GreenConnect
TM
WARNINGS
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes
and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
Before Installation
• Ensure location is within network range.
• Requires single gang device back box.
• Supports multi-gang installations.
• Requires Decora
®
faceplate, sold separately.
• Devices use 0-10VDC low voltage control wires which may be installed as Class 1 or
Class 2.
IMPORTANT NOTE: If installed as Class 2, all devices in the circuit must be Class 2
rated and this switch must be wired per instructions below.
Class 2 Installation:
As required under NEC code NFPA 70, paragraph 725.136 (d) and under Canadian
Electrical Code, section 16-202, the Class 2 0-10V (pink and violet) control wires must be
mechanically separated from Class 1 wiring (line, neutral and ground power lines) when
located within the same electrical box. This is accomplished by installing a mechanical
barrier such as silicone tubing or other non-conducting sleeve over the length of 0-10V
control wires.
When product is used with 120VAC power source and the 0-10V control wires are
connected to CL3, CL3R or CL3P rated control cables (or permitted substitute), then
silicone tubing or other non-conducting sleeve is required over the control wires for the
entire wire length from the device to the location where the wires exit the box. Tubing is
not required on the CL3, CL3R or CL3P between the wire connector and extending out of
the electrical box.
When used with 277VAC power source and the 0-10V control wires are connected to CL3,
CL3R or CL3P rated control cables (or permitted substitute), then silicone tubing or other
non-conducting sleeve is required over the control wires for the entire wire length from the
device to the location where the wires exit the box. Tubing is also required on the CL3,
CL3R or CL3P between the wire connector and extending out of the electrical box.
NOTE:
• Silicone tubing should be NRTL (UL/CSA/ETL) recognized or equivalent to provide
mechanical separation equal to .25 in. in air.
• Connectors joining 0-10V control wires should be approved LISTED CONNECTORS.
• Wire connectors and wire tubing should be provided by the installation contractor.
Installation
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker
or fuse and test that power is off before wiring!
1.
Remove 0.75 in. of insulation from the line and load wires. Remove the precut insulation
from load controller wires and connect according to the wiring diagram. Ensure wires
are firmly connected with no exposed copper.
Connectors
Electrical Box
Hot (Black)
Black
Line
Green
Ground
Neutral (White)
Class 1 installation shown (for Class 2, refer to notes)
White
Blue
Black
Green
Violet
Pink
2.
Gently place the wires and your device into the wall box and attach with
screws provided.
3.
Restore power and test ON/OFF operation. LED locator light should be ON when load
is OFF.
4.
If desired, change switch color.
Wireless 0-10VDC Dimmer
Cat. No. ZB700-D0Z, Ratings: 120-277VAC, 50/60Hz.
Cat. No. ZB700-30Z, Ratings: 347VAC, 50/60Hz.
INSTALLATION INSTRUCTIONS
Violet
Pink
Sleeve
Blue
Black
0-10VDC
White
White
Ballast/LED Driver
Load
Neutral
Line (Hot)
Ground
CAUTIONS
• Use this device with copper or copper clad wire only.
• For indoor applications only.
• Save these instructions.
• To avoid damage to the product, DO NOT use disinfecting products, including
foggers, sprays or other types of atomized cleaning agents. DO NOT spray
liquid onto the product. To clean use a damp cloth with mild soap.
5.
Install Decora faceplate.
To release, push sides.
6.
Enroll Device and configure your system.
PADDLE TOP - ON
BRIGHTNESS INDICATORS
LEDs indicate brightness level.
PADDLE BOTTOM - OFF
LOCATOR LED - on when switch is
off so you can find your control
Catalog Nos.
Input Voltage/Frequency
Input Current
120V
277V
347V
Load Ratings
LED, CFL, Electronic Ballast
@ 120V
LED, CFL, Electronic Ballast
@ 277V
LED, CFL, Electronic Ballast
@ 347V
Magnetic Ballast @ 120V
Magnetic Ballast @ 277V
Magnetic Ballast @ 347V
Resistive, Tungsten @ 120V
Resistive, Tungsten @ 277V
Resistive, Tungsten @ 347V
Motor @ 120V
Motor @ 277V
Motor @ 347V
UL Impulse Voltage
UL Pollution Degree
Operating Temperature
Storage Temperature
IP Rating
Network Connections
Line up and press in to attach.
ROCKER UP - Tap to
raise.
ROCKER DOWN - Tap to
lower.
SPECIFICATIONS
ZB700-D0Z
ZB700-30Z
120-277VAC, 50/60Hz.
347VAC, 50/60Hz.
Standby: 0.2W
Not rated for use
Max: 0.5W+Load Current
Standby: 0.3W
Not rated for use
Max: 0.6W+Load Current
Not rated for use
0.5W + Load Current
8A
Not rated for use
5A
Not rated for use
Not rated for use
4A, 1388VA
10A
Not rated for use
10A
Not rated for use
Not rated for use
3.45A, 1200VA
6.67A
Not rated for use
6.67A
Not rated for use
Not rated for use
6.67A
1/4Hp (FLA 5.8A)
Not rated for use
1/3Hp (FLA 3.0A)
Not rated for use
Not rated for use
1/4Hp
4000V
6000V
2
32°F - 104°F (0°C - 40°C)
-40°F - 185°F (-40°C to 85°C)
IP10
IEEE 802.15.4, 2.4Ghz, wireless, mesh network up to 75'
range between device
DI-000-ZB700-02A-W