INSTALLATION GUIDE
Versatec 300 Console
R-454B
60Hz
General Installation Information ................................................................................................ 2
Refrigeration Detection and Mitigation ................................................................................. 4
Serial Plate ......................................................................................................................................... 6
Water Quality ................................................................................................................................... 13
Electrical Connections .................................................................................................................. 14
Dimensional Data ............................................................................................................................ 15
Physical Data .................................................................................................................................... 19
Blower Performance Data ........................................................................................................... 19
Unit Startup Notes .......................................................................................................................... 20
Unit Startup ....................................................................................................................................... 21
Refrigerant Removal and Evacuation ..................................................................................... 22
Charging Procedures ..................................................................................................................... 22
Refrigerant Recovery..................................................................................................................... 23
Refrigeration Cycle Analysis ....................................................................................................... 24
Revision Guide ................................................................................................................................. 25
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All products are designed, tested, and
manufactured to comply with the latest publicly released
and available edition of UL 60335-2-40 for electrical
safety certification. All field electrical connections must
follow the National Electrical Code (NEC) guide standards
and / or any local codes that may be applicable for the
installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
WARNING
death or serious injury.
CAUTION
NOTICE
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
All Versatec Low Sill Console are safety listed under UL 60335-2-40 through ETL, and
performance listed with AHRI in accordance with ASHRAE/ANSI/AHRI/ISO Standard 13256-1.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
service personnel with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
IGV3-0008W
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Versatec 300 and is the answer not in the manual?

Questions and answers

Summary of Contents for Water Furnace Versatec 300

  • Page 1: Table Of Contents

    INSTALLATION GUIDE Versatec 300 Console R-454B 60Hz IGV3-0008W General Installation Information ....................2 Refrigeration Detection and Mitigation ................. 4 Serial Plate ............................6 Water Quality ........................... 13 Electrical Connections ........................14 Dimensional Data ..........................15 Physical Data ............................ 19 Blower Performance Data ......................19 Unit Startup Notes ..........................
  • Page 2: General Installation Information

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information NOTICE: Do not store or install units in corrosive environments No person carrying out work in relation to a REFRIGERATING SYSTEM which involves exposing any pipe work shall use any or in locations subject to temperature or humidity extremes. sources of ignition in such a manner that it may lead to the risk of Corrosive conditions and high temperature or humidity can fire or explosion.
  • Page 3 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 64 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information: Refrigerant Detection and Mitigation WARNING meter Check that cabling will not be subject to wear, corrosion, excessive 1.00 pressure, vibration, sharp edges or any other adverse environmental 1.00 1312 1.00 effects. The check shall also take into account the effects of aging or 1968 1.00 continual vibration from sources such as compressors or fans.
  • Page 5 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information: Refrigerant Detection and Mitigation If H is greater than or equal to 7.22 FT (2.2 M), use Table Value 7.22 FT (2.2 M) If H is under 23.6 IN (0.6 M), use Table Value 23.6 IN (0.6 M) If H is between these values,...
  • Page 6: Serial Plate

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Serial Plate Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max. outlet air temperature (F/C) Unit Restrictions Max.
  • Page 7 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information Safety Considerations Water Piping The proper water flow must be provided to each unit WARNING: Before performing service or whenever the unit operates. To assure proper flow, use maintenance operations on a system, turn off main pressure/temperature ports to determine the flow rate.
  • Page 8 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information Step 1: Unpack Equipment and Inspect for Damage Step 2: Determine Equipment Location • Choose level flooring surface (Correctable with shims. Do not pitch towards drain.) • Location of wall support and fasteners required to secure chassis backplate. •...
  • Page 9 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information Step 4: Provide Water and Condensate Drain Connections • A two-pipe reverse return piping configuration is recommended as it equalizes the piping circuit lengths and delivers even water flow to each unit. A direct return piping configuration may be used, but it may be difficult to achieve and maintain proper water flow to the units.
  • Page 10 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information Step 5: Provide Line Voltage Wiring • Check unit data plate located on control side of chassis for ampacity and fuse size. • Remove electrical knockouts from chassis backplate. • Run line voltage wiring through knockout and secure wiring to backplate or disconnect. Step 6: Chassis Installation •...
  • Page 11 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE General Installation Information Field Converting Console Chassis is normally configured with controls on right end and piping on left end (see Figure 3 top view). In this position panel number 1 would be positioned against wall or back plate. Unit may also be turned 180° against wall or back plate. In this position controls will be on left end and piping on right end panel number 2 would be positioned against wall or back plate.
  • Page 12 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Installation Information Condensate Drain Duct System On vertical units, the internal condensate drain assembly An air outlet collar is provided on vertical top flow units consists of a drain tube which is connected to the drain pan, and all horizontal units to facilitate a duct connection.
  • Page 13: Water Quality

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside.
  • Page 14: Electrical Connections

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Electrical Connections General Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. Consult the unit’s serial plate data for correct fuse sizes.
  • Page 15 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Dimensional Data - Flat Top Cabinet Chassis with Cabinet 09-018 Left Hand Cabinet Right Hand Cabinet FRONT SIDE Right return cabinet shown in dimensional views Overall Cabinet Grille Flat Top Configuration Grille Grille Grille Width Depth Height...
  • Page 16 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Dimensional Data- Slope Top Cabinet 09-018 Right Hand Cabinet Left Hand Cabinet 80° SIDE FRONT Right return cabinet shown in dimensional views Overall Cabinet Grille Slope Top Configuration Grille Grille Grille Width Depth Height Length Width 45.1...
  • Page 17: Dimensional Data

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Dimensional Data - Chassis 09-018 LC09-12 WATER OUT 28.0 AIR FLOW 1/2" FPT 37.8 WATER IN 29.1 10.2 1/2" FPT COMPRESSOR BLOWER ACCESS PANEL ACCESS PANEL 21.6 16.7 16.2 FILTER CONDENSATE DRAIN CONNECTION 015-018 33.1 AIR FLOW 42.7 33.6...
  • Page 18 WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Dimensional Data - Controls Detail: Flat Top Chassis Left Return Right Return Blower Option Switch Control Panel (Remove For Access To Control Box) Control Panel (Remove For Access Blower Option Switch To Control Box) Wall Mount For Chassis w/Flat Top Cabinets Wall Mount For Chassis...
  • Page 19: Physical Data

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Physical Data Console Model Compressor (1 each) Rotary Factory Charge R454B, oz [kg] 22 [0.62] 22 [0.62] 26 [0.74] 26 [0.74] Blower Motor & Blower Blower Motor Type/Speeds 3 Speeds Blower Motor - hp [W] 0.25 [186] 0.25 [186] 0.25 [186]...
  • Page 20: Unit Startup Notes

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Unit Startup Notes Electrical Disconnect Hydronic Loop Controller for Optional field installed console disconnect provides a Boiler/Tower Installations permanent electrical connection to the main electrical supply The hydronic loop controller is a microprocessor based branch.
  • Page 21: Unit Startup

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Unit Startup Before Powering Unit, Check The Following: • High voltage is correct and matches nameplate. • Fuses, breakers and wire size correct. • Low voltage wiring complete. • Piping completed and water system cleaned and flushed. •...
  • Page 22: Refrigerant Removal And Evacuation

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Refrigerant Removal and Evacuation When breaking into the refrigerant circuit to make repairs – or The refrigerant charge shall be recovered into the correct re- for any other purpose conventional procedures shall be used. covery cylinders if venting is not allowed by local and national However, for flammable refrigerants it is important that best codes.
  • Page 23: Refrigerant Recovery

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.
  • Page 24: Refrigeration Cycle Analysis

    WATER-SOURCE/GEOTHERMAL HEAT PUMP CONSOLE INSTALLATION GUIDE Refrigeration Cycle Analysis DEALER: PHONE #: DATE: PROBLEM: MODEL #: Startup/Troubleshooting Form SERIAL #: COOLING CYCLE ANALYSIS SAT °F °F Unit Amp Draw: Loop: Open Closed Line Voltage: °F °F COIL SUCTION COMPRESSOR REVERSING COAX EXPANSION VALVE...
  • Page 25: Revision Guide

    Revision Guide Pages: Description: Date: Document Creation 15 April 2024...
  • Page 26 Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com *IGV3-0008W* Product: Versatec 300 Console Type: Geothermal/Water Source Heat Pump Size: 0.75-1.0 Ton Document: Installation Guide IGV3-0008W 08/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and...
  • Page 27 MANUEL D’INSTALLATION Console Versatec 300 R-454B 60 Hz IGV3-0008W Informations générales sur l’installation ................2 Détection et atténuation des fuites de réfrigérant ............4 Plaque signalétique ........................6 Qualité de l’eau ..........................13 Raccords électriques ........................14 Données dimensionnelles ......................15 Données physiques ........................
  • Page 28: Informations Générales Sur L'installation

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation AVIS : N’installez pas les unités dans un environnement corrosif ou dans Aucune personne effectuant des travaux sur un SYSTÈME FRIGORIFIQUE des endroits soumis à des températures extrêmes ou à l’humidité élevée. impliquant l’exposition d’une tuyauterie ne doit utiliser des sources Les conditions corrosives et des températures extrêmes ou à...
  • Page 29 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation AVERTISSEMENT Espace d’installation requis Zone ventilée : Assurez-vous que la zone est à découvert ou REMARQUE : Le matériel dont la charge de réfrigérant est qu’elle est correctement ventilée avant d’intervenir dans le inférieure à...
  • Page 30: Détection Et Atténuation Des Fuites De Réfrigérant

    Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant AVERTISSEMENT Assurez-vous que le câblage ne sera pas soumis à l’usure, à la corrosion, alte à une pression excessive, à des vibrations, à des bords tranchants ou à 1,00 tout autre effet nocif de l’environnement.
  • Page 31 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Si H est supérieur ou égal à 2,2 m (7,22 pi), utilisez la valeur du tableau 2,2 m (7,22 pi). Si H est inférieur à...
  • Page 32: Plaque Signalétique

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Plaque signalétique Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max.
  • Page 33 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation Considérations de sécurité Tuyauterie d’eau AVERTISSEMENT : Avant d’effectuer toute opération Le bon débit d’eau doit être fourni à chaque unité chaque fois que d’entretien ou de maintenance d’un système, coupez celle-ci fonctionne.
  • Page 34 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation Étape 1 : Déballer l’équipement et vérifier s’il est endommagé Étape 2 : Déterminer l’emplacement de l’équipement • Choisissez une surface de plancher de niveau (à corriger avec des cales). N’inclinez pas vers le drain. •...
  • Page 35 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation Étape 4 : Fournir des raccords d’eau et de drain de condensat • Une configuration de tuyauterie de retour inversé à deux tuyaux est recommandée, car elle permet d’égaliser les longueurs des circuits de tuyauterie et d’assurer un débit d’eau uniforme vers chaque unité.
  • Page 36 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation Étape 5 : Fournir le câblage de tension de ligne • Vérifiez le courant admissible et la taille du fusible sur la plaque signalétique de l’appareil située du côté des commandes du cadre. •...
  • Page 37 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Informations générales sur l’installation Console à conversion sur place Le cadre est normalement configuré avec des commandes à l’extrémité droite et de la tuyauterie à l’extrémité gauche (reportez-vous à la vue de dessus de la Figure 3).
  • Page 38 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Information sur l’installation Drain de condensat Système de conduits Sur les unités verticales, l’ensemble de drain de condensat interne Un collier de sortie d’air est fourni sur les unités verticales à débit se compose d’un tube d’évacuation relié...
  • Page 39: Qualité De L'eau

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Qualité de l’eau Dans les eaux souterraine où l’entartrage pourrait être important ou en cas de croissance biologique comme des bactéries ferreuses, un système en boucle fermée est recommandé. Les serpentins d’échangeur de chaleur des réseaux d’eau souterraine peuvent, sur une certaine période de temps, perdre leur capacité...
  • Page 40: Raccords Électriques

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Raccords électriques Généralités Assurez-vous que l’alimentation disponible correspond au même voltage et à la même phase que celles indiquées sur la plaque de série de l’appareil. Le câblage de ligne et de la basse tension doit être effectué conformément aux codes locaux ou au Code national de l’électricité, selon ce qui est applicable.
  • Page 41: Données Dimensionnelles

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Données dimensionnelles – armoire à dessus plat Cadre avec armoire 09-018 Armoire ouvrant à gauche Armoire ouvrant à droite DESSUS AVANT CÔTÉ Armoire de retour de droite illustrée dans les vues dimensionnelles Ensemble du Cabinet Grille Dessus plat...
  • Page 42 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Données dimensionnelles – armoire à dessus incliné 09-018 Armoire ouvrant à droite Armoire ouvrant à gauche DESSUS 80° CÔTÉ AVANT Armoire de retour de droite illustrée dans les vues dimensionnelles Ensemble du Cabinet Grille Dessus incliné...
  • Page 43 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Données dimensionnelles – cadre 09-018 LC09-12 37 8 29 1 10 2 21 6 16 7 16 2 015-018 DÉBIT D’AIR DE 33.1 42.7 33.6 12.1 SORTIE D’EAU 12,7 mm (1/2 po) FPT 2.10 ENTRÉE D’EAU 12,7 mm...
  • Page 44 GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Données dimensionnelles – détails des commandes : Cadre à dessus plat Retour de gauche Retour de droite Interrupteur en option du ventilateur Panneau de commande (à retirer pour accéder au boîtier de commande) Panneau de commande (à...
  • Page 45: Données Physiques

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Données physiques Console Modèle Compresseur (1 chacun) Rotatif Charge d’usine R454B, kg [oz] 0,62 [22] 0,62 [22] 0,74 [26] 0,74 [26] Moteur du ventilateur et ventilateur Type/vitesses du moteur du ventilateur 3 vitesses Moteur du ventilateur –...
  • Page 46: Notes Sur Le Démarrage De L'unité

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Notes sur le démarrage de l’unité Déconnexion électrique Contrôleur de boucle hydronique pour Le sectionneur de console installé sur place en option assure un les installations de chaudière et de tour raccord électrique permanent au service d’alimentation électrique Le contrôleur de boucle hydronique est un panneau de commande principal.
  • Page 47: Démarrage De L'unité

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Démarrage de l’unité Avant d’alimenter l’appareil, vérifier ce qui suit : • La haute tension est correcte et correspond à la plaque d’identification. • Les fusibles, les disjoncteurs et le calibre des fils sont appropriés. •...
  • Page 48: Retrait Et Évacuation Du Réfrigérant

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer des La charge de réfrigérant doit être récupérée dans les bouteilles de réparations, ou pour toute autre fin, vous devez suivre les procédures récupération appropriées si la ventilation n’est pas autorisée par conventionnelles.
  • Page 49: Récupération Du Réfrigérant

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité. Lors du transfert du réfrigérant dans des bouteilles, assurez-vous que seules des bouteilles appropriées de récupération de réfrigérant sont utilisées.
  • Page 50: Analyse Du Cycle De Réfrigération

    GUIDE D’INSTALLATION DE LA CONSOLE DE POMPE THERMIQUE HYDRAULIQUE/GÉOTHERMIQUE Analyse du cycle de réfrigération FOURNISSEUR : NUMÉRO DE TÉLÉPHONE : DATE : PROBLÈME : NUMÉRO DE MODÈLE : Formulaire de démarrage/dépannage NUMÉRO DE SÉRIE : ANALYSE DU CYCLE DE REFROIDISSEMENT SAT °F °F Ampérage...
  • Page 51: Guide De Révision

    Guide de révision Pages  Description  Date  Par  Toutes Création de document 15 avril 2024...
  • Page 52 Fabriqué par WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com (en anglais seulement) *IGV3-0008W* Produit : Console Versatec 300 Type : Pompe à chaleur géothermique/aquathermique Taille : 0,75 à 1,0 tonne Document : Manuel d’installation IGV3-0008W 08/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. La politique de WaterFurnace en matière de recherche et de développement...