzer 11.6 Cancelling/uncancelling output to a fault notification routing device Cancelling/ 11.6.1 uncancelling output to a fault notification routing device Cancelling output to a fault 11.6.2...
Page 6
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Content AVENAR panel 2000 | AVENAR keypad 8000 Day and night modes 17.1 Switching between day mode and night 17.2 mode Viewing details 17.3 Time change to switch to night mode Configuration 18.1...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | For your safety | it is AVENAR panel 2000 | AVENAR keypad 8000 For your safety Before using the equipment, please familiarize yourself with these instructions. If you do not read and understand these explanations, you will not be able to operate the equipment without problems.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | For your safety AVENAR panel 2000 | AVENAR keypad 8000 Use according to standards The panel controller is designed to operate the AVENAR panel 8000/2000 fire panel. It can perform the following tasks: –...
All functions at a glance, Page 12 . What's new? The AVENAR panel 8000/2000 is the successor to the modular fire control panel FPA-5000/FPA-1200. The AVENAR panel 8000/2000 combines a new, powerful platform for the control panel with all the most stable safety features known.
– Defective repairs – Catastrophes, influence of foreign bodies and force majeure. Without permission from Bosch, no changes or additions may be made to the control unit or the central controller, nor should they be rebuilt. Reconstruction requires written permission. In the event of unapproved construction changes, all warranty claims against Bosch become invalid.
Page 11
FPA-5000 | FPA-1200 | AVENAR panel 8000 | For your information | it is AVENAR panel 2000 | AVENAR keypad 8000 Bosch Security Systems GmbH Operating manual 2020-07 | 3.0 | F.01U.378.877...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | All functions at a glance AVENAR panel 2000 | AVENAR keypad 8000 All functions at a glance Main menu Cancel Block Diagnosis Maintenance Configuration Switch to Day Mode Other functions...
Page 13
FPA-5000 | FPA-1200 | AVENAR panel 8000 | All functions at a glance | en AVENAR panel 2000 | AVENAR keypad 8000 Other functions -> Other functions Change date/time Master Password Remote Services Change password Alarm counters Evacuate Control / Supervision...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | In summary AVENAR panel 2000 | AVENAR keypad 8000 In summary This chapter contains information about the following elements of the plant controller: – Operating elements, Page 14 – Status LED, Page 15 –...
Page 15
FPA-5000 | FPA-1200 | AVENAR panel 8000 | In summary | it is AVENAR panel 2000 | AVENAR keypad 8000 Display and control all alarm zones. Login and Logout: Enter your user ID and password, or access the custom menu if you are already logged in.
Page 16
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | In summary AVENAR panel 2000 | AVENAR keypad 8000 Day mode/delays active General deactivation General breakdown TO** Fire detector faulty/deactivated TO** Signaling device with fault/disabled TO** Alarm transmission device faulty/disabled...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | In summary | it is AVENAR panel 2000 | AVENAR keypad 8000 general or with a general icon disabled depending on your condition. Also, in case of fault, the LED of the respective element flashes while the LED indicating the general fault lights up yellow.
Page 18
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | In summary AVENAR panel 2000 | AVENAR keypad 8000 * Level 3 logged in Bypass Diagnostics Block Configuration Maintenance PQRS WXYZ Switch to day mode Further functions Control Reset Monitoring...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | In summary | it is AVENAR panel 2000 | AVENAR keypad 8000 Text Meaning Central 4-1 Logical node address Access level 3 Access level of the logged in operator. Maximum levels: 2, 3 or 4 They are only displayed in the main menu.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | In summary AVENAR panel 2000 | AVENAR keypad 8000 - Date - Hour – Night mode either – Day mode either – Night/day combination Depending on the settings, additional information may appear.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Operating principle | en AVENAR panel 2000 | AVENAR keypad 8000 Operating principle Activate and deactivate Power button The fire panel must be switched on and off using a power button located on the right side of the panel.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Operating principle AVENAR panel 2000 | AVENAR keypad 8000 Warning! To prevent the PBX from running in a safe state, do not restart the PBX twice within 100 seconds. If the control panel is rebooted twice within 100 seconds (either due to a system error or intentionally, for example during initial installation), it runs in a safe state that can only be terminated by a manual reboot.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Operating principle | en AVENAR panel 2000 | AVENAR keypad 8000 Connection and disconnection To access access levels 2 to 4, you must log in. The prerequisite is that you have access authorization.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Operating principle AVENAR panel 2000 | AVENAR keypad 8000 Access authorization Warning! Depending on your access authorization, you can use certain functions of the central controller. If you want to select a function for which special access authorization is required and no user with the appropriate authorization has logged in, you will be asked to enter your user number and password.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Operating principle AVENAR panel 2000 | AVENAR keypad 8000 – By description – By number – By number (do not show description) SelectBy description. A list of all detectors appears, sorted alphabetically.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Operating principle | en AVENAR panel 2000 | AVENAR keypad 8000 List field Meaning State of the list field Assigned mode The selected item has already been assigned a TEXT specific mode. It is selected to and marked reset it to its original mode;...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Operating principle AVENAR panel 2000 | AVENAR keypad 8000 In the main menuSearch function/element, it is possible to search for all elements connected to the system and all functions offered by the control panel controller, as well as equipment descriptions, regardless of the menu in which they appear;...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Operating principle | en AVENAR panel 2000 | AVENAR keypad 8000 Character JKLjkl5 MNÑOmnño6 PQRSpqrs7 TUVtuv8 WXYZwxyz9 You can enter letters and numbers using each of the keys shown. Press the corresponding key on the membrane keypad until the required letter or number appears.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Operating principle AVENAR panel 2000 | AVENAR keypad 8000 – Entering a shortcut – Through a menu selection 5.12.1 Enter by shortcut The language of the control panel can be quickly changed with a shortcut: 1.
Page 31
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Operating principle | en AVENAR panel 2000 | AVENAR keypad 8000 Examples: Element with physical addressing: 5.1 - 4 Element with logical addressing: 3 - 4 Bosch Security Systems GmbH Operating manual...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Network operation via Ethernet AVENAR panel 2000 | AVENAR keypad 8000 Network operation via Ethernet IP settings To change the Ethernet settings or configure them for the first time, select from the start...
Page 33
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Networking via Ethernet | en AVENAR panel 2000 | AVENAR keypad 8000 Sending a ping command to a specific IP address to check the availability of other nodes on the network. –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Remote Keyboard AVENAR panel 2000 | AVENAR keypad 8000 Remote keyboard Operation and display A remote keypad is programmed by default to display messages even if no operator is logged in.
Page 35
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Remote Keyboard | en AVENAR panel 2000 | AVENAR keypad 8000 Warning! It is also possible to establish a connection to a remote control panel via another control panel. Closing the connection to the remote central 1.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Alarm AVENAR panel 2000 | AVENAR keypad 8000 Alarm Warning! You can find information on how to handle a fire alarm at the Fire Alarm, Page 43 . This chapter contains information on the following points: –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Alarm | en AVENAR panel 2000 | AVENAR keypad 8000 The FSP-5000-RPS programming software can be used to program various false alarm avoidance strategies. These strategies are primarily used on fire detectors, but can also be assigned to any other detector, depending on the configuration.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Alarm AVENAR panel 2000 | AVENAR keypad 8000 Depending on the settings, an incoming alarm is handled differently in day and night modes: Night mode Night mode has the highest security level. Depending on the setting, the alarm message is transmitted to the fire department without delay.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Alarm | en AVENAR panel 2000 | AVENAR keypad 8000 8.4.2 Display of detector zones in alarm state The number of messages in question is displayed in the status bar. Warning! First, the logical zones in which one or more detectors have triggered an alarm are listed. To view individual detectors, select the desired logical zone.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Alarm AVENAR panel 2000 | AVENAR keypad 8000 Warning! 30 seconds after the last entry (e.g. after scrolling through the list), the first and oldest alarm appears again at the top of the list.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Alarm | en AVENAR panel 2000 | AVENAR keypad 8000 8.4.6 Displaying individual detectors in a logical zone To view individual detectors in a logical zone, select the desired logical zone. Alarm messages from individual detectors are listed: 8.4.7...
Page 42
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Alarm AVENAR panel 2000 | AVENAR keypad 8000 – Type of message – Date and time of the message – Physical and logical addressing of the detector – For LSN detectors only: specification of detector type –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Fire Alarm | en AVENAR panel 2000 | AVENAR keypad 8000 Fire Alarm Warning! Detailed information about alarm types, alarm delays and the panel controller display can be found in the Alarm, Page 36 .
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Fire Alarm AVENAR panel 2000 | AVENAR keypad 8000 – Fuchsia: groups that are actively controlled without a real alarm, for example in the event of a fire drill. – Green: groups that are not active.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Fire Alarm | en AVENAR panel 2000 | AVENAR keypad 8000 Warning! The display automatically switches back to the alarm indication after 30 seconds. To return to the alarm indication before 30 seconds have elapsed, selectFire.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Fire Alarm AVENAR panel 2000 | AVENAR keypad 8000 – Recognition timeThe alarm must be confirmed within the specified time interval. – Research timeThe alarm must be verified within the specified time interval. A different time interval can be specified for each logical zone or detector.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Fire Alarm | en AVENAR panel 2000 | AVENAR keypad 8000 Depending on the configuration, three reset variants are offered: - Standard Reset all messages of the same type: All messages of the selected message type, such as fire, are reset.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Error message AVENAR panel 2000 | AVENAR keypad 8000 Error message This chapter contains information on the following points: – Fault indication call, Page 48 – Fault message on the central unit, Page 48 –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Error message | en AVENAR panel 2000 | AVENAR keypad 8000 Unrecognized list fields indicate recognized error messages. Warning! A maximum of four fault messages can be displayed on the screen at any one time. Only fields that can be operated are shown (e.g.Recognizeand Reset).
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Error message AVENAR panel 2000 | AVENAR keypad 8000 Warning! Depending on the system configuration, the logical or physical address of the element is displayed. 10.2.4 The newest message The newest message is displayed at the bottom of the list.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Error message | en AVENAR panel 2000 | AVENAR keypad 8000 Warning! The information displayed is entered into the FSP-5000-RPS programming software. The following information will appear: – Item Category – Message Type –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Error message AVENAR panel 2000 | AVENAR keypad 8000 The selected item/group of items is reset. If a list field is marked with an "R", the reset process has not yet been completed for this item.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Cancellation | en AVENAR panel 2000 | AVENAR keypad 8000 Annulment This chapter contains information on the following points: – Cancellation and de-annulment of elements, Page 53 – Viewing and un-un-un-un-un-un-un-groups, Page 53 –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Cancellation AVENAR panel 2000 | AVENAR keypad 8000 A list of various item categories is displayed. The number listed shows the number of overridden items or groups of overridden items in the corresponding item category: 3.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Cancellation | en AVENAR panel 2000 | AVENAR keypad 8000 Annular Further... Buzzer The buzzer is ignored and the UI text changes toUnmute buzzer. To remove the buzzer override, selectUnmute buzzerin step 4.
Page 56
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Cancellation AVENAR panel 2000 | AVENAR keypad 8000 4. Select the output in the fault notification routing equipment from the list and pressUn- cancel. If necessary, enter your user ID and password to log in to the central controller.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Block | is AVENAR panel 2000 | AVENAR keypad 8000 Block This chapter contains information on the following points: – Locking and unlocking items, Page 57 – Viewing the list of all blocked items, Page 57 Caution! All alarm and fault messages from blocked detectors are no longer displayed.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | is | Block AVENAR panel 2000 | AVENAR keypad 8000 12.3.1 Using the menu To view a list of all blocked items, select the following from the start menu: Cancel Block Block Show blocked devices A list of various item categories is displayed.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Diagnosis | en AVENAR panel 2000 | AVENAR keypad 8000 Diagnosis This chapter contains information on the following points: – Item Details, Page 59 : Diagnostic information about LSN modules and about the elements of a selected LSN module –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Diagnosis AVENAR panel 2000 | AVENAR keypad 8000 2. Select the desired list fields. The list fields are marked. 3. SelectYeah. A list of various data types is displayed. 4. Select the desired field. The field is marked.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Diagnosis | en AVENAR panel 2000 | AVENAR keypad 8000 Screen test To test the display's operability: 1. From the start menu, selectDiagnosis Hardware 3. SelectScreen test. First, the buzzer will turn on for a short time. Then the screen will fill with black, white, red, green and blue colors.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Diagnosis | en AVENAR panel 2000 | AVENAR keypad 8000 13.7.3 Ethernet ports To display a table listing the various parameters and status of the two Ethernet ports: check the consistency of the 1.
Page 64
LSN devices and AVENAR panel 8000/2000 modules is collected and sent to the Bosch RemotePortal or a central management server system (CMS) via a secure private network, where it can be analyzed to provide preventive services to customers.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Diagnosis | en AVENAR panel 2000 | AVENAR keypad 8000 – RM/RA: Last transfer status:Status of the last data transfer from the LSN devices connected to the fire panel to the RemotePortal server (OK/Wrong/Auth. wrong) –...
Page 66
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Diagnosis AVENAR panel 2000 | AVENAR keypad 8000 – Connection failure counter: shows the number of connection errors with the VAS over IP system until the last restart of the control panel.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Maintenance AVENAR panel 2000 | AVENAR keypad 8000 Warning! In the category of elementsHVAC, the function field is also offeredCar. Select this function field to assign automatic mode to a fan, for example.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Maintenance – Test | en AVENAR panel 2000 | AVENAR keypad 8000 Maintenance – Test This chapter contains information on the following points: – Test Groups, Page 69 – Starting and ending the test, Page 71 –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Maintenance – Test AVENAR panel 2000 | AVENAR keypad 8000 Warning! Deleted items are assigned to the groupUnassigned items. Tilting function New items can be added and existing items can be deleted in each submenu.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Maintenance – Test | en AVENAR panel 2000 | AVENAR keypad 8000 4. SelectAdd. The selected item is added to the selected test group. Change name To change the name of the input or output group: 1.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Maintenance – Test AVENAR panel 2000 | AVENAR keypad 8000 15.3 Completion of testing for all elements To end the test for all groups and test items: 1. SelectFinishin the status bar.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Maintenance - historical | en AVENAR panel 2000 | AVENAR keypad 8000 Maintenance - historical In the history, all data on specific events or equipment types is stored by date and time. Filters can be set to display specific data.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Maintenance - historical AVENAR panel 2000 | AVENAR keypad 8000 16.3 Filter change In each filter menu, another filter can be set using the status bar: 1. SelectChange filterin the selection bar below. The different filters are displayed.
Page 75
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Maintenance - historical | en AVENAR panel 2000 | AVENAR keypad 8000 2. SelectDefine interval. Two possibilities are offered on the screen. 3. Check the check box in front of one of the two options: –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Day and night modes AVENAR panel 2000 | AVENAR keypad 8000 Day and night modes This chapter contains information on the following: – Switching between Day/Night mode – Time change to switch to night mode The way an incoming alarm is handled depends on whether the system is in day mode or night mode;...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Day and night modes | en AVENAR panel 2000 | AVENAR keypad 8000 Switching via the menu Depending on the mode the control unit has been switched to, it is displayedSwitch to Day Mode eitherSwitch to Night Modein the start menu.
Page 78
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Day and night modes AVENAR panel 2000 | AVENAR keypad 8000 On the status bar, select either either From the start menu, selectSwitch to Day Mode. 1. Select Change time.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Configuration | en AVENAR panel 2000 | AVENAR keypad 8000 Configuration This chapter contains information on the following points: – Physical Node Address (PNA/RSN), Page 79 – Group Edition, Page 79 –...
Page 80
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Settings AVENAR panel 2000 | AVENAR keypad 8000 You can select several options: – Delete all: Deletes all items in the selected input group. – Show/Change: Displays all items in the selected input group and deletes individual items.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Configuration | en AVENAR panel 2000 | AVENAR keypad 8000 To add new items: 1. SelectNew. The screen changes. Several item categories are displayed with items that have not yet been assigned to a test group.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Settings AVENAR panel 2000 | AVENAR keypad 8000 – Change universal password: The same password can be set for all access levels via the FSP-5000-RPS programming software. This means that all users with access authorisation for the second level receive the same password, for example.
Remote Services secure network gateway. For detailed instructions on setting up a remote connection to the RemotePortal, refer to the Network Operation Guide. To set up a connection to the Bosch Remote Portal to activate Remote Services, perform the following steps: 1.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Settings AVENAR panel 2000 | AVENAR keypad 8000 7. Confirm withAcceptand return to the screenRemote Services. To leave the screen without saving changes, selectCancel. Warning! Change only theSystem IDIf you want to reuse an existing oneSystem ID.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Other functions | en AVENAR panel 2000 | AVENAR keypad 8000 Other functions This chapter contains information on the following points: – Changing the date/time, Page 85 – Master Password, Page 85 –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Other functions AVENAR panel 2000 | AVENAR keypad 8000 The controller can be asked to issue a number. Please send this number to the sales support department by phone or email. A password will be provided which is only valid for 24 hours.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Other functions | en AVENAR panel 2000 | AVENAR keypad 8000 Message transmission to the Remote Portal is stopped until the next restart of the central controller. – To unblock the service, selectUnlock Remote Alert.
Page 88
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Other functions AVENAR panel 2000 | AVENAR keypad 8000 Fire Alarm Fault/supervision alarm Yeah The evacuation is completed automatically. Alarm indication Fault indication The screen switches to Fire evacuation after the...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Reset | is AVENAR panel 2000 | AVENAR keypad 8000 Restore This chapter contains information on how to reset items. During reset, the selected items are restored to their initial state. –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Control/Monitor AVENAR panel 2000 | AVENAR keypad 8000 Control/Monitor This chapter contains information on the following topics: – Activate retainer, control element or HVAC, Page 90 – Go to item, Page 90 –...
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Control/Monitor | en AVENAR panel 2000 | AVENAR keypad 8000 – the mode (e.g., Override, Reset, etc.) the selected item is in. 21.4 Search function To search: 1. From the start menu, selectControl monitoring Search function A list of all functions appears.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Boot menu AVENAR panel 2000 | AVENAR keypad 8000 Boot menu To access the boot menu of an active control panel: 1. Press the power button briefly to shut down the control panel. Wait until the control panel has completely shut down.
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Index | en AVENAR panel 2000 | AVENAR keypad 8000 Index Symbols Switching between status bars "Login" function key Switching language display List fields, CAN ID statuses Accessing the Start Menu Activating Fire...
Page 94
FPA-5000 | FPA-1200 | AVENAR panel 8000 | en | Index AVENAR panel 2000 | AVENAR keypad 8000 Day/night mode, detail display Night mode Input Group, Add Items Input Group, Delete 38, 76 Items Input/Output Group, Rename Test Group Show global event counters...
Page 95
FPA-5000 | FPA-1200 | AVENAR panel 8000 | Index | en AVENAR panel 2000 | AVENAR keypad 8000 Detector Sensitivity Optical/ Acoustic Signals Mute signaling devices activated Mute the internal buzzer Voice alarm system Full VAS over IP Route table "Left arrow"...