Analogue threshold display (IP 69K) DP4200 1 Preliminary note You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at documentation.ifm.com. 1.1 Symbols used Requirement Instructions Reaction, result [...] Designation of keys, buttons or indications...
DP4200 Analogue threshold display (IP 69K) 2 Safety instructions • The unit described is a subcomponent for integration into a system. – The system architect is responsible for the safety of the system. – The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system.
Analogue threshold display (IP 69K) DP4200 3 Intended use The device is used for the evaluation of an analogue signal (4...20 mA) from a connected sensor or another device with analogue output (4...20 mA). The device has one analogue current input and two outputs: output 1 (digital) and optionally output 2 (analogue current output).
DP4200 Analogue threshold display (IP 69K) 4 Function There are basically two modes in which the device can be operated: • As stand-alone device The device compares the measured current value with the set parameters and switches its output according to the selected parameters. This mode is without IO-Link functionality. The parameters can only be set with an IO-Link tool.
Analogue threshold display (IP 69K) DP4200 4.2.2 Application example 4...20 mA Fieldbus 4...20 mA 24 V DC Fig. 3: Application example with IO-Link master Sensor with analogue output (e.g. pressure sensor) Threshold display Fully bidirectional IO-Link communication Looping through an analogue input signal •...
DP4200 Analogue threshold display (IP 69K) 5 Installation ATTENTION Higher shock ≥ IK06 w Damage possible w Protection rating and, in wet environments, electrical protection might be impaired u If necessary, the system creator must take external measures to protect the device depending on the requirements of the corresponding application.
Analogue threshold display (IP 69K) DP4200 6 Electrical connection The unit must be connected by a qualified electrician. Observe the national and international regulations for the installation of electrical equipment. Voltage supply according to SELV, PELV. CAUTION Use in wet environments w Electric shock possible.
Analogue threshold display (IP 69K) DP4200 7 Operating and display elements LED I LED Power LED II Display 7.1 LEDs Colour Status Designation OUT1 yellow Output 1 switched. Power green Voltage supply OK. Device in operating mode. No voltage supply. Device switched off.
DP4200 Analogue threshold display (IP 69K) 7.2.1 Representation of the measured current value 20.5 [mA] Input current "nPrb" "UL" 3.60...21.00 mA "OL" Process 32764 -32760 3600-21000 μA 32760 data Silent nPrb events No measured data nPrb: No sensor Input current below the range (-)
Analogue threshold display (IP 69K) DP4200 8 Menu 8.1 General Irrespective of the operating mode (standard IO mode or IO-Link device), the device can be configured via an IO-Link tool. Parameter cloning and parameter setting backup is possible with an IO-Link tool.
DP4200 Analogue threshold display (IP 69K) Window upper threshold I [mA] Window lower threshold Window Fno: Window function normally open Fnc: Window function normally closed OUT1 Fig. 6: Window functions u Select [FH1] and set the upper limit. u Select [FL1] and set the lower limit.
Analogue threshold display (IP 69K) DP4200 8.2.7 C.ASP/C.AEP - customer-specific analogue start/end point Settings for scaled display values. The parameters are only displayed if [ScAL] is set to [cccc], [ccc.c], [cc.cc] or [c.ccc]. C.ASP value: -746 ... 9745 corresponds to 4 mA.
DP4200 Analogue threshold display (IP 69K) OUT1 OUT1 4 mA 20 mA 4 mA 20 mA Fig. 8: Hysteresis function with [r1ou] Fig. 9: Hysteresis function with [G1ou] 4 mA 20 mA 4 mA 20 mA Fig. 10: Window function with [r1ou] Fig. 11: Window function with [G1ou] [r-cF] = red when the measured value is between the values [cFL] and [cFH].
Analogue threshold display (IP 69K) DP4200 8.2.11 Lo/Hi ─ min/max measured input values [Lo] = lowest measured value [Hi] = highest measured value 8.2.12 dAP ─ damping Damping of the measured analogue value. Setting also influences the set point, the IO-Link process data and the display.
DP4200 Analogue threshold display (IP 69K) 9 Operation After power on, the device is in the operating mode (SIO). It carries out its measurement and evaluation functions and provides output signals according to the set parameters. 9.1 Functions output 1 OUT1 (connector, pin 4): •...
Analogue threshold display (IP 69K) DP4200 10 Troubleshooting Display Error Troubleshooting Power Supply voltage too low. Check/correct the supply voltage: Electrical connection flashes can differ can differ Excessive current at switching out- Check switching output OUT1 for put OUT1. short circuit or excessive current.
DP4200 Analogue threshold display (IP 69K) 11 Maintenance, repair and disposal The unit is maintenance-free. u Carry out cleaning considering the technical data (protection rating) and the connection technology used. u Cleaning agents must be checked by the system manufacturer / operator for their suitability for the device materials (→...