3 = IntelliStart NOTE: MUI = Medium User Interface All 5 Series 502W12 product is safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-2. The 5 Series 502W12 is also Energy Star rated.
5 SERIES 502W12 INSTALLATION MANUAL General Installation Information Safety Considerations Unit Location Installing and servicing air conditioning and heating Provide sufficient room to make water and electrical equipment can be hazardous due to system pressure and connections. If the unit is located in a confined space, electrical components.
Load Flow Rate with the ability to measure water temperatures and The load flow on the 5 Series 502W12 should be 20 gpm pressures. The water lines should be routed so as not to (typically the rated flow). Refer to the table below. This interfere with access to the unit.
5 SERIES 502W12 INSTALLATION MANUAL Field Connected Water Piping cont. Open Loop Well Water Systems Installation of an open loop system is not recommended unless water quality guidelines are met. Well Tank Earth Coupled Systems All supply and return water piping should be insulated to...
5 SERIES 502W12 INSTALLATION MANUAL Water Quality The following table outlines the water quality guidelines for unit General heat exchangers. If these conditions are exceeded, a secondary Reversible chiller systems may be successfully applied in a heat exchanger is required. Failure to supply a secondary heat wide range of commercial and industrial applications.
5 SERIES 502W12 INSTALLATION MANUAL Physical Data Model Compressor (2 each) Scroll Factory Charge R-134a, oz [kg] 76 [2.16] Load Water Connection FPT - in 1.25 Source Water Connection FPT - in 1.25 Weight - Operating, lb [kg] 420 [190]...
5 SERIES 502W12 INSTALLATION MANUAL Wiring Schematics cont. 208-230/60/1 Compressor Compressor Current Switch ( Circuit A ) ( Circuit B ) Current Switch Blue Blue Black Black Black Black Black Black Tan (52B) Tan (52A) Unit Power Supply #2 Unit Power Supply #1...
Page 13
5 SERIES 502W12 INSTALLATION MANUAL Wiring Schematics cont. 208-230/60/1 cont. External Timer (delay on close) NOTE 10 Source Load Black (101) Black Pump Pump NOTE 1 208V Blue 230V Black/White Yellow Black (C) Black/White (26) Black (95) 24VAC COM Red (104)
Page 14
5 SERIES 502W12 INSTALLATION MANUAL Wiring Schematics cont. 208-230/60/1 with IntelliStart Compressor ( Circuit A ) Compressor Current Switch Current Switch ( Circuit B ) Blue Black Blue Black Black Black Black Black Blue Blue Tan (52B) Tan (52A) Pink...
Page 15
5 SERIES 502W12 INSTALLATION MANUAL Wiring Schematics cont. 208-230/60/1 with IntelliStart cont. External NOTE 10 Load Source Timer (delay on close) Pump Pump Black (101) Black NOTE 1 208V Blue 230V Black/White Yellow Black (C) Black/White (26) Black (95) 24VAC COM...
Page 16
5 SERIES 502W12 INSTALLATION MANUAL Wiring Schematics cont. MUI Wiring Diagram Instructions : 5VDC DLI Card 1.) Disconnect all power sources to the unit 2.) Remove MUI from Back Plate 3.) Follow Wiring Instruction Below NOTE 7 4.) Reinstall MUI to Back Plate...
5 SERIES 502W12 INSTALLATION MANUAL Field Wiring and Control Setup Figure 2 - High Voltage Connections Line Voltage High Voltage Connections Connect power wiring as shown in Figure 2. 208 Volt Operation Switch red and blue transformer wires for 208V operation.
5 SERIES 502W12 INSTALLATION MANUAL Field Wiring and Control Setup cont. Accessory Relay Setup °F or °C - Unit of Measure The accessory output set to “close” upon Y1 compressor call Degrees Fahrenheit is factory set, however degrees Celsius (compressor is delayed 90 sec. after Y1) but can be set to can be selected using the following procedure: “open”...
Page 19
5 SERIES 502W12 INSTALLATION MANUAL Control Features cont. Basic Freeze Detection Operation: “Comp1 or condition, the compressor is allowed to operate so that Comp2 Freeze” Alarm the refrigerant temperature may eventually be at the threshold of the freeze detection setpoint. NOTE: This This alarm can be triggered by one of two detection schemes.
5 SERIES 502W12 INSTALLATION MANUAL Control Features cont. is open continuously for (30) seconds the compressor Compressor 2 Alarm Output (DO-6) output for that circuit will be disabled. The compressor The compressor 2 alarm output will be enabled when stage...
5 SERIES 502W12 INSTALLATION MANUAL Inputs and Outputs Confi guration DUAL STAGE WW Input Name Input Output Name Output Entering Load Water Temperature AI 1 Compressor 1 Leaving Load Water Temperature 1 AI 2 Compressor 2 Source Heating Freeze Detection 1...
Page 22
5 SERIES 502W12 INSTALLATION MANUAL Unit Display and Interface cont. MUI Menu Navigation Welcome Info Temp Stat Outputs Settings Maint Alarm_History Temp Info Stat Outputs Settings Outputs Status Dual Stage Temperatures Settings Unit Status Auto Comp1 Status Water-to-Water Enter Load 77.2°F...
Page 23
5 SERIES 502W12 INSTALLATION MANUAL Unit Display and Interface cont. Source Flow – Source Flow Switch is Not Closed Menu and Menu Contents • The source flow switch must be closed prior to either Alarm compressor starting and must remain closed for the •...
5 SERIES 502W12 INSTALLATION MANUAL Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + gpm x 500* gpm x 500* NOTE: * When using water. Use 485 for 15% methanol/water or Environol solution. Legend ABBREVIATIONS AND DEFINITIONS: = coefficient of performance (HC/kW x 3.413)
5 SERIES 502W12 INSTALLATION MANUAL Startup and Troubleshooting Form Company Name: _________________________________ Company Phone No: ______________________________ Technician Name: ________________________________ Date: __________________________________________ Model No: ______________________________________ Serial No:_______________________________________ Owner’s Name: __________________________________ Open or Closed Loop: _____________________________ Installation Address: ______________________________ Installation Date: _________________________________...
5 SERIES 502W12 INSTALLATION MANUAL Troubleshooting Should a major problem develop, refer to the following The internal winding of the compressor motor may information for possible causes and corrective steps. be grounded to the compressor shell. If so, replace the compressor.
5 SERIES 502W12 INSTALLATION MANUAL Revision Guide Pages: Description: Date: Updated Field Wiring and Control Setup 25 Feb 2013 Updated Sequence of Operation 25 Feb 2013 Added Revision Guide 25 Feb 2013...