4 | Compressor assembly
INFO
4.1 Setting up
Storage at (-40°C) - (+100°C), maximum permissible relative Humid-
ity 10% - 95%, no condensation
Fittings (e.g. pipe holders, additional units etc.) on the compressor are
permissible only following consultation with Bock.
Setup on an even surface or frame with sufficient load-bearing capac-
ity. Use all 4 fastening points.
Correct setup of the compressor and mounting of the belt drive are
decisive for running comfort, operating safety and the service life of
the compressor.
In the condition on delivery the compressor is provided with installa-
tion feet (see Fig. 4). Alternatively the compressor can also be bolted
directly, without installation feet, on the substructure.
4.2 Maximum permissible inclination
ATTENTION Poor lubrication can damage the compressor. Respect the stated
A
a
Fig. 5
© Danfoss | Climate Solutions | 2025.04
New compressors are factory- lled with inert gas. Leave this ser-
vice charge in the compressor for as long as possible and prevent
the ingress of air.
Check the compressor for transport damage before starting any
work.
values.
A
A
a
A
a
a
AQ450641889580en-000402 | 9
Fig. 4
max. 30°,
A
max. 2 minutes
max. 15°,
a
continuous