Regudis W-CE Table of contents Page General information ......................6 Validity of the instructions ........................6 Scope of delivery ............................ 6 Contact ..............................6 Symbols used ............................6 Safety-related information ....................6 Normative guidelines ..........................6 Intended use ............................6 Modifications to the product ........................6 Warnings ..............................
Page 4
Regudis W-CE Table of contents Page Venting the circulation pipe (if available) ....................22 Setting the shutoff valves for operation ....................23 Setting the hot water temperature ......................23 7.5.1 Sliding hot water temperature control ....................... 23 Setting the derivative temperature control set (if available) ..............23 Teaching-in the actuator ........................
German. Action required • Validity of the instructions List These instructions are valid for the Regudis W-CE dwelling Fixed order. Steps 1 to X. station in the following configuration levels: Dwelling station with Result of action Performance range...
Regudis W-CE Safety-related information Safety instructions Warning symbol SIGNAL WORD We have developed this product in accordance with Type and source of danger! current safety requirements. Possible consequences if the danger occurs or the Observe the following instructions for safe use.
Regudis W-CE Safety-related information • Wear suitable protective clothing to avoid The temperature of the potable water in the cold water pipeline must not exceed 25 °C. unprotected contact with hot fittings and system • components. The water in the potable water circuit must be completely replaced after 72 hours at the latest.
Regudis W-CE Technical description 3. Technical description Design Fig. 2: Overview of the Regudis W-CE dwelling station Heat exchanger Control valve with integrated differential pressure and volume flow control Vent valve in the heating circuit Rotary knob Actuator with integrated potable water temperature...
Hot water outlet (19). This offers you the possibility to close the zone valve time-controlled. Heating circuit return The Regudis W-CE dwelling station is available in different performance ranges and versions (see charts in the Heating circuit supply appendix). Primary supply from the buffer storage cylinder The performance ranges differ in terms of the size of the heat exchanger.
Regudis W-CE Technical description The control valve remains completely open until you turn Cold water outlet the rotary knob back to the desired hot water temperature (< 70 °C). Cold water inlet from the house connection Technical data Actuator with integrated potable...
Page 12
Regudis W-CE Technical description Max. volume flow 460 l/h Temperature sensor ((15) 15 Nm in Fig. 2 on page 9) Differential pressure 150 mbar control Filter insert ((16) in Fig. 2 15 Nm on page 9) Potable water circuit Drain valve ((12) in Fig. 2 15 Nm Potable water (see...
Page 13
Regudis W-CE Technical description Fig. 6: Dimensions Item no. Dwelling station with cold water outlet and spacer for water meter, 26.5 performance range 1 Dwelling station with cold water outlet and spacer for water meter, 26.5 performance range 2 Dwelling station without cold water outlet and spacer for water meter, 26.5...
Page 14
Regudis W-CE Technical description Fig. 7: Connection assignment Hot water outlet Heating circuit return Heating circuit supply Primary supply from the buffer storage cylinder Primary return to the buffer storage cylinder Cold water outlet Cold water inlet from the house connection...
Regudis W-CE Accessories and spare parts 4. Accessories and spare parts Accessories Designation Item no. Connection and shutoff set for the potable water 1344684 circulation module Potable water circulation 1344555 module Derivative temperature 1344490 control set Stainless steel spacer 1349052...
Page 16
Regudis W-CE Accessories and spare parts Fig. 8: Spare parts Actuator with integrated potable water temperature control Power supply unit 100 - 240 V, ~50 - 60 Hz (in connection box) Volume flow sensor in a housing Filter insert Sealing ring (5 pieces for G ¾ connections) Sealing ring (5 pieces for G 1 connections)
Regudis W-CE Transport and storage 5. Transport and storage For the electrical connection, observe chapter 5.3.2 of EN60204-1. Transport the product in its original packaging. Store the product under the following conditions: • Mount the station in a dry, frost-free room in which the ambient temperature does not exceed 35 °C...
Regudis W-CE Mounting Position the angle ball valves so that the supply pipes (see Fig. 9 on page 17 (2)) can be routed to the dwelling station from the desired direction. Mount the two angle ball valves (see Fig. 9 on page 17 (3)) with flat seal in an orientation that is easily accessible for further connection.
Regudis W-CE Mounting meter in the primary supply. Screw the adapter into the connection in the primary supply (2). Screw the temperature sensor into the adapter. Slowly open the angle ball valves in the primary return (5) and primary supply (2). Open the vent valve (8) slightly.
Regudis W-CE Mounting The water meter is mounted. Connecting the dwelling station electrically DANGER Danger to life due to electric current! There is a danger to life if live components are touched. Disconnect the station from the power supply at all poles an secure it against being switched on again.
Regudis W-CE Commissioning Connection box Connection terminals Cover Screws Loosen the screws ((6) in Fig. 13 on page 20) and remove the cover (5) of the connection box (3). Connect the power supply cable (1) to the prepared terminals (4) in the connection box.
Regudis W-CE Commissioning CAUTION Connect a hose line to the drain valve (2) in the primary circuit to make it easier to direct escaping Risk of scalding due to hot media! water into a container. If the heating system is already in operation and...
Regudis W-CE Commissioning Venting of the circulation pipe is complete. Set the desired hot water temperature with the rotary knob (2) on the actuator (1). Setting the shutoff valves for 7.5.1 Sliding hot water temperature control operation If the desired hot water temperature cannot be reached...
Regudis W-CE Commissioning Open one or more hot water draw-off points and run the hot water at a constant hot water volume flow of more than 7 l/min for at least 5 minutes. Meanwhile, the control parameters adapt to the conditions in the building's heating system.
Regudis W-CE Troubleshooting 8. Troubleshooting Troubleshooting table MALFUNCTION CAUSE REMEDY No heating of the potable water The volume flow sensor is Clean the volume flow sensor (see (only cold water at the draw-off contaminated or defective. section 8.4 on page 29 ). If this does not points, LED lights up green).
Regudis W-CE Troubleshooting MALFUNCTION CAUSE REMEDY The hot water volume flow at the The heat exchanger is heavily Decalcify the heat exchanger (see draw-off point is too low. calcified. section 8.3.2 on page 28). The cold water pressure is too low Check the setting of the pressure reducer (pressure reducer incorrectly set).
Regudis W-CE Troubleshooting 8.2.1 Status messages Indicator light Description LED lights up green Normal operation, no hot water tapping. LED flashes green Normal operation, hot water tapping. LED lights up orange Calibration run or service run. LED lights up red Service mode active, actuator fully retracted.
Regudis W-CE Troubleshooting 8.2.3 Fail-safe mode CAUTION The fail-safe mode becomes active as soon as one of the Risk of scalding due to hot media! listed errors occurs. In fail-safe mode, the actuator closes During some work, the station has to remain in...
Regudis W-CE Troubleshooting Connect a hose line to the drain valve ((1) in Fig. 19 on page 29) in the primary circuit to make it easier to direct escaping water into a container. Have a cloth and a container ready to catch any water that escapes.
Regudis W-CE Troubleshooting Volume flow sensor Ceramic disc valve Actuator with integrated potable water temperature control 8.4.1 Inspecting the volume flow sensor A malfunction occurs when no hot water can be tapped at the draw-off points. This can have several causes (see section 8.1 on page 25).
Regudis W-CE Troubleshooting Screw the sealing cap ((2) in Fig. 24 on page 31) tightly onto the circulation connection. Insert the volume flow sensor into the housing and secure it with the safety clip. Fit the volume flow sensor (1) onto the pipes and tighten the union nuts (3) of the volume flow sensor.
Regudis W-CE Maintenance CAUTION Have a cloth and a container ready to catch any water that escapes. Risk of scalding due to hot media! During some work, the station has to remain in Pull the plug together with the screen out of the filter operation and there is a risk of scalding due to insert.
Regudis W-CE Notes for the operator 10.2 Legionella prevention actuator (e.g. 60 °C). If the difference is more than 5 °C: Legionella multiply quickly if the hot potable water temperature is constantly too low or if the water is left Check the filter insert.
Regudis W-CE Dismantling and disposal 11.1.2 Dismantling the dwelling station Directive 2012/19/EU WEEE: • CAUTION The “crossed-out wheeled bin” symbolises that you are legally obliged to dispose of old appliances Risk of injury from pressurised media! separately from unsorted municipal waste. Incorrect Media escaping under pressure can cause injuries.
Valves, controls + systems Fresh water and dwelling stations Advice regarding corrosion protection The materials used in the Oventrop fresh water and dwelling The below table shows limit values of substances in potable stations are selected and processed in accordance with strict water when using heat exchangers with different brazing materials (copper, nickel or stainless steel).
Page 37
The specifying engineer and the user of the system are responsible for incorporating and evaluating substances and other factors in the water, which could influence corrosion and the formation of stones in the system. In critical water supply are- as, the local water authority should be consulted. OVENTROP GmbH & Co. KG Paul-Oventrop-Straße 1 D-59939 Olsberg...