NOTICE indicates a potentially dangerous situation that could result in damage to property. NOTE NOTE indicates helpful tips and recommendations, as well as information for efficient and trouble-free operation. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Failure to obey these warnings could result in personal injury or equipment damage. Akytec company shall not be liable for technical or editorial errors or omissions contained in this document. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Connection, adjustment and maintenance of the device must be carried out only by qualified personnel after reading this operating manual. Device designation when ordering: МV210-212 and МV210-214. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
– For МV210-212: contact sensor, npn and pnp transistors. – For МV210-214: dry contact sensor, npn transistor. The Module is intended for use in industry and agriculture. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
The electrical strength of the supplementary insulation is insulation (SI) checked by type tests: by applying an alternating test AC voltage of various levels (RMS value) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
The resistance to climatic influences during the operation of Device is in accordance with IEC 61131-2. Module is class II equipment in accordance with IEC 61131-2. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Fig. 3.2 Improper installation CAUTION During installation, a free space of 50 mm above and below the module is required. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
The connectors of the interfaces and the power supply of the device are shown in the figure below. Fig. 4.1 The device's connectors akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Using power supplies without potential isolation or with basic isolation of low voltage circuits from AC lines can lead to dangerous voltage in the circuits. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
2. Connection is possible to any Ethernet port of the module. 3. The unused Ethernet port must be closed with a blanking plug. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 19
2. An adjacent connection scheme is allowed. 3. The unused Ethernet port should be closed with a blanking plug. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Data transfer via Ethernet port Eth 2 (green) Flashing Normal operation Fault (red) Main application and / or configuration failure akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
As a string of HEX characters with leading the parameter zeros string 1 byte Separator Character ";" (without quotes) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 22
If in response to the request a message is received with error code 0x04 (MODBUS_SLAVE_DEVICE_FAILURE), then you can conclude that the addresses of the registers akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Read only 61568 0xF080 UINT 32 (UTC) since 2000 (s) New time 61565 0xF07D Read and write UINT 32 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 24
Additional mode 2 – period 0х41 Read and write UINT 16 for Input DI2* measurement; 3 – frequency measurement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 25
4 – encoder signal processing 0 – off; Debounce filter 0х60 Read and write UINT 16 for input DI1* 1 – on akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 26
1 – on 0 – off; Debounce filter 0х76 Read and write UINT 16 for input DI23* 1 – on akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 27
1 – 100 ms; 0х86 Read and write UINT 16 for input DI7* 2 – 1 s; akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 28
(pulses) – mode Value on input Read only DI5 in additional 0xA8 UINT 32 mode* 10…4294967295 (ms) – mode 2 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 29
(pulses) DI12 Value of pulse 0...4294967295 Read only counter on input 0хB8 UINT 32 (pulses) DI13 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 30
0хD8 UINT 32 (pulses) DI29 Value of pulse 0...4294967295 Read only counter on input 0хDA UINT 32 (pulses) DI30 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 31
Reset pulse 0 – reset counter on input 0хEC Read and write UINT 16 1 – do not reset DI13 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 32
Reset pulse 0 – reset counter on input 0хFD Read and write UINT 16 1 – do not reset DI30 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
21 (0x15) Writing log to file RECORD Situations leading to errors during operation with registers are described in Table 5.8. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 34
– could not open the file for reading (it may be missing) MODBUS_ILLEGAL_ – could not move to the desired offset DATA_VALUE in the file akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
– encoder signal processing (see Section 5.6.4). Up to 3 encoders can be connected. NOTICE Only one additional operation mode can be switched on at one input. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
If the counter overflows, the value is reset. To force a counter reset, write 0 to input value reset register. The counter will be reset within 10 ms after writing the value 0. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
If the IP address assignment with service button does not work, set the DHCP mode to One- off setting with service button in the akYtecToolPro program (default setting). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
A restart of the Module is required to complete the update. If the Module is connected via USB, it must also be disconnected. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
If the input state counter overflows, then the corresponding register is reset automatically. To force the counter to zero, write the value 0 to the counter reset register. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
When loosening the fastening screws, the terminal block rises, so it is recommended to unscrew the screws by turns several turns at a time. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 42
7. Alternately remove the hooks from the holes on the both sides of Module and remove the top cover. Fig. 7.3 Battery replacement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 43
After the Module is assembled and turned on, make sure that the system time is correct. If necessary, configure the real-time clock in the akYtecToolPro program. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH! akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Power supply terminal 2EGTK-5-02P-14 Ethernet blanking plug NOTICE The manufacturer reserves the right to introduce amendments to the scope of delivery. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...