Pro-G Automation for sectional and rolling doors EN - Instructions and warnings for installation and use...
Page 2
NICE CANADA warrants that materials and workmanship are free from defects for a period of two years from the date of invoice. Materials returned to Nice deemed defective after examination will be returned at the option of Nice with repaired, new or re-manufactured parts.
Page 3
TABLE OF CONTENTS PAGE: WARRANTY _________________________________________________________________ VERIFICATION OF OPERATOR AND HARDWARE ______________________________ SPECIFICATIONS ___________________________________________________________ SAFETY INSTRUCTIONS ____________________________________________________ INSTALLATION_______________________________________________________________ ELECTRICAL CONNECTIONS AND SETTINGS___________________________________ LIMIT SWITCH ADJUSTMENT _______________________________________________ PHOTOBEAM INSTALLATION INSTRUCTIONS__________________________________ MECHANICAL LOAD SENSING ADJUSTMENT_________________________________ EMERGENCY MANUAL OPERATION _________________________________________ OPERATOR MAINTENANCE _________________________________________________ MECHANICAL DRAWINGS AND PARTS LISTS ________________________________ ELECTRICAL DIAGRAMS ______________________________________________________ OPTIONS...
Page 4
CONTACT NICE AT 1-877-888-1116 SAVE THESE INSTRUCTIONS VERIFICATION OF OPERATOR AND HARDWARE Upon delivery of your Nice medium duty gearhead jackshaft door operator, please inspect the unit carefully for damage. Verify that operator horsepower, voltage, phase and amperage correspond to available power supply and door application.
IMPORTANT SAFETY INSTRUCTIONS WARNING TO REDUCE THE RISK OF INJURY OR DEATH: READ AND FOLLOW ALL INSTRUCTIONS Never allow children to operate or play with door controls. Keep the remote control (where provided) away from children. Personnel should keep away from a door in motion and keep the moving door in sight until it is completely closed or opened.
INSTALLATION INSTRUCTIONS WARNING DO NOT INSTALL THIS OPERATOR BEFORE READING THIS MANUAL CAREFULLY. Note: - Installation of operator must be done by a qualified installer. Door must be properly installed and working smoothly. Remove all door locks prior to installation. - For the PRO-GJ operators the handing of the operator must be stated at time of order.
Page 8
As a general rule, the door operator should be installed below the drive shaft and as close to the door as possible. The ideal distance between the operator drive shaft and the door shaft is approximately 12” (30cm) to 15” (38cm). The operator may be wall/bench mounted or bracket /shelf mounted.
Page 9
Install chain keeper to wall below operator at approximately 4’ from floor. Run disconnect chain through keyhole of chain keeper and cut excess chain links if required. Attach keyring to end of disconnect chain. If an optional floor level disconnect lever was ordered in lieu of the chain keeper, mount to wall with suitable hardware.
MSLLHR-WW or MSLLHR220-WW, in the electrical drawings section at the end of this manual. IMPORTANT NICE HIGHLY RECOMMENDS THAT EACH INDIVIDUAL COMMERCIAL DOOR OPERATOR HAVE IT’S OWN DEDICATED POWER SUPPLY NICE HIGHLY RECOMMENDS THAT EACH INDIVIDUAL COMMERCIAL DOOR...
SECTION A: PRO-GJ Standard relay logic controls (not UL325 (2010) compliant, not available in US) CONNECTION OF POWER SUPPLY AND CONTROL STATION POWER WIRING: Use 1-1/8” (2.85 cm) diameter holes for all power wiring. Single phase: Connect single phase power supply to terminals L/L1 (line) and N/L2 on three-pole power terminal strip.
Page 12
CONNECTION OF A REVERSING EDGE DEVICE AND CONTROL ACCESSORIES Reversing Edge device (must be normally open contact): Note: If the door is controlled by any device or wired in such a manner that the door is not controlled by constant pressure on close then an appropriate reversing edge must be installed. External interlock: Remove jumper between terminals 1 and 2 and wire a N.C.
NOTE: THIS OPERATOR COMES WITH AN I NTERFACE MODULE INTEGRATED INTO THE CONTROL CIRCUIT. THE PURPOSE OF THE INTERFACE MODULE IS TO ALLOW FOR FAILSAFE MONITORING OF A NICE COMPATIBLE SAFETY DEVICE AS PER UL 325 (2010) REQUIREMENTS. Important: Follow these steps carefully and in the order shown 1) Connect Power supply: Single phase: Connect single phase power supply to terminals L/L1 and N/L2 on the 3-pole power terminals strip.
Page 14
3-phase operators (1/2 HP 230V, 460V, 575V 60 Hz or 380V 50Hz): If door moves in wrong direction, turn off incoming power and reverse any two of the three incoming power supply leads to correct rotation. Press the open button and then activate the open limit to ensure door stops.
Page 15
Note: Only one monitored failsafe safety device can be connected across terminals P1 and P2. Note: See section E for complete installation instructions for the Nice N-1 or the Fraba photocells. Secondary non-monitored safety device(s): A standard 2-wire safety edge, non-monitored reflective or thru-beam photo eye or any other non-monitored reversing devices with a N.O dry contact can be connected to terminals S1 and S2.
SECTION C: PRO-GJ(E) Limited Duty Smart 5.0 logic board (UL325 (2010) compliant) Note: The operator is shipped from the factory in the C2 mode (constant pressure close and momentary open). The operator should remain in this mode until all connections and limit switch adjustments are completed. POWER WIRING INSTRUCTIONS: Connect primary power supply directly to the separate power terminal strip supplied using any of the 1-1/8"...
Page 17
1 or more secondary non-monitored safety device(s). Primary monitored safety device: Nice monitored failsafe photo beams or Nice compatible monitored failsafe devices must be connected to terminals Pl and P2 as primary monitored safety device. Primary monitored safety device must be connected if momentary activation on close is required in B2, T and TS modes.
Page 18
CONNECTION OF EXTERNAL SINGLE-BUTTON DEVICE Connect an external single-button as shown in diagram. Please refer to ''Modes of operation'' for the functionality of singlebutton. "' ...J SINGLE PUSH-BUTT� ___L_ GENERAL INFORMATION: Auxiliary device may be installed to edge terminals, open or close button terminals, and single button terminals providing that they are of the NORMALLY OPEN DRY CONTACT TYPE.
Page 19
TS: (Momentary on open and close, timer to close secure, STOP BUTTON DISABLES TIMER) • Open Button: Momentary activation opens the door. When door is closing, momentary activation reverses the door. Momentary contact at full-open position re-activates the timer if timer has been disabled previously by stop button. •...
SECTION D: For all operator control types LIMIT SWITCH ADJUSTMENT Adjustment of door travel is done by moving the limit cams on the threaded shaft. The position of the 4 limit switches are factory adjusted and should not be altered. The limit switches are: - "Open"...
IMPORTANT: For momentary activation on close, the Nice photobeams (or a Nice 2-wire monitored edge), must be installed as part of the operator system. If a Nice 2-wire monitored edge or the Nice infrared photobeam system is not installed (or not operating correctly), the operator will only operate in fault mode (constant pressure to close).
Page 22
> > L ______ _ NICE N-4 PHOTOCELL (MK00650) Note: The MK00650 photocell system has a maximum range of 24ft. Sun visor protector optional. Installation Note: Photo beams should be mounted as close to the door track inside the door to offer maximum entrapment protection.
Page 23
Photo system operation: Nice photo beams must be connected for the door to close in momentary mode (unless a Nice monitored 2-wire edge is connected). When the photo system is properly installed and aligned, the infrared beam will detect any obstruction in the path of the beam.
Page 24
FRABA N-4/4X THRU-BEAM PHOTOCELL (MK00697) Note: The MK00697 photocell system has a maximum range of 45 ft. Sun visor protector optional. 1. Select a location on the wall no more than 6 inches from the floor to install wall mounting brackets on the left and right side of the door.
Page 25
MECHANICAL EXTERNAL LOAD SENSING ADJUSTMENT If the operator is equipped with an optional Mechanical External Load Sensing feature (MP00107): If the grille/gate is obstructed or locked while opening then the load sensing feature will activate and and stop grille/gate movement. Upon activation of the load sensing feature, you must initiate a close command to reset the system. NOTE: SPRING TENSION ADJUSTMENT WINNG NUT MUST BE ADJUSTED PER INSTALLATION.
Page 26
EMERGENCY MANUAL OPERATION The PRO-GJ operator is equipped with an emergency disconnect device to manually operate door in case of emergency. This feature should not be used to manually operate a malfunctioning door. WARNING TO REDUCE THE RISK OF INJURY OR DEATH: DO NOT ATTEMPT TO USE EMERGENCY DISCONNECT SYSTEM WHILE OPERATOR IS RUNNING.
OPERATOR MAINTENANCE WARNING TO REDUCE THE RISK OF INJURY OR DEATH: DO NOT ATTEMPT TO SERVICE THE OPERATOR UNLESS POWER SUPPLY HAS BEEN DISCONNECTED Inspect manual function of the door every 3-months. Make sure that door runs smoothly. If door does not manually open or close freely, have a qualified service person make repairs.
Page 30
□ CLOSE --------□ □ RANGE RAD! □ RANGE. - ---�-., RECEIVER - - - - +- +-+-+-- - G RAY NOTE: TO REVERSE MOTOR ROTATION CAPACITOR INTERCHANGE RED 70UFD 240VAC AND YELLOW WIRE ON CAPACITOR. �-t----- R ED---+--+-+-+-+-+-+-------- BL ACK - +- -+-+-+-+-+-+- - - - - - - - ...
Page 31
□ ( CLOSE ) □, N.C. RADIO 24V CONTACT POWER ..@l@l@I >- >- >- "' "' "' L'.l L'.l L'.l � � N.C. N.C. ADVANCED ADVANCED GRAY OPEN CLOSE □. □. L IMIT LIMIT Sl.'ITCH Sl.'ITCH >- � !i:i�i:: NOTE: TO REVERSE MOTOR ROTATION...
Page 32
� - DRANGE- - - - - - - - - - DRANGE ( □ COM ( ,--� --- il - ,I R ANGE �--- □RANGE ---�--. CLOSE ) RAD! □ N.O. RECEIVER □ □ P EN � CLOSE BRAKE S LENlID (IF USED) LIMIT LIMIT...
Page 33
RANGE RANGE □ CLOSE RAD! ORANGE ORANGE □ □ RECEIVER □ LIMIT □. S\/ITCH GRAY □ I f I f I GRAY ' -- - + - + - + - + - GRAY - GRAY � -·=- - - - BLUE □.
Page 34
OPEN ( CLOSE ) -RED- - - *NOTE: RAD! � TO REVERSE □ RECEIVER . ,-- --�-- -----. MOTOR CLOSE LIMIT LIMIT ROTATION � □ □ S\IITCH □ S\IITCH -RED GRAY - - - INTERCHANGE ' ' Q RED AND YELLOW WIRE �...
Page 35
ANGE- �□RANGE BRAKE SII..EN□ID <Ir USED) ..__ COM ANGE RANGE RADm OPEN CLOSE REC□VER lK 0-2 inZY •I - - ->-- - - -+-� CLOSE LIMIT SI/ITCH r:· Q N,C, □ N,C, Q IMIT SI/ITCH _RAY- -RED :� 380 VAC BLUE ru\n □...
Page 36
.& OPEN CLOSE ) IF STOP BUTTON GRAY USEO, REMOVE JUMPER RADIO CLOSE LIMIT BETWEEN "STOP" AND RECEIVER "COM" TERMINALS. □ S\JITCH YELL MICANAN MONITORED PHOTO BEAMS OR MICANAN Q ADVANCED LACK COMPATIBLE MONITORED CLOSE LIMIT SAFETY DEVICES MUST BE S\IITCH CONNECTED TO Pl AND P2 BLUE...
Page 37
OPEN -�----GRAY � IF STOP BUTTON RADIO USED, REMOVE JUMPER RECEIVER BETWEEN 'STOP' AND 'COM' TERMINALS. MICANAN f..£). MONITORED PHOTO BEAMS OR MICANAN COMPATIBLE MONITORED SAFETY DEVICES MUST BE CONNECTED TO Pl AND P2 FOR THE DOOR TO CLOSE IN MOMENTARY MODE (B2 OR TS).