SICK MLG-2 ProNet Operating Instructions Manual
SICK MLG-2 ProNet Operating Instructions Manual

SICK MLG-2 ProNet Operating Instructions Manual

Measuring automation light grid with profibus fieldbus
Table of Contents

Advertisement

Quick Links

O P E R A T I N G I N S T R U C T I O N S
MLG-2 ProNet
Measuring automation light grid with
PROFIBUS fieldbus

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MLG-2 ProNet and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SICK MLG-2 ProNet

  • Page 1 O P E R A T I N G I N S T R U C T I O N S MLG-2 ProNet Measuring automation light grid with PROFIBUS fieldbus...
  • Page 2 This document is an original document of SICK AG. 2006/42/EC SAFETY O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 3: Table Of Contents

    Transparent operating mode........... 3.8.3 Dust- and sunlight-resistant operating mode......8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 4 Parameters for definition of operating mode and perform‐ ance options................O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 5 10.2 SICK support..................... 153 10.3 LED indicators and error indicators............153 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 6 List of figures..................174 List of tables..................177 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 7: About This Document

    Highlights useful tips and recommendations as well as information for efficient and trouble-free operation. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 8: Abbreviations Used

    Run-length code SOPAS Device Description Programmable logic controller O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 9: Safety Information

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 10: Qualification Of Personnel

    • knowledge of the applicable regulations and standards O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 11: Product Description

    01: Standard (DPV1) nections and software 02: For replacement (DPV0) 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 12: Monitoring Height

    • Without optics ± 10 ° (at a range of 2.5 m and 5 m) O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 13: Preconfigurations

    The receiver consists of receiver optics, several receiver elements (photodi‐ odes) and evaluation electronics. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 14: Device Components Of The Mlg-2

    PC/notebook, a connection for the power supply, and a connection for the receiver. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 15: Measurement Principle

    Figure 6: Schematic representation of available beam separations (mm) 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 16: Sensing Ranges

    During the teach-in process, the switching thresholds for all beams are individually adjusted for the sensing range and the ambient conditions. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 17: Beam Blanking

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 18: Response Time, Minimum Presence Time And Reproducibility Of The Mlg-2

    When the cross-beam function is enabled, the light beam from a sender LED is received by three receiver diodes in two scans. This doubles the scan time. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 19: Scan Time With High-Speed Scan On The Mlg-2

    Figure 12: Scan time in relation to the number of beams when using the high-speed scan 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 20: Beam Separation And Minimum Detectable Object

    10 mm 14 mm 20 mm 24 mm 25 mm 29 mm 30 mm 34 mm O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 21: Minimum Detectable Object Length

    SOPAS ET on the MLG-2 (see "Interface", page 95). 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 22: Minimum Detectable Object With Cross-Beam Function

    50 mm – – 1110 mm 1200 mm 1,200 m 29 mm 54 mm O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 23: Minimum Detectable Object With High Measurement Accuracy From The Mlg-2

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 24: Operating Reserve

    Transparent operating mode enables the detection of transparent objects, such as those made of glass, PET, etc. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 25: Dust- And Sunlight-Resistant Operating Mode

    Examples are for illustrative purposes only. The signal attenuation and the minimum detectable absorption to be configured must be determined for each individual application. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 26: Interfaces

    Alarm Q1 Defines various diagnostic settings for Q1 – O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 27 The cloning status shows the status of the stored parameters in the fieldbus module. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 28: Available Process Data

    The MLG-2 provides a series of process data. The following table shows which process data is available for the individual applications. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 29 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 30: Display And Operating Elements

    153 explains the meaning of the LED indicators. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 31: Receiver

    Figure 18: LEDs on the front and on the control panel Yellow Green Alignment LED 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 32: Fieldbus Module

    153 explains the meaning of the LED indicators. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 33: Application Examples

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 34 Figure 26: Volume measurement Figure 27: Contour measurement O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 35: Mounting

    6 x FlexFix brackets for monitoring heights above 2 m. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 36: Mounting With Light In The Same Direction

    Minimum distance of the MLG-2 Minimum distance of the MLG-2 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 37 MLG-2 with 5 m, 8.5 and 14.5 m sensing range 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 38: Placement Of Two Light Grids At Right Angles

    Figure 32: Placement of two light grids at right angles O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 39: Minimum Distance From Reflective Surfaces

    This minimum distance depends on the distance between sender and receiver and on the operating range. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 40: Mounting Procedure

    Applies to specular surfaces perpendicular to the housings Applies to specular surfaces parallel and perpendicular to the housings O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 41: Mounting The Quickfix Bracket

    QuickFix bracket and the machine or profile frame. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 42 If you are using the QuickFix bracket, you will need one more QuickFix bracket for the fieldbus module. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 43: Mounting The Flexfix Bracket

    A screw nut or threaded hole is required on the machine or profile frame. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 44 If you are using the FlexFix bracket, you will need a mounting bracket for the fieldbus module. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 45: Turning The Fieldbus Module On The Mlg-2

    180° so you can feed the cables in from the front or the back. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 46 Insert the fieldbus module again Tighten the mounting screw O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 47: Mounting The Fieldbus Module Offset From The Mlg-2

    The maximum length of cable between the MLG-2 receiver and the FBM fieldbus module/AFB connection box must not exceed 2.7 m. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 48: Electrical Installation

    T-distributor in order to connect the sender and receiver via a short synchronization cable wherever possible. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 49: Fieldbus Module Connections

    Signal Meaning Ethernet Ethernet TX– Ethernet RX– Ethernet 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 50 - ros gra/pnk - blk red/blu - vio O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 51: Sender Connections

    Blue Test_In Test input Black Sync_B Synchronization Gray 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 52: Connecting The Mlg-2

    Sender Receiver Fieldbus module T-distributor Voltage supply Fieldbus O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 53 1 and the test input. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 54 GND supply voltage Switching output 1 Not connected Not connected O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 55: Commissioning

    • Adjust vertically (H) • Rotate (±15°) 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 56: Alignment And Teach-In

    The yellow LED on the front of the receiver and the Alignment LED show the rough alignment. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 57 .Teach-in can also be triggered via SOPAS ET or the PLC. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 58: The Mlg-2 On The Profibus Network

    Communication takes place via PROFIBUS Read/Write Record Indication and Record Response. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 59: Addressing

    30). You can use these DIP switches to set the address for the MLG-2. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 60 In the Address configuration area, you can enter the address in the PROFIBUS. You can enter an address from 1 to 125 for the MLG-2. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 61: Gsd File

    BOOL Boolean = logical value 0 or 1 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 62 UINT-16 FBB Zone 3 – First beam blocked in Zone 3 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 63 “Find Me” function BOOL Pushbutton lock BOOL Beam numbering 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 64: Cyclic Data (Process Data)

    Cyclic data (process data) Specify the required modules for the cyclic process data. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 65: Modules With Beam Functions

    This module transfers the number of the first beam blocked. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 66: Beam Function Fbb

    • The count direction of the beams depends on the configured beam numbering. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 67: Beam Function Lbb

    The beam function facilitates the object measurement of a hanging object, for example. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 68: Beam Function Ncbb

    If there are several gaps of the same size in the detection area, the gap with the lowest-value beam is used for the measurement. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 69: Beam Function Cbb

    This module transfers the outside dimension of an object. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 70: Beam Function Odi

    Objects such as pallet cages are not suitable as they involve too many status changes. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 71 31h: beam 33 – 64. … 3Fh: beam 481 – 512. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 72 Zone 2 beams blocked in Zone 2. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 73 UINT-16 User defined 3 UINT-16 User defined 4 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 74: Modules With System Information

    If the received values are getting worse, the process quality drops. Possible causes of a drop in process quality include: O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 75: Modules For Initiating Operating Functions

    8-bit length. Use the FBM-P22 for complete compatibility. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 76 This module transfers the number of the first beam made. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 77 This module transfers the inside dimension of an object. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 78: Acyclic Data (Service Data)

    If an additional teach-in is to be initiated, this index must first be described using 0. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 79 Activate the Teach-in with blanking function. Perform a teach-in. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 80: Example Of The Blanking Of Blocked Beams

    0. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 81: Example Of Blanking Made Beams

    Figure 70: Bit-coded beam mask for an MLG-2, with 30 beams 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 82: Parameters For Definition Of Operating Mode And Performance Options

    "Minimum detectable object with parallel-beam function", page 20). O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 83 Operator = 1; equates to ≥ Operand 2 = 30 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 84 Beam number of the last beam blocked in Zone 1 (e.g., for object height measurement) O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 85 User defined 3 User defined 4 User defined 4 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 86: Parameters With Auxiliary Resources And Diagnostic Options

    0 = alignment aid not active 1 = alignment aid active O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 87: Beam Numbering

    MLG-2 so that the beam numbering begins at the top. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 88 A teach-in is required. All functions become available again only after a ° successful teach-in process. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 89 ACTIVE: An upload or download is currently active. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 90: Parameters With System Information

    Entering a mounting location makes it easier to identify where the MLG-2 is mounted. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 91: Beam Evaluation

    For additional information, see "Function Zone measuring", page 125 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 92 1: BBH mode active 2: LBH mode active O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 93 Byte 26: NCBB/CBB Zone 3 Byte 27: NCBB/CBB Zone 4 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 94: Configuration With Sopas Et

    If you configure a device offline, you must then connect the PC to the MLG-2 and download the MLG-2 configuration. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 95: Operation Sopas Et

    For users with experience or more complex requirements, the function level EXPERT is available, where all parameters can be configured. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 96: Display Of The System Boundaries

    SOPAS ET displays the maximum recommended sensing range with which the MLG-2 can be safely operated. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 97: Wizards

    Under Basic functions, you will find the following information: 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 98: Detection Area - Simulation

    Representation of the detection area Figure 78: Detection area – Simulation O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 99: Combining Beams Into Zones

    > For object recognition > Use Qx. Figure 80: Using beams for object recognition 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 100: Using Beams For Height Classification

    In the context menu, select the command Blank all selected beams. ► O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 101 In the context menu, select the command Device orientation > rotate left or > rotate ► right. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 102: Image Of The Mlg-2 Rotated

    To close the expandable menu, click the double arrow – which is now inverted – ► again. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 103: User Level

    The current user level is displayed in the Log in panel. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 104 Under Devices , select the Change password menu item ... Follow the input screwwn and confirm the change using the Change passwordbut‐ O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 105 Now enter the password for the selected user level. Confirm the password with OK 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 106: Connection Via Sopas Et

    To log in via the project view, use Login on the corresponding tile. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 107: Service Settings (Service User Level)

    SOPAS ET is no longer possible. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 108: System Settings

    Locked: The teach-in button is locked to prevent inadvertent actuation, for exam‐ ple. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 109: I/O Configuration

    You can use the pushbutton lock to set two options for the teach-in button on the device: 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 110: Measuring And Diagnostic Functions For Switching Outputs

    MLG2. If the criteria configured for the function are met, this is signaled on the relevant output. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 111: Height Classification

    Applies when light grid is mounted upright with the connection side facing down and beam numbering beginning on the connection side (factory setting). 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 112: Settings For Height Classification

    For additional information, see "Function Zone measuring", page 125 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 113: Object Recognition

    This also applies to multiple objects, e.g., the feet of a pallet. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 114: Object Recognition, Static

    Figure 101: Object recognition, dynamic O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 115: Object Detection/Object Width

    The number of beams is configured in the settings or configured graphically in the Simulation area using the mouse. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 116 Figure 104: Setting the object size with the mouse O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 117: Hole Detection/Hole Size

    Select one of the following settings for the hole detection and enter the number of ► n beams: 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 118 Figure 107: Setting the hole size with the mouse O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 119: Outside/Inside Dimension

    Configure whether you want to measure the outside dimension or inside dimension. ► 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 120: Measurement Of The Outside Dimension

    "Advanced settings for the outputs", page 124. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 121: Classification Of An Object Position

    The object center is equal to the position of beam number n. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 122: Classification Of A Hole Position

    The number of the beam located in the center of the hole is greater than or equal to the number of the configured beam. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 123 The hole position that has been set is shown in the Simulation area. It can be changed using the mouse. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 124: Diagnostics

    Advanced settings for the outputs For switching outputs, you can select the option Invert output. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 125: Zones

    Zone n are available for each zone (n = 1, 2, 3 or 4). 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 126: Measuring Within Zones

    ✓ The configured zones are indicated in the Zones expandable menu. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 127: Sopas Et - Assigning An Application And Zone To An Output

    I/O tab in the Basic functions area. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 128: Teach-In

    MLG-2 calculates this value based on the quality of the light level received. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 129: Example Of The Blanking Of Blocked Beams

    You will never be notified that beams are blocked during the teach-in process. Blank made beams as follows: 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 130: Switching Thresholds From Material Teach-In

    O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 131: Selection Of Switching Thresholds From Material Teach-In In Installation Wizard

    Confirm the selection with Next. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 132: Selection Of Application Situation

    "Minimum transmission difference for switching thresholds from material teach-in", page 164. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 133: Selection Of Relevant Rays

    For the best possible result, carry out a final teach-in by clicking on Next (recom‐ mended). 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 134: Summary Of The Determined Transmissions With A Positive Result

    Cancel pushbutton. Figure 133: Summary of the determined transmissions with a negative result O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 135: Performance Options

    (in transparent mode) the minimum attenuation of an object. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 136 SOPAS ET (see "System boundaries and status", page 96). O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 137 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 138: Illustration Of The Measuring Object

    In order to detect a transparent object, it must absorb a certain percentage of the energy from the light beam. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 139: Cross Beamfunction

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 140 ✓ The Cross beam switching function is activated. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 141: Soaps Et - Activating Cross Beam Switching

    Cross beam measuringfunction. Adjust the configuration accordingly. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 142: Sopas Et - Activating Cross Beam Measuring

    Adjust the configuration for the cross beam measuring function. ► O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 143: Energy Option (Only In Expert Function Level)

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 144: Lost Beams Hold (Lbh) Evaluation Mode

    Lost Beams Hold (LBH) evaluation mode Prerequisites Expert function level ■ O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 145: Simulation

    Click on the plus sign to add a simulation object. ► 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 146: Start Simulation

    Figure 144: Determine the size of the simulation object Click Start simulation. ► O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 147: Beam Monitor (Only In Expert Function Level)

    Figure 147: Beam status 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 148: Function Programming (In Expert Function Level)

    Easy function level, these settings are automatically transferred to the Funktionsprog‐ rammierung view. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 149 CONFIGURATION WITH SOPAS ET Figure 148: Function programming 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 150: Beam Functions

    4) zone O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 151 4) object position) in the indicated zone 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 152: Servicing

    Perform the teach-in process on the MLG-2 again. To do this, press the Teach ► pushbutton. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 153: Troubleshooting

    Ö 10 Hz blocked Hardware error Synchronization error Short-circuit 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 154: Advanced Diagnostics On The Mlg-2

    The STATUS LED follows the respective fieldbus specification O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 155: Decommissioning

    • A description of the fault that occurred 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 156: Technical Data

    • < 3 V Maximum output current per output 100 mA O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 157 In Dust- and sunlight-resistant operating mode: 3 m / 5 m depending on device type. Depending on device version and operating mode. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 158: Fieldbus Module Data Sheet

    • • Typical 115 mA • Maximum • < 160 mA O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 159 Table 130: Fieldbus module data sheet - PROFIBUS interface Data transmission rate Autobaud, 9,600 kbit/s to 12 Mbit/s 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 160: Diagrams

    If the cross-beam function is configured, multiply the minimum presence time and the response time by 2. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 161: Response Time And Minimum Presence Time For Highspeed Scan With 2.5 Mm Raster

    SDD, especially for 2.5 mm raster devices. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 162: Response Time And Minimum Presence Time During High-Speed Scan With Up To 3.5 M Sensing Range

    Figure 152: Response time and minimum presence time up to 8.5 m sensing range O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 163: Minimum Attenuation In Transparent Mode

    8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 164: Minimum Transmission Difference For Switching Thresholds From Material Teach-In

    The minimum transmission difference increases due to signal reduction, e.g. due to contamination or an increasing working distance. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 165: Dimensional Drawings

    A + B see table 132, page 166 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 166: Measurement Tables

    88.3 mm 16.1 mm 50 mm 108.3 mm 16.1 mm see table 131. O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 167: Dimensional Drawings For The Mlg-2 Fieldbus Module

    Figure 157: Dimensional drawing 1 MLG-2 fieldbus module 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 168 Openings for mounting pins DIP switch cover fixing screw O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 169: Ordering Information

    Ordering information for the MLG-2 can be found in the MLG-2 product information, SICK part number 8017054. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 170: Accessories

    5 m, shielded, 5- 2095733 wire 5-pin, straight, PUR / 5*0.34 / BK A-coded O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 171 Open flying leads 10 m, 5-wire, 6026008 pin, straight 0.34 mm² 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 172 6056903 pin, straight pin, straight shielded, PUR, halogen-free O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 173: Annex

    Printed copies of the license texts are also available on request. 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 174: List Of Figures

    53. Address configuration in SOPAS ET................61 54. Beam function NBB....................65 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 175 111. Setting the outside dimension with the mouse............120 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 176 157. Dimensional drawing 1 MLG-2 fieldbus module............ 167 158. Dimensional drawing 2 MLG-2 fieldbus module............ 168 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK...
  • Page 177: List Of Tables

    53. Beam status........................ 71 54. Beam functions for Zone measuring................. 72 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 178 110. Zone measuring......................92 111. Cross beam measuring....................92 O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK Subject to change without notice...
  • Page 179 141. Part number for MLG-2 connection cable to fieldbus module......172 8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet Subject to change without notice...
  • Page 180 Phone +65 6744 3732 Phone +30 210 6825100 Phone +65 6744 3732 E-Mail sales.gsg@sick.com E-Mail office@sick.com.gr E-Mail sales.gsg@sick.com Hong Kong Slovakia Phone +852 2153 6300 Phone +421 482 901 201 E-Mail ghk@sick.com.hk E-Mail mail@sick-sk.sk Detailed addresses and further locations at www.sick.com SICK AG  |  Waldkirch  |  Germany  |  www.sick.com...