Download Print this page
IFM Electronic Efector 300 SC050R Operating Instructions
IFM Electronic Efector 300 SC050R Operating Instructions

IFM Electronic Efector 300 SC050R Operating Instructions

Flow monitor compact

Advertisement

Quick Links

Operating instructions
Flow monitor compact
UK
SC050R

Advertisement

loading

Summary of Contents for IFM Electronic Efector 300 SC050R

  • Page 1 Operating instructions Flow monitor compact SC050R...
  • Page 2: Function And Features

    1 Function and features The flow monitor monitors liquid media. It senses whether there is a preset flow and provides a switching signal. • The switch point can be set: 10...60 cm/s in steps of 5 cm/s). This value is valid for water and installation in pipes 4".
  • Page 3: Electrical Connection

    To avoid malfunction a minimum distance between the flow monitor and bends, valves, changes in cross-section or such like must min. 3 x D be observed: • Min. 5 x pipe diameter upstream (A). min. 5 x D • Min. 3 x pipe diameter downstream (B).
  • Page 4: Switch Point Setting

    The maximum current rating must not be exceeded. Even if it is exceeded for a short time the unit is destroyed. 4 Switch point setting Apply the operating voltage (+UB) to pin 2 for the specified time. IN (Pin 2) OUT = 1 OUT = 0 Time window...
  • Page 5: Operation

    5 Operation ► After mountingand wiring check whether the unit operates correctly. Recommended maintenance: ► Check the sensor tip for build-up from time to time. Clean it with a soft cloth. If necessary, build-up which adheres firmly (e.g. lime) can be removed with a common vinegar cleansing agent.