INSTALLATION GUIDE
TruClimate 100
R-454B
60Hz
Reversible Water-to-Water Heat Pump
General Installation Information ................................................................................................ 2
Refrigeration Detection and Mitigation ................................................................................. 4
Serial Plate ......................................................................................................................................... 8
Dimensional Data ............................................................................................................................ 9
Physical Data .................................................................................................................................... 11
Electrical Data .................................................................................................................................. 12
Installation ......................................................................................................................................... 13
Water Connections & Water Quality ....................................................................................... 15
Field Wiring and Control Setup ................................................................................................ 18
Reference Calculation, Legend and Unit Startup ............................................................... 20
Refrigerant Removal and Evacuation ..................................................................................... 21
Charging Procedures ..................................................................................................................... 21
Refrigerant Recovery..................................................................................................................... 22
Refrigeration Cycle Analysis ....................................................................................................... 23
Revision Guide ................................................................................................................................. 34
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All WaterFurnace products are designed,
tested, and manufactured to comply with the latest
publicly released and available edition of UL 60335-2-
40 for electrical safety certification. All field electrical
connections must follow the National Electrical Code
(NEC) guide standards and / or any local codes that may
be applicable for the installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
WARNING
CAUTION
NOTICE
Conforms To UL STDS 60335-1 & 60335-2-40
Certified To CSA STDS C22.2 # 60335-1 & 60335-2-40
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
death or serious injury.
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
serviceman with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
All TruClimate 100 products are tested in accordance to ISO
13256-2 Standard for Water-Cooled Water Chilling and Heat
Pump Water-Heating Packages.
IGT1-0027W
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TRUCLIMATE 100 and is the answer not in the manual?

Questions and answers

Summary of Contents for Water Furnace TRUCLIMATE 100

  • Page 1: Table Of Contents

    Indicates a situation that could result in NOTICE equipment or property damage. All TruClimate 100 products are tested in accordance to ISO Conforms To UL STDS 60335-1 & 60335-2-40 13256-2 Standard for Water-Cooled Water Chilling and Heat Certified To CSA STDS C22.2 # 60335-1 & 60335-2-40...
  • Page 2: General Installation Information

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP General Installation Information NOTICE: Do not store or install units in corrosive environments No person carrying out work in relation to a REFRIGERATING SYSTEM which involves exposing any pipe work shall use any or in locations subject to temperature or humidity extremes. sources of ignition in such a manner that it may lead to the risk of Corrosive conditions and high temperature or humidity can fire or explosion.
  • Page 3 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 64 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Example: For instance, if your elevation is 5249Ft (1500mm) WARNING your area factor would be 1.12.  If your charge weight is 80oz (2.268 kg) at a floor height installation.  The Amin would be Check that cabling will not be subject to wear, corrosion, excessive 516 square Ft (48.0 square meters). ...
  • Page 5 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Charge Amin Area (A1) Exhaust Area (EAmin) Ventilation (Qmin) Model ft^3/min m^3/hr T1RM020SN2 9.00 4.08 26.6 57.2 18.0 T1RM030SN2 10.50 4.76 37.3 80.2 19.6 T1RM050SN2 19.00 8.62 85.3 183.6 17.1...
  • Page 6 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation External Relay/Blower for Mitigation For applications in an ASHRAE 15 Room, wire these Alarm Connections to Room Mitigation System. Otherwise, field wire to External Relay/Blower for Mitigation. 24VAC When Alarmed FIELD WIRING...
  • Page 7 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Natural Ventilation to the Outdoors or Adjacent Indoor Space Nature ventilation can be achieved by ensuring that there is a connected space to the room housing the equipment. There must be a permanent opening between the spaces.
  • Page 8: Serial Plate

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Serial Plate Unit Nomenclature and Serial Number Unit Voltage Fuse/Breaker Size Component Electrical Information Min. distance to combustible surface (in/cm) Max. outlet air temperature )F/C) Unit Restrictions Max. external static pressure (in water/Pa) Max. inlet water temperature (F/C) Max.
  • Page 9: Dimensional Data

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Dimensional Data: Dimensional Data Dimensional Data Dimensional Data for unit with enclosure Dimensional Data for unit with enclosure Model Model 64.2 24.1 50.5 15.4 15.5 15.4 12.1 020-030 120-180 [1631] [612] [1283] [175] [432] [353] [432] [307]...
  • Page 10 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Dimensional Data: cont. Dimensional Data Dimensional Data for unit with enclosure Dimensional Data for unit with enclosure Model Model 120-180 65.0 42.0 69.9 19.9 19.5 020-030 240-360 [1651] [1067] [1775] [505] [495] [246] [46] 70.0 42.0 76.8...
  • Page 11: Physical Data

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Physical Data Reversible Water-to-Water Heat Pump Model Reversible Water-to-Water Heat Pump Refrigerant R-454B Number of Circuits Factory Charge, lbs [kg]* 7.00 [3.18] 11.50 [5.22] 19.00 [8.61] Compressor Single Speed Scroll Compressor Quantity [tons] 2 [10] 2 [15] 2 [25] Compressor Weight, lbs [kg] (each)
  • Page 12: Electrical Data

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Electrical Data Reversible Water-to-Water Heat Pump (20-50 Ton) Electrical Table Rated Voltage Total Compressor Model Voltage Min/Max Unit Circ Fuse/ Fuse/ HACR HACR 208-230/60/3 187/253 52.2 35.2 250.0 70.4 79.2 80.0 460/60/3 414/506 27.0 19.2 140.0 38.4...
  • Page 13: Installation

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Installation Information Safety Considerations Unit Location Installing and servicing air conditioning and heating equipment Provide sufficient room to make water and electrical can be hazardous due to system pressure and electrical connections. If the unit is located in a confined space, components.
  • Page 14 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Installation Information Mounting Units Remove the unit from the wooden shipping skids (see physical dimensions). Units do not ship standard with vibration isolation hardware, however, non-standard options are selectable for the unit. Non-standard options include: •...
  • Page 15 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Installation Information - Field Connected Water Piping General NOTE: The placement and connection of the water circulating pump(s) must be taken into consideration prior System piping should be kept as simple as possible to to designing the final water piping systems.
  • Page 16 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Water Quality 1.0. Minimum Fluid Volume 1.4. Flow Sensing Devices Water-to-water heat pumps require a minimum amount A fl ow switch or equivalent must be installed on the of source and load side fl uid volume to ensure accurate evaporator for each unit to be installed.
  • Page 17 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Water Quality cont. 1.6. Insulation 1.7. Brine Applications Heat pumps are built with factory installed insulation Applications where the leaving fl uid temperature goes on any surface that may be subject to temperatures below 40°F a suitable brine solution must be used. below the room dew point.
  • Page 18: Field Wiring And Control Setup

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Field Wiring and Control Setup Line Voltage Pump Control Power supply wiring connects directly to lugs on the top Slow Opening Valve Wiring of the electrical disconnect. In 208-230V applications, heat pumps are factory wired for 208V supply. In the case of The accessory output on either one of the ABC Aurora 230V supply, the blue and red wires from the primary of the boards can be used to control either a slow opening valve...
  • Page 19 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Field Wiring and Control Setup cont. Flow Switch Operation Slow Opening Valve Wiring cont. Slow Source Flow Switch (SFS) Unit is factory shipped with no connections on Flow Switch wires from HA1 off AXB-A (entering). If flow proving switch is required, hook up as shown in the figure and Note 1.
  • Page 20 INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + GPM x 500* GPM x 500* NOTE: * When using water. Use 485 for 15% methanol/water or Environol solution. Legend Abbreviations and Definitions = entering load fluid temperature to heat pump = pressure drop in pounds per square inch...
  • Page 21: Refrigerant Removal And Evacuation

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Refrigerant Removal and Evacuation This process might need to be repeated several times. Com- When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be used. pressed air or oxygen shall not be used for purging refriger- However, for flammable refrigerants it is important that best ant systems.
  • Page 22: Refrigerant Recovery

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.
  • Page 23: Refrigeration Cycle Analysis

    INSTALLATION GUIDE: REVERSIBLE WATER-TO-WATER HEAT PUMP Refrigeration Cycle Analysis PSIG = Condenser Discharge Filter Suction Drier Compressor Evaporator PSIG = Unit Amp Draw Entering Hot Water Line Voltage Entering Water Pressure PSIG Subcooling Leaving Hot Water Superheat Leaving Water Pressure PSIG Entering Chilled Water Entering Water Pressure...
  • Page 24: Revision Guide

    Physical data table (charge weights), tonnage listing adjustment, AHRI safety listing 23 May 2024 language adjustment Manufactured at 9000 Conservation Way Fort Wayne, IN 46809 *IGT1-0027W* Product: TruClimate 100 Type: Reversible Water-to-Water Heat Pump - 60 Hz Size: 20-50 Tons Document: Installation Manual IGT1-00027W 05/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794.
  • Page 25 Indique une situation qui pourrait endommager AVIS l’équipement ou la propriété. Tous les produits TruClimate 100 sont testés conformément à la Conforme aux normes UL 60335-1 et 60335-2-40 Certifié conforme aux normes CSA C22.2 # 60335-1 et norme ISO 13256-2 pour les ensembles de refroidissement par eau et 60335-2-40 de chauffage de l’eau par pompe à...
  • Page 26: Informations Générales Sur L'installation

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations générales sur l’installation AVIS : Ne pas installer les unités dans un environnement corrosif Aucune personne effectuant des travaux sur un SYSTÈME FRIGORIFIQUE impliquant l’exposition d’une tuyauterie ne doit ou dans des endroits soumis à des températures extrêmes ou à utiliser des sources d’inflammation de manière à...
  • Page 27 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations générales sur l’installation Espace d’installation requis AVERTISSEMENT REMARQUE : Le matériel dont la charge de réfrigérant est inférieure Zone ventilée : assurez-vous que la zone est à découvert ou qu’elle à 64 oz n’exige pas une surface de plancher minimale et ne nécessite est correctement ventilée avant d’intervenir dans le système ou de pas de capteur de détection de fuite de réfrigérant.
  • Page 28: Détection Et Atténuation Des Fuites De Réfrigérant

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Exemple : si votre altitude est de 1500 m (5249 pi) votre facteur AVERTISSEMENT de zone serait 1,12. Si le poids de votre charge est de 2,268 kg (80 oz) à...
  • Page 29 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Charge Smin Surface (A1) Section de sortie (SSmin) Ventilation (Qmin) Modèle pi^3/min m^3/hr T1RM020SN2 9,00 4,08 26,6 57,2 18,0 T1RM030SN2 10,50 4,76 37,3 80,2 19,6 T1RM050SN2...
  • Page 30 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Relais externe/ventilateur soufflant pour l’atténuation Pour les applications dans une salle ASHRAE 15, câblez ces raccords d’alarme au système d’atténuation de la salle. Sinon, câblez sur place le relais externe/ventilateur soufflant pour...
  • Page 31 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Ventilation naturelle vers l’extérieur ou l’espace intérieur adjacent La ventilation naturelle peut être obtenue en veillant à ce qu’il y ait un espace connecté à la salle abritant le matériel. Il doit y avoir une ouverture permanente entre les espaces.
  • Page 32: Plaque Signalétique

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Plaque signalétique Unit Nomenclature and Serial Number Unit Voltage Fuse/Breaker Size Component Electrical Information Min. distance to combustible surface (in/cm) Max. outlet air temperature )F/C) Unit Restrictions Max. external static pressure (in water/Pa) Max. inlet water temperature (F/C) Max.
  • Page 33: Données Dimensionnelles

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Données dimensionnelles : Réversible Données dimensionnelles Dimensional Data Données dimensionnelles pour l’unité avec enceinte Dimensional Data for unit with enclosure Modèle Model 64,2 24,1 50,5 15,4 15,5 15,4 12,1 020-030 120-180 [1631] [612] [1283] [175] [432] [353] [432] [307]...
  • Page 34 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Données dimensionnelles : réversible (suite) Dimensional Data Dimensional Data for unit with enclosure Données dimensionnelles pour l’unité avec enceinte Model Modèle 120-180 65,0 42,0 69,9 19,9 19,5 020-030 240-360 [1651] [1067] [1775] [505] [495] [246] [46] 70,0 42,0 76,8...
  • Page 35: Données Physiques

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Données physiques Thermopompe eau-eau réversible Thermopompe eau-eau réversible Modèle Réfrigérant R-454B Nombre de circuits 7.00 [3.18] 11.50 [5.22] 19.00 [8.61] Charge d’usine, lb [kg]* Spirale à une vitesse Compresseur Volume du compresseur [tonnes] 2 [10] 2 [15] 2 [25] Poids du compresseur, lb [kg] (chaque)
  • Page 36: Données Électriques

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Données électriques Tableau électrique de la thermopompe eau-eau réversible (20-50 tonnes) Tension nominale Tension Total Min. Min. Max. Compresseur Modèle min/max de l’unité Circ fusible/ fusible/ HACR HACR 208-230/60/3 187/253 52,2 35,2 250,0 70,4 79,2 80,0 460/60/3 414/506...
  • Page 37: Installation

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Information sur l’installation Considérations de sécurité Emplacement de l’unité L’installation et l’entretien des appareils de climatisation et de Prévoyez un espace suffisamment grand pour effectuer les chauffage peuvent être dangereux en raison de la pression du raccords d’eau et d’électricité.
  • Page 38 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Information sur l’installation Montage des unités Retirez l’unité des palettes d’expédition en bois (voir les dimensions physiques). Les unités ne sont pas livrées de série avec du matériel d’isolation des vibrations, mais des options non standard peuvent être sélectionnées pour l’unité. Les options non standard comprennent : •...
  • Page 39 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Informations sur l’installation – Tuyauterie d’eau raccordée sur place Généralités REMARQUE : L’emplacement et le raccordement des pompes de circulation d’eau doivent être pris en compte avant de La tuyauterie du système devrait être aussi simple que possible concevoir les systèmes de tuyauterie d’eau finaux.
  • Page 40 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Qualité de l’eau 1.0 Volume minimal de liquide 1.4 Dispositifs de détection de débit Les thermopompes eau-eau exigent une quantité Un régulateur de circulation d’eau ou l’équivalent doit être minimale de liquide du côté source et du côté charge pour installé...
  • Page 41 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Qualité de l’eau (suite) 1.6 Isolant 1.7 Application de saumure Les thermopompes sont construites avec un isolant Pour les applications où la température du liquide de installé en usine sur toute surface qui peut être soumise à départ est inférieure à...
  • Page 42: Câblage Sur Place Et Configuration Des Commandes

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Câblage sur place et configuration des commandes Tension composée Commande de pompe Le câblage d’alimentation électrique est raccordé directement Câblage de robinet à ouverture lente aux cosses sur le dessus du disjoncteur. Dans les applications de 208-230 V, les thermopompes sont câblées en usine pour une La sortie accessoire sur l’une ou l’autre des cartes ABC Aurora alimentation de 208 V.
  • Page 43 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Câblage sur place et configuration des commandes (suite) Fonctionnement du régulateur de Câblage de robinet à ouverture lente (suite) Câ Câ Câbl blag circulation d’eau Régulateur de circulation d’eau de la source (RCES) L’unité est expédié par l’usine sans connexion sur les fils de régulateur de circulation d’eau HA1 hors AXB-A (entrée).
  • Page 44 MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Calculs de référence Calculs de chauffage : Calculs de refroidissement : LWT = EWT - LWT = EWT + GPM x 500* GPM x 500* REMARQUE : * lorsque vous utilisez de l’eau, utilisez 485 pour 15 % de méthanol/eau ou de solution Environol. Légende Abréviations et définitions = entering load fluid temperature to heat pump (température...
  • Page 45: Retrait Et Évacuation Du Réfrigérant

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer des Ce processus devra peut-être être répété plusieurs fois. L’air réparations, ou pour toute autre fin, vous devez suivre les comprimé et l’oxygène ne doivent pas être utilisés pour purger procédures conventionnelles.
  • Page 46: Récupération Du Réfrigérant

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité. Lors du transfert du réfrigérant dans des bouteilles, assurez- vous que seules des bouteilles appropriées de récupération de réfrigérant sont utilisées.
  • Page 47: Analyse Du Cycle De Réfrigération

    MANUEL D’INSTALLATION : THERMOPOMPE EAU-EAU RÉVERSIBLE Analyse du cycle de réfrigération PSIG = Condenseur Décharge Déshydra- Aspiration teur-filtre Compresseur Évaporateur PSIG = Ampérage de l’unité Entrée eau chaude Pression de l’eau à l’entrée PSIG Tension composée Sous-refroidissement Sortie eau chaude Sortie pression à chaud PSIG Surchauffe Entrée eau réfrigérée...
  • Page 48: Guide De Révision

    Physical data table (charge weights), tonnage listing adjustment, AHRI safety listing language adjustment Fabriqué à 9000 Conservation Way Fort Wayne, IN 46809 *IGT1-0027W* Produit : TruClimate 100 Type : Thermopompe eau-eau réversible – 60 Hz Taille : 10-50 tonnes Document : Manuel d’installation IGT1-00027W  05/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794.