INSTALLATION GUIDE
7 Series 700A11
R-454B
60Hz
General Installation Information ................................................................................................ 2
Nomenclature ................................................................................................................................... 7
Water Quality ................................................................................................................................... 13
Hot Water Generator Connections .......................................................................................... 14
Electrical Connections .................................................................................................................. 16
Electronic Thermostat Installation ........................................................................................... 18
Blower Performance Data ........................................................................................................... 19
Dimensional Data ............................................................................................................................ 20
Physical Data .................................................................................................................................... 22
Reference Calculations ................................................................................................................. 23
Operating Limits.............................................................................................................................. 23
Refrigerant Removal and Evacuation ..................................................................................... 24
Charging Procedures ..................................................................................................................... 24
Refrigerant Recovery..................................................................................................................... 25
Unit Startup ....................................................................................................................................... 26
Revision Guide ................................................................................................................................. 31
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All products are designed, tested, and
manufactured to comply with the latest publicly released
and available edition of UL 60335-2-40 for electrical
safety certification. All field electrical connections must
follow the National Electrical Code (NEC) guide standards
and / or any local codes that may be applicable for the
installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
WARNING
CAUTION
NOTICE
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
death or serious injury.
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
service personnel with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
IGW7-0018W
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 7 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Water Furnace 7 Series

  • Page 1: Table Of Contents

    INSTALLATION GUIDE 7 Series 700A11 R-454B 60Hz IGW7-0018W General Installation Information ....................2 Nomenclature ........................... 7 Water Quality ........................... 13 Hot Water Generator Connections ..................14 Electrical Connections ........................16 Electronic Thermostat Installation ................... 18 Blower Performance Data ......................19 Dimensional Data ..........................
  • Page 2: General Installation Information

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information NOTICE: Do not store or install units in corrosive environments No person carrying out work in relation to a REFRIGERATING SYSTEM which involves exposing any pipe work shall use any or in locations subject to temperature or humidity extremes.
  • Page 3: Installation Space Requirements

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 64 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information WARNING meter Check that cabling will not be subject to wear, corrosion, excessive 1.00 pressure, vibration, sharp edges or any other adverse environmental 1.00 effects. The check shall also take into account the effects of aging or 1312 1.00 1968...
  • Page 5 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information Minimum Floor Area Charge Model Confi guration m3/h Vertical 54.4 4.53 1.38 95.5 108.2 183.9 60.0 Horizontal Floor 23.6 1.97 0.60 290.9 27.0 101.4 172.4 56.2 Horizontal Floor +2 Ft 47.6 3.97 1.21...
  • Page 6 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information If H is greater than or equal to 7.22 FT (2.2 M), use Table Value 7.22 FT (2.2 M) If H is under 23.6 IN (0.6 M), use Table Value 23.6 IN (0.6 M) If H is between these values, use the table to calculate A...
  • Page 7: Nomenclature

    General Installation Information Model Nomenclature IntelliStart Brand 0 – None W – WFI Model Mitigation 7 – 7 Series 1 – Sensor Mitigation Type Controls A – Water to Air D – Aurora Premium Control (Performance and Refrigeration Cabinet Configuration Monitoring) with EEV V –...
  • Page 8 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information - Serial Plate Example Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max.
  • Page 9 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information personnel to perform maintenance or repair. Provide sufficient NOTICE room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by NOTICE: To avoid equipment damage, do not leave the means of a louvered door, etc.
  • Page 10: Installing Horizontal Units

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information cont. could loosen a single nut. To allow filter access, one bracket Installing Horizontal Units on the filter side should be installed 180° from the position Remove and discard the compressor hold down shipping shown in Figure 3.
  • Page 11: Duct System

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information cont. in CK4LI connector kit) against the rubber gasket in the Duct System swivel connector and thread the female locking ring onto An air outlet collar is provided on vertical top and rear air the pipe threads, while maintaining the brass connector discharge units and all horizontal units to facilitate a duct in the desired direction.
  • Page 12: Condensate Drain

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE General Installation Information cont. Condensate Drain Figure 5: Horizontal Drain Connection On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a Vent (if needed) 3/4-inch PVC female adapter and a flexible connecting hose.
  • Page 13: Water Quality

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Water Quality Material Copper 90/10 Cupronickel 316 Stainless Steel Acidity/Alkalinity 7 - 9 7 - 9 7 - 9 Calcium and (Total Hardness) (Total Hardness) (Total Hardness) Scaling Magnesium Carbonate less than 350 ppm less than 350 ppm less than 350 ppm Less than 0.5 ppm (rotten egg...
  • Page 14: Hot Water Generator Connections

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Hot Water Generator Connections To maximize the benefits of the hot water generator a Figure 11: Typical Hot Water Generator Installation minimum 50-gallon water heater is recommended for higher Cold 3/4” x 3/4” x 1/2” tee demand applications, use an 80-gallon water heater or two Water In Water Out...
  • Page 15: Plumbing Installation

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Hot Water Generator Connections Cont. Plumbing Installation Hot Water Generator Startup 1. Turn the hot water generator switch to the “ON” position. 1. Inspect the dip tube in the water heater cold inlet for a The hot water generator switch will allow the hot water check valve.
  • Page 16: Electrical Connections

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Electrical Connections General Accessory Relay Be sure the available power is the same voltage and phase A set of “dry” contacts has been provided to control as that shown on the unit serial plate. Line and low voltage accessory devices, such as water solenoid valves on open loop wiring must be done in accordance with local codes or installations, electronic air cleaners, humidifiers, etc.
  • Page 17 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Electrical Connections Cont. Pump Power Wiring Figure 14: Pump Wiring 208-230/60/1 See Figure 14 for electrical connections from control box to Wire Nuts pumps. FC1/FC2 style flow centers with fixed speed pumps connect to PB1 in the control box.
  • Page 18: Electronic Thermostat Installation

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Electronic Thermostat Installation Position the thermostat subbase against the wall so that it is Figure 15: Thermostat Wiring (Communicating Style Signals) level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 3/16-inch bit.
  • Page 19: Blower Performance Data

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Blower Performance Data Variable Speed Air Flow Model Max ESP Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Speed 8 Speed 9 Speed 10 Speed 11 Speed 12 1100 1220 1440...
  • Page 20: Dimensional Data

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Vertical Dimensional Data Top Air Discharge LEFT RETURN RIGHT RETURN 6 in [15.2 cm] 1.9in MINIMUM [4.8cm] CLEARANCE TO VENT 1.9in ACCESS [4.8cm] PANEL I K J D E H F FRONT RIGHT SIDE LEFT SIDE Return Connection Electrical Connections...
  • Page 21: Horizontal Dimensional Data

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Horizontal Dimensional Data TOP VIEW 2.1in [5.4cm] MOUNT (2) HANGER BRACKETS AS SHOWN TO ALLOW ACCESS HORIZONTAL TO FILTER 6 in [15.2 cm] MINIMUM 2 ft [61 cm] CLEARANCE TO VENT Primary Service Access ACCESS PANEL SIDE DISHCARGE VIEW...
  • Page 22: Physical Data

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Physical Data Model Compressor (1 each) Variable Speed Scroll Factory Charge R-454B, oz [kg] Vertical 64 [1.81] 64 [1.81] 95 [2.69] 110 [3.12] Factory Charge R-454B, oz [kg] Horizontal 60 [1.70] 60 [1.70] 91 [2.58] 118 [3.35] Factory Charge R-454B, oz [kg]...
  • Page 23: Reference Calculations

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Reference Calculations Abbreviations and Definitions Heating Calculations: Cooling Calculations: = airflow, cubic feet/minute LWT = EWT + LWT = EWT - gpm x 500 EWT = entering water temperature, Fahrenheit gpm x 500 = water flow in gallons/minute WPD = water pressure drop, psi and feet of water LAT (DB) = EAT (DB) -...
  • Page 24: Refrigerant Removal And Evacuation

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Refrigerant Removal and Evacuation When breaking into the refrigerant circuit to make repairs – or This process might need to be repeated several times. Com- for any other purpose conventional procedures shall be used. pressed air or oxygen shall not be used for purging refriger- However, for flammable refrigerants it is important that best ant systems.
  • Page 25: Refrigerant Recovery

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.
  • Page 26: Unit Startup

    Aurora Startup procedure for the controls pumping watts. configuration. An AID Tool is required for setup, configuration, and troubleshooting on the 7 Series Variable Speed system. Sensor Kit Setup Screen in AID TOOL AID Tool version 2.09 or greater is preferred.
  • Page 27 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Unit Startup iv. Activate energy option Dehumidify v. Select blower energy – PSC or ECM/5-Speed ECM vi. Line Voltage calibration – Voltmeter required to calibrate line voltage during heating or cooling. Refer to Line Voltage Calibration in this manual for more details.
  • Page 28: Startup Steps

    VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Unit Startup the pump watts used in the calculation. Pump b. Activate ‘Flowmeter’ to activate the flow sensor select the appropriate 3/4 in., 1 in., or none (1 in. is watts are measured on VS pumps and estimated standard on variable speed units).
  • Page 29 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Unit Startup 14. Check for an air temperature rise of 12°F to 35°F across 16. Adjust the heating setpoint below room temperature the air coil (heating compressor speed 12), depending and verify that the compressor and water valve or loop on the fan speed and entering water temperature.
  • Page 30 VARIABLE SPEED PACKAGED HEAT PUMP INSTALLATION GUIDE Notes...
  • Page 31: Revision Guide

    Revision Guide Pages: Description: Date: Document Creation 25 Jan 2024...
  • Page 32 Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com Product: 7 Series 700A11 Type: Geothermal Heat Pump Size: 3-5 Ton Variable Speed Document: Installation Guide *IGW7-0018W* ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy IGW7-0018W 07/24 of continual product research and development and reserves the right to change design and specifi...
  • Page 33: Manuel D'installation

    MANUEL D’INSTALLATION Série 7 700A11 R-454B 60Hz IGW7-0018W Informations générales sur l’installation ..................2 Nomenclature ............................. 7 Qualité de l’eau ............................13 Raccords du générateur d’eau chaude ..................... 14 Raccords électriques ..........................16 Installation du thermostat électronique ................... 18 Données sur le rendement du ventilateur ..................19 Données dimensionnelles ........................
  • Page 34: Informations Générales Sur L'installation

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation AVIS : Ne pas installer les unités dans un environnement corrosif d’incendie approprié doit être à portée de main. Gardez un extincteur à poudre sèche ou à CO2 à proximité de la zone de chargement. ou dans des endroits soumis à...
  • Page 35: Site D'installation

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation Espace d’installation requis  AVERTISSEMENT Zone ventilée : assurez-vous que la zone est à découvert ou qu’elle REMARQUE : Le matériel dont la charge de réfrigérant est inférieure est correctement ventilée avant d’intervenir dans le système ou de à...
  • Page 36 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation  AVERTISSEMENT alte mètres Assurez-vous que le câblage ne sera pas soumis à l’usure, à la corrosion, à 1,00 une pression excessive, à des vibrations, à des bords tranchants ou à tout 1,00 autre effet nocif de l’environnement.
  • Page 37 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation Superfi cie minimale du plancher Charge Modèle Confi guration m3/h Verticale 54,4 4,53 1,38 95,5 108,2 183,9 60,0 23,6 1,97 0,60 290,9 27,0 101,4 172,4 56,2 Plancher horizontal 47,6 3,97 1,21...
  • Page 38 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation Si H est supérieur ou égal à 7,22 pi (2,2 m) utilisez la valeur du tableau 7,22 pi (2,2 m). Si H est inférieur à 0,6 m (23,6 po), utilisez la valeur du tableau 0,6 m (23,6 po).
  • Page 39: Nomenclature

    Informations générales sur l’installation Nomenclature du modèle IntelliStart Brand 0 – None W – WFI Model Mitigation 7 – 7 Series 1 – Sensor Mitigation Type Controls A – Water to Air D – Aurora Premium Control (Performance and Refrigeration Cabinet Configuration Monitoring) with EEV V –...
  • Page 40 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Renseignements généraux sur l’installation – Exemple de plaque de série Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min.
  • Page 41 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation d’entraînement VS, ce qui entraîne une surchauffe de celui-ci. AVIS L’emplacement doit avoir suffisamment d’espace pour que le personnel d’entretien puisse effectuer l’entretien ou les réparations. AVIS : Pour éviter d’endommager l’équipement, ne laissez pas Prévoir suffisamment d’espace pour faire des raccordements d’eau, le système rempli dans un bâtiment sans chauffage par temps d’électricité...
  • Page 42 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation (suite) double est requis puisque la vibration pourrait desserrer un Installation d’unités horizontales écrou simple. Pour permettre l’accès au filtre, un support du côté Enlevez et jetez le boulon d’expédition de maintien du filtre doit être installé...
  • Page 43 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation (suite) trousse de connecteur CK4LI) contre le joint en caoutchouc du Système de conduits connecteur pivotant et vissez l’anneau de verrouillage femelle Un collier de sortie d’air est fourni sur les appareils verticaux sur le tuyau fileté, tout en maintenant le connecteur en laiton à...
  • Page 44 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Informations générales sur l’installation (suite) Drain de condensat Figure 5 : Raccord de drain horizontal Sur les unités verticales, l’ensemble de drain de condensat interne se compose d’un tube d’évacuation relié au bac de récupération, Évent d’un adaptateur femelle en PVC de 3/4 po et d’un tuyau flexible (au besoin)
  • Page 45: Qualité De L'eau

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Qualité de l’eau Matériel Cuivre 90/10 Cupronickel Acier inoxydable 316 Acidité/Alcalinité 7 à 9 7 à 9 7 à 9 Calcium et carbonate de (Dureté totale) (Dureté totale) (Dureté totale) Entartrage magnésium moins de 350 ppm moins de 350 ppm moins de 350 ppm...
  • Page 46: Raccords Du Générateur D'eau Chaude

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Raccords du générateur d’eau chaude Pour optimiser les avantages du générateur d’eau chaude, Figure 11 : Installation typique d’un générateur d’eau chaude un chauffe-eau d’au moins 50 gallons est recommandé. Pour Raccord en T de 3/4 po x Entrée les applications à...
  • Page 47 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Raccords du générateur d’eau chaude suite Installation de plomberie Démarrage de l’interrupteur du générateur d’eau chaude 1. Inspectez le tube plongeur dans l’entrée froide du chauffe- eau pour déceler la présence d’un clapet antiretour. Si un 1.
  • Page 48: Raccords Électriques

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Raccords électriques Généralités Relais d’accessoires Assurez-vous que l’alimentation disponible correspond au Un ensemble de contacts « secs » a été fourni pour commander même voltage et à la même phase que celles indiquées sur la les dispositifs accessoires, comme les électrovannes d’eau sur les plaque de série de l’appareil.
  • Page 49 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Raccords électriques suite Câblage d’alimentation de la pompe Figure 14 : Câblage de la pompe 208-230/60/1 Voir la figure 14 pour les connexions électriques entre le boîtier Écrous pour fil métallique de commande et les pompes. Rouge Rouge Les centres de débit de style FC1/FC2 avec des pompes à...
  • Page 50: Installation Du Thermostat Électronique

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Installation du thermostat électronique Positionnez la sous-base du thermostat contre le mur de manière Figure 15 : Câblage du thermostat (signaux de communication) à ce qu’elle soit de niveau et que les fils du thermostat dépassent au milieu de la sous-base.
  • Page 51: Données Sur Le Rendement Du Ventilateur

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Données sur le rendement du ventilateur Débit d’air à vitesse variable Pression statique Modèle Vitesse 1 Vitesse 2 Vitesse 3 Vitesse 4 Vitesse 5 Vitesse 6 Vitesse 7 Vitesse 8 Vitesse 9 Vitesse 10 Vitesse 11 Vitesse 12 (ESP) max 1100 1220...
  • Page 52: Données Dimensionnelles

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Données dimensionnelles verticales Évacuation d’air supérieur LEFT RETURN RIGHT RETURN 6 in [15.2 cm] 1.9in MINIMUM [4.8cm] CLEARANCE TO VENT 1.9in ACCESS [4.8cm] PANEL I K J D E H F FRONT RIGHT SIDE LEFT SIDE...
  • Page 53 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Données dimensionnelles horizontales TOP VIEW 2.1in [5.4cm] MOUNT (2) HANGER BRACKETS AS SHOWN TO ALLOW ACCESS HORIZONTAL TO FILTER 6 in [15.2 cm] MINIMUM 2 ft [61 cm] CLEARANCE TO VENT Primary Service Access ACCESS PANEL...
  • Page 54: Données Physiques

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Données physiques Modèle Compresseur (1 chacun) Spirale à vitesse variable Charge d’usine R-454B, oz [kg] Verticale 64 [1,81] 64 [1,81] 95 [2,69] 110 [3,12] Charge d’usine R-454B, oz [kg] Horizontal 60 [1,70] 60 [1,70] 91 [2,58] 118 [3,35]...
  • Page 55: Calculs De Référence

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Calculs de référence Abréviations et définitions Calculs de chauffage : Calculs de refroidissement : pi3/min = débit d’air, pieds cubes/minute LWT = EWT + LWT = EWT - = entering water temperature (température de l’entrée d’eau), gmp x 500 gmp x 500 Fahrenheit...
  • Page 56: Retrait Et Évacuation Du Réfrigérant

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer des Ce processus devra peut-être être répété plusieurs fois. L’air réparations, ou pour toute autre fin, vous devez suivre les comprimé...
  • Page 57: Récupération Du Réfrigérant

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité. Lors du transfert du réfrigérant dans des bouteilles, assurez- vous que seules des bouteilles appropriées de récupération de réfrigérant sont utilisées.
  • Page 58: Démarrage De L'unité

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Démarrage de l’unité 2. Écran de configuration Aurora Avant d’alimenter l’appareil, vérifier ce qui a. Configuration du module de commande du moteur suit : pour le chauffage du débit d’air – sélectionner les REMARQUE : Enlevez et jetez le boulon d’expédition de fixation vitesses de soufflante G, basse, élevée et auxiliaire de compresseur situé...
  • Page 59 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Démarrage de l’unité iii. Activez l’option d’énergie e. La surveillance de la puissance peut être lue sur iv. Sélectionnez la puissance du ventilateur – n’importe lequel des composants suivants : PSC ou ECM/5 vitesses. i.
  • Page 60: Étapes De Démarrage

    MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Démarrage de l’unité iii. Réglez ensuite le pourcentage maximal de la 14. Si des chaufferettes électriques auxiliaires sont installées, pompe VS pour atteindre au moins 3,0 gal/ augmenter le point de consigne de chauffage jusqu’à ce que min par tonne pour un fonctionnement à...
  • Page 61 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE...
  • Page 62 MANUEL D’INSTALLATION DE LA THERMOPOMPE EMBALLÉE À VITESSE VARIABLE Notes...
  • Page 63: Guide De Révision

    Guide de révision Pages : Description : Date : Par : Toutes Création de document 25 janvier 2024...
  • Page 64 Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com Product: 7 Series 700A11 Type: Geothermal Heat Pump Size: 3-5 Ton Variable Speed Document: Installation Guide *IGW7-0018W* ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy IGW7-0018W 07/24 of continual product research and development and reserves the right to change design and specifi...