MV210-212/214
Digital input module
User guide
MV210-212/214_3-EN-59115-1.8
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MV210-212 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Akytec MV210-212

  • Page 1 MV210-212/214 Digital input module User guide MV210-212/214_3-EN-59115-1.8 © All rights reserved Subject to technical changes and misprints akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 2: Table Of Contents

    7 Maintenance ........................40 7.1 General Instructions ....................40 7.2 Battery replacement ....................40 8 Transportation and storage ....................43 9 Scope of delivery ......................44 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 3 Appendix A Encrypting the log file ..................45 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 4: Warning Notice System

    NOTICE indicates a potentially dangerous situation that could result in damage to property. NOTE NOTE indicates helpful tips and recommendations, as well as information for efficient and trouble-free operation. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 5: Abbreviations

    – UTC – coordinated universal time. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 6: Safety

    Failure to obey these warnings could result in personal injury or equipment damage. Akytec company shall not be liable for technical or editorial errors or omissions contained in this document. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 7: Introduction

    Connection, adjustment and maintenance of the device must be carried out only by qualified personnel after reading this operating manual. Device designation when ordering: МV210-212 and МV210-214. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 8: Overview

    – For МV210-212: contact sensor, npn and pnp transistors. – For МV210-214: dry contact sensor, npn transistor. The Module is intended for use in industry and agriculture. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 9: Specifications

    1 ms Resistance of contacts (switch) and connecting wires connected to a discrete 100 Ω input, max. Flash-memory (log-file) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 10: Isolation Of The Device Components

    The electrical strength of the supplementary insulation is insulation (SI) checked by type tests: by applying an alternating test AC voltage of various levels (RMS value) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 11: Environmental Conditions

    The resistance to climatic influences during the operation of Device is in accordance with IEC 61131-2. Module is class II equipment in accordance with IEC 61131-2. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 12: Installation

    Fig. 3.2 Improper installation CAUTION During installation, a free space of 50 mm above and below the module is required. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 13 3 Installation Fig. 3.4 Mounting dimensions Fig. 3.3 Dimensions akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 14: Connection

    The connectors of the interfaces and the power supply of the device are shown in the figure below. Fig. 4.1 The device's connectors akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 15: Power Supply

    Using power supplies without potential isolation or with basic isolation of low voltage circuits from AC lines can lead to dangerous voltage in the circuits. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 16: Electrical Connection

    Fig. 4.3 Terminal block layout Table 4.1 Contact function Marking Description DI1–DI32 Inputs DI1-DI32 COM (for MV210-214) Common input point SS (for MV210-212) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 17: Contact Sensors

    Fig. 4.7 Connection of NPN transistors (only for MV210-212) for MV210-212) Fig. 4.8 Connection of NPN transistors (only for MV210-214) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 18: Pnp And Npn Encoders

    2. Connection is possible to any Ethernet port of the module. 3. The unused Ethernet port must be closed with a blanking plug. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 19 2. An adjacent connection scheme is allowed. 3. The unused Ethernet port should be closed with a blanking plug. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 20: Operation

    Data transfer via Ethernet port Eth 2 (green) Flashing Normal operation Fault (red) Main application and / or configuration failure akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 21: Real Time Clock

    As a string of HEX characters with leading the parameter zeros string 1 byte Separator Character ";" (without quotes) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 22 If in response to the request a message is received with error code 0x04 (MODBUS_SLAVE_DEVICE_FAILURE), then you can conclude that the addresses of the registers akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 23: Data Exchange Modes

    Read only 61568 0xF080 UINT 32 (UTC) since 2000 (s) New time 61565 0xF07D Read and write UINT 32 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 24 Additional mode 2 – period 0х41 Read and write UINT 16 for Input DI2* measurement; 3 – frequency measurement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 25 4 – encoder signal processing 0 – off; Debounce filter 0х60 Read and write UINT 16 for input DI1* 1 – on akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 26 1 – on 0 – off; Debounce filter 0х76 Read and write UINT 16 for input DI23* 1 – on akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 27 1 – 100 ms; 0х86 Read and write UINT 16 for input DI7* 2 – 1 s; akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 28 (pulses) – mode Value on input Read only DI5 in additional 0xA8 UINT 32 mode* 10…4294967295 (ms) – mode 2 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 29 (pulses) DI12 Value of pulse 0...4294967295 Read only counter on input 0хB8 UINT 32 (pulses) DI13 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 30 0хD8 UINT 32 (pulses) DI29 Value of pulse 0...4294967295 Read only counter on input 0хDA UINT 32 (pulses) DI30 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 31 Reset pulse 0 – reset counter on input 0хEC Read and write UINT 16 1 – do not reset DI13 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 32 Reset pulse 0 – reset counter on input 0хFD Read and write UINT 16 1 – do not reset DI30 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 33: Error Codes For Modbus Protocol

    21 (0x15) Writing log to file RECORD Situations leading to errors during operation with registers are described in Table 5.8. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 34 – could not open the file for reading (it may be missing) MODBUS_ILLEGAL_ – could not move to the desired offset DATA_VALUE in the file akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 35: Digital Inputs Operation Modes

    – encoder signal processing (see Section 5.6.4). Up to 3 encoders can be connected. NOTICE Only one additional operation mode can be switched on at one input. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 36: Logic Level Detection

    If the counter overflows, the value is reset. To force a counter reset, write 0 to input value reset register. The counter will be reset within 10 ms after writing the value 0. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 37: Configuration

    1. In the drop-down menu, select the akYtec Auto Detection Protocol. Fig. 6.2 Select Protocol 2. Select Find device. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 38: Configuring Network Settings

    If the IP address assignment with service button does not work, set the DHCP mode to One- off setting with service button in the akYtecToolPro program (default setting). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 39: Module Access Password

    A restart of the Module is required to complete the update. If the Module is connected via USB, it must also be disconnected. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 40: Real-Time Clock Setting

    If the input state counter overflows, then the corresponding register is reset automatically. To force the counter to zero, write the value 0 to the counter reset register. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 41: Maintenance

    When loosening the fastening screws, the terminal block rises, so it is recommended to unscrew the screws by turns several turns at a time. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 42 7. Alternately remove the hooks from the holes on the both sides of Module and remove the top cover. Fig. 7.3 Battery replacement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 43 After the Module is assembled and turned on, make sure that the system time is correct. If necessary, configure the real-time clock in the akYtecToolPro program. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 44: Transportation And Storage

    Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH! akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 45: Scope Of Delivery

    Power supply terminal 2EGTK-5-02P-14 Ethernet blanking plug NOTICE The manufacturer reserves the right to introduce amendments to the scope of delivery. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 46 (!str) break; temp.hi += (unsigned char) (*str); temp.hi –= (temp.hi << 13) | (temp.hi >> 19); str++; return temp.hilo; akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...