  • Page 1 SE24 SE24 - (AS05860) Electronic control unit INSTRUCTIONS FOR INSTALLATION Firmware V.40...
  • Page 2: Electrical Connections

    SE24 ELECTRICAL CONNECTIONS 9 9 1 SE24 ENCODER START (NO) PED (NO) PHOTO (NC) STOP/SAFETY (NC/8K2) SAFETY (NC/8K2) LAMP 24Vcc 10W MAX FUSE +24Vdc TEST/E. SAV. +24Vdc MOTOR MOTOR 24 Vac BLACK WIRE 24 Vac RED WIRE...
  • Page 3: Power Supply Connection

    SE24 POWER SUPPLY CONNECTION FUSE 1A PHASE OVERCURRENT CIRCUIT BREAKER BROWN WIRE NEUTRAL 230Vac BLUE WIRE RESIDUAL-CURRENT DEVICE PHASE NEUTRAL LEDS COLOR START GREEN BATT GREEN PHOTO EXIT DOWN STOP START BATT FCA FCC PHOTO SAF STOP...
  • Page 4 SE24 LIMIT SWITCHES POSITION STOP STOP CLOSING OPENING STOP STOP OPENING CLOSING...
  • Page 5 SE24 FLASHING LIGHT CONNECTION FLASHING 7 8 9 10 1 1 12 24 Vdc 10W max PREFLASHING WARNING LIGHT CONNECTION 24Vdc 3W MAX 7 8 9 10 1 1 12 7 8 9 10 1 1 12 12/24Vdc CONTROL DEVICES CONNECTION...
  • Page 6 SE24 PHOTOCELLS CONNECTION DCF180 13 14 15 16 17 18 19 20 21 7 8 9 10 1 1 12 PHOTOCELLS CONNECTION WITH TEST DCF180 7 8 9 10 1 1 12 13 14 15 16 17 18 19 20 21...
  • Page 7 SE24 NC “SAFETY DEVICE” CONNECTION Set terminal 13 as «NC EDGE» 13 14 15 16 17 18 19 20 21 8K2 “SAFETY DEVICE” CONNECTION Set terminal 13 as «8K2 EDGE» 13 14 15 16 17 18 19 20 21 ADDITIONAL NC “SAFETY DEVICE” CONNECTION Set terminal 14 set as «NC EDGE»...
  • Page 8 SE24 ADDITIONAL 8K2 “SAFETY DEVICE” CONNECTION Set terminal 14 as «8K2 EDGE» 13 14 15 16 17 18 19 20 21 NC STOP CONNECTION Set terminal 14 as «NC STOP» 4 19 13 14 15 16 17 18 19 20 21...
  • Page 9 SE24 CONNECTIONS WITH CB24 BATTERY CHARGER 1 2 3 4 5 6 7 8 9 10 1 1 12 1 2 3 4 5...
  • Page 10 • Programming of automatic reclosing and pause time. • Pedestrian operation with adjustable opening. • Presetting for use with backup batteries ( GIBIDI BATTERIES KIT) . • Checking of batteries charging. During the operation with batteries, an acoustic signal sinchronyzed with the flashing light will be enabled.
  • Page 11: Installation Warnings

    SE24 3 - INSTALLATION WARNINGS • Before proceeding with the installation, it is necessary to fit a differential magneto htermal switch with maximum capacity of 10A upstream of the system. The switch must guarantee an omnipolar separation of the contacts, with an opening distance of at least 3 mm.
  • Page 12 SE24 5 - ELECTRICAL CONNECTIONS: TERMINAL BOARDS Terminal Position Signal Description 0 Vac input. 0 Vac 24 Vac 24 Vac input. 24Vdc motor output. MOTOR 24Vdc motor output. MOTOR Positive connection to the BATTERY CHARGER BOARD. +SK BAT Negative connection to the BATTERY CHARGER BOARD.
  • Page 13: Protection Fuses

    SE24 6 - PROTECTION FUSES Position Value Type Description It protects the control unit. FAST 7 - BUTTONS • During the programming it means OK/CONFIRMATION. • During normal operation it has START function. • During the programming they allow to scroll the •...
  • Page 14: Access To The Menus

    SE24 9 - ACCESS TO THE MENUS When the motor is not running, if you push buttons at the same time, you can acceed to the menus for operation parametres setting. The default values of the different parameters in following paragraphs are underlined.
  • Page 15: Language Menu

    SE24 10 - LANGUAGE MENU LANGUAGE Exit Up/Down ITALIANO Back Up/Down ENGLISH Back Up/Down ESPAÑOL Back Up/Down Display language selection DEUTSCH Back Up/Down FRANÇAIS Back Up/Down NEDERLANDS Back Up/Down 11 - SETUP WIZARD MENU Setup wizard is a guided and simplified procedure for the first setup of the system after having completed the mechanical and electrical installation.
  • Page 16 SE24 12 - TRANSMITTERS MENU TRANSMITTERS Exit Up/Down STORE NEW Procedure to learn some new transmitters. Back Up/Down Push any button of the new transmitter within 6s, the learning is confirmed by some fast blinking of the flashing light. The procedure keeps active for 6s after the learning of one transmitter, so it is possible to learn more transmitters in succession.
  • Page 17: Commands Menu

    SE24 13 - COMMANDS MENU COMMANDS Exit Up/Down START TRANSMITTER BUTTON 1: START command on button 1. Back Up/Down Back Up/Down BUTTON 2: START command on button 2. BUTTON 3: START command on button 3. BUTTON 4: START command on button 4.
  • Page 18 SE24 13 - COMMANDS MENU AUTO-CLOSE OFF: Automatic closing disabled. Back Up/Down 5s... 60s ...255s : Automatic closing enabled, adjustable every 5s. FAST CLOSING OFF: Fast closing disabled. Back Up/Down ON: Reduces the pause time to 2s after photocells intervention...
  • Page 19 SE24 14 - SAFETY DEVICES MENU SAFETY SETTINGS Exit Up/Down PHOTOCELLS MODE PHOTOCELLS ACTIVE IN CLOSE: Back Up/Down Back Up/Down PHOTO input active only during closing phase. Stop the motion and inverts completely opening. If intercepted in pause, it charges the pause time again.
  • Page 20 SE24 14 - SAFETY DEVICES MENU SAFETY TERMINAL ACTIVE IN OFF: Input disabled. Back Back Up/Down Up/Down OPENING: Input for safety devices enabled only in opening. CLOSING: Input for safety devices enabled only in closing. CLOSE AND OPEN: Input for safety devices enabled both in opening and closing.
  • Page 21 SE24 14 - SAFETY DEVICES MENU FULL REVERSE: When an EDGE event happens, the gate stops and reverse with a manoeuvre slowed down for 1s at 70% of max. speed, then goes on as a manoeuvre of normal movement up to the complete opening or closing.
  • Page 22: Device Test

    SE24 14 - SAFETY DEVICES MENU DEVICE TEST Back Up/Down Test of the accessory control units DSC80-DSC90 enabled. At the movement command of the gate (START, PEDESTRIAN), by terminal 8, power is turned off from the control unit for 1 s and then turned on to check its correct operation.
  • Page 23 SE24 14 - SAFETY DEVICES MENU ANTI - CRUSHING ANTI-CRUSHING Setting to increase/ DECREASE the value of the ant- OFFSET Back Up/Down Back Up/Down crushing threshold learnt during learning procedure. -20 ... -1: Decreasing in percentage of the threshold in comparison with the value learnt during the procedure of stroke learning.
  • Page 24: Movement Menu

    SE24 15 - MOVEMENT MENU MOVEMENT Exit Up/Down SPEED % 70% ... 100%: Back Up/Down Setting of the speed of not slowed movement, in percentage compared to the max. speed, adjustable every 5%. The modification of this parameter forces the execution of learning cycle.
  • Page 25: Clock Menu

    SE24 16 - BLINKING MENU FLASHING LAMP Exit Up/Down FLASHING MODE Flashing: Blinking flashing light input. Back Up/Down Fixed: Fixed flashing light input.. PREFLASHING ON: The flashing light will start 3 s before motor start. Back Up/Down OFF: The flashing light and the motor will start at the same time.
  • Page 26 SE24 17 - CLOCK MENU TIMERS TIMER 1 The timers are specific functions that allow making a Back Up/Down Back Up/Down specific function only within a specific time band. The timers are active also on Saturdays and Sundays. It is possible to set up two timers with the same or a TIMER 2 different function in the same or different time bands.
  • Page 27: Advanced Menu

    SE24 18 - ADVANCED MENU ADVANCED TOOLS Exit Up/Down EVENT LOGS SAFETY EDGE EVENTS Display of date and hours of last 4 events of SAFETY Back Up/Down Back Up/Down input. STOP EVENTS Display of date and hours of last 4 events of STOP...
  • Page 28: Warning Light

    SE24 18 - ADVANCED MENU PED TERMINAL Functions available: Back Up/Down PEDESTRIAN: PED terminal works as N.O. input to run the PEDESTRIAN manoeuvre. CLOSE: PED terminal works as N.O. input to run the CLOSING command: Operation in reply to a START command:...
  • Page 29: Factory Reset

    SE24 18 - ADVANCED MENU POWER ON Display of the number of operation days of the control unit. Back Up/Down CYCLES Display of the number of cycles (opening + closing) made. Back Up/Down FIRMWARE Display of firmware version. Back Up/Down 19 - FACTORY RESET The procedure of factory reset allows restoring all the parameters and the setting to default values.
  • Page 30: Final Checks

    SAFETY terminal test failed 1 slow blinking STOP terminal test failed Thank you for choosing GIBIDI. READ CAREFULLY THESE INSTRUCTIONS BEFORE PROCEEDING WITH INSTALLATION. WARNINGS: This product has been tested by GI.BI.DI. for full compliance with the requirements of the directives in force. GI.BI.DI. S.r.l. reserves the right to change the technical data without prior notice in relation to product development.
  • Page 31 Moreover declares that the product must not be used until the machine in which it has been incorporated has not been declared in accordance with 2006/42/CE Directive. The Legal Representative Date 05/10/2021 Michele Prandi UKCA manufacturer declaration: The UKCA declaration is available at http://conformity.gibidi.com...