Digital input module
Short guide
1. Overview
MV210-212/214 is an extension module with 32 digital inputs.
The module operates as a slave in Ethernet network with Modbus TCP
protocol.
The device is intended for use in industrial automation for creation of
decentralized control systems.
2. Environmental conditions
Table 1 Operating conditions
Permissible range
Condition
Ambient temperature
Transportation and storage
Relative humidity
up to 95 % (at +35 °C, non-condencing)
up to 2000 m ASL
Attitude
IP code
Vibration / shock resistance
conforms to IEC 61131-2
EMC emission / immunity
conforms to IEC 61131-2
3. Specifications
Table 2 General specifications
Electrical
Power supply
Power consumption
Polarity protection
Appliance class
Interfaces
Double Ethernet 10/100 Mbps
Data transfer
Protocols
Configuration interface
Digital inputs of MV210-212
Inputs number
contact sensor (requires external
Input signal
high frequency pulses counter
frequency measurement (only
Functions
encoder signal processing (up to
Pulse length, min, (DI1-8)
Pulse length, min, (DI9-20)
LOW level (current), max.
MV210-212/214_3-EN-61905-3.1
© All rights reserved. Subject to technical changes and misprints.
HIGH level (current). max.
LOW level (voltage range).
HIGH level (voltage range)
Inputs number
Input signal
Functions
Pulse length, min.
Input lines (loop) resistance, min.
File size, max.
Number of log files, ,max.
-40...+55 °C
Logging interval, min.
Accuracy
IP20
Backup battery
Dimensions
Weight
4. Installation and connection
Before installation make sure there is enough free space for connecting
24 (10 ... 48) V DC
the module and placing the wires. The module is mounted on a DIN rail
6 W at 24 V DC
or on a vertical surface using screws.
Yes
Installation of external connections is carried out by a wire with a cross
section of not more than 0.75 mm
II
For stranded wires, use end sleeves.
After installation, put the wires into the cable channel of the module
Modbus TCP
housing and close the cover.
MQTT
If necessary, in order to remove the terminal blocks of the module, loosen
SNMP
the two screws at the corners of the terminal blocks.
NTP
USB 2.0 (MicroUSB)
CAUTION
Ethernet 10/100 Mbps
Connection and maintenance is performed only when the
module power and the power to all devices connected to it is
turned off.
32
Table 3 Network parameters
24 V power supply)
Parameter
NPN / PNP transistor
IP address
AB encoder
logical level detection
Subnet mask
Gateway
(only DI1-DI8)
DNS server 1
DI1-DI8)
DNS server 2
3 encoders)
5 µs (up to 100 kHz)
1 ms (up to 400 Hz)
1.2 mA
MV210-212/214
Digital input module
5.5 mA
0.0...6.1 V
8.8...30.0 V
Digital inputs of MV210-214
32
Switch contact (potential free)
NPN transistor
Pulse counter
Logical level detection
1 ms (f ≤ 400 Hz)
100 Ω
Flash-memory (log file storage)
2 kB
1000
10 s
Real time clock
±3 s/day at +25 °С
±10 s/day at -40 °С
CR2032
Mechanical
42 × 124 × 83 mm
approx. 260 g
2
.
Description
Default value
IPv4 Internet Protocol address
192.168.1.99
IP address recognition area in the
255.255.255.0
subnet
IP address of the gateway
192.168.1.1
Primary DNS server
77.88.8.8
Secondary DNS server
8.88.8.8
5. Electrical connection
Fig. 1 Terminal block layout
Table 4
Terminal assignments
Marking
DI1...DI20
Input terminals
COM (MV210-214)
Common input power supply point
SS (MV210-212)
The service button performs the following functions:
• Factory settings restore
• IP-address assignment
Fig. 2 Device connectors
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany