PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 1 - Panic and Fire Rated Devices a. Checklist 1 . Check device for shipping damage prior to installation and make sure all parts are on hand . 2 . Identify options provided with device . 3 .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 2 - Insert and P.C. Board Assembly, continued NOTES: y Factory keyed orders will be shipped assembled . y Prior to insert assembly, device must be cut to proper length to prevent damage to circuit board . 36"...
Page 6
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 3 - DIP Switch Settings, continued Nuisance Delay (seconds) Cover Armed LED Color is Green S2-6 Cover Armed LED Color is Red (default) Momentary egress mode 5, 10, 20 or 40 seconds . Device will immediately Rearm S2-2 OFF OFF ON OFF* After Closing (RAC) door, if closed before selected time expires or it will enter...
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 4 - Device Mounting 1 . Refer to installation instructions included with device and trim for complete door and frame preparations . Refer to template for wire access hole location . 2 .
Page 8
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 4 - Device Mounting, continued NOTE: For additional instructions on hardware install, refer to 1 . When required, mount outside trim to door (see trim 5 . Slide mount rail cover back toward chassis . installation instructions) .
Page 11
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 5 - Wire Routing, continued PE8400 Electric Trim (If applicable) 54-Lever Monitoring (if applicable) Connection 1 . Route wires as shown and secure trim to door . 2 . Route wires through chassis as shown and secure chassis to door .
Page 12
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 5 - Wire Routing, continued PE8500 - OVERVIEW 1 . Install chassis to rail (Section 4) . Route wires through door as shown . 2 . Secure trim . 3 .
Page 13
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 5 - Wire Routing, continued PE8600 - OVERVIEW Electric Trim (If applicable) 54-Lever Monitoring (if applicable) Electric Trim (If applicable) 53- Connection Electric Trim (If applicable) A8298 08/24 Rev 2 1-800-727-5477 •...
Page 14
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 5 - Wire Routing, continued PE8600 2 . Install chassis (Section 4) and route wires through chassis as shown . 53- Connection Electric Trim (If applicable) 54-Lever Monitoring 1 . Route wires as shown and (if applicable) secure trim to door .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 6 - Installation of Insert Assembly to Device 1 . The Dip Switches are on the side of the assembly . Ensure eight S2 Dip Switches are set for application (see Section 2).
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 8 - Input and Output Connector Designations Harness Connector Circuit Board Input/ Harness Function Pin Number* Pin Number Output Wire Color J200-2 Input +24 VDC power J200-1 Input Black -Return J200-4 Input...
Page 23
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 8 - Input and Output Connector Designations, continued Harness Connector I/O Circuit Board Function Pin Number* Pin Number +24 VDC Power Supply Input (+) - This input may be tied to the normally closed contact of a building’s fire J200-2 alarm system .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 8 - Input and Output Connector Designations, continued NOTE: ElectroLynx QC12 Hinge is required if Electrified ET, Secure (SEC) Relay and/or if any other additional non default wiring is required . J200 J201 Top View...
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 10 - ElectroLynx Wiring Options Overview with QC12 Hinge 1 . Refer to installation instructions included with device and trim for complete door and frame preparations . Refer to template for wire access hole location .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 11 - System Wiring Examples ElectroLynx QC8 Hinge Delayed Egress System with Fire Alarm and Remote Reset with ElectroLynx QC8 Hinge During a fire alarm condition, the fire alarm contact opens which removes power from Delayed Egress (rail) and allows immediate egress . Rail can be rearmed by momentary closure at the Remote Reset (RR) switch .
Page 27
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 11 - System Wiring Examples ElectroLynx QC8 Hinge, continued Delayed Egress System with Fire Alarm, Switch Controls, DPS, Horn with ElectroLynx QC8 Hinge During a fire alarm condition, the fire alarm contact opens which removes power from DEED (rail) and allows immediate egress . For External Inhibit (EI) control, a valid code entry at the Inside keypad or valid card presentation at Inside card reader shunts the rail and allows egress for a time period programmable at the keypad .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 12 - System Wiring Examples ElectroLynx QC12 Hinge Delayed Egress System with Fail Safe Electrified Exit Trim (ET) and ElectroLynx QC12 Hinge. During a fire alarm condition, the fire alarm contact opens which removes power from DEED (rail) and Fail Safe ET, and allows immediate egress and ingress .
Page 29
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 12 - System Wiring Examples ElectroLynx QC12 Hinge, continued Delayed Egress System with Fail Secure Electrified Exit Trim (ET) and ElectroLynx QC12 Hinge. During a fire alarm condition, the fire alarm contact opens which removes power from DEED (rail), and allows immediate egress . For External Inhibit (EI) control, a valid code entry at the Inside keypad or valid card presentation at Inside card reader shunts the rail and allows egress for a time period programmable at the keypad .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 13 - Field Wiring Door Prep NOTE: y Do not scale drawing . y Dimensions are in inches (") and millimeters (mm) y LHR H .M . opening shown . Details are typical for all opening materials (both hands) . y This preparation is an addition to preparation shown on device template .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 14 - Operating Instructions, continued Re-arm After Closing for Indefinite Delay With 40 second momentary egress setting (S2-4 ON & S2-5 ON), S2-7 ON, and an external DPS is wired to the PCBA (S2-8 OFF), after activation of momentary egress by cylinder key switch or external remote reset signal, if the Door/DPS is open beyond 40 seconds, it will remain in momentary egress mode indefinitely and shall not enter alarm mode .
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 17 - Troubleshooting Problem Solution y Check all connections on circuit board and wire harness . y Check for power 24VDC at power inputs (-black) and (+red) and check polarity . Power is applied, but unit will not arm y Check wire transfer for any bad connections or broken wires .
Page 34
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 17 - Troubleshooting, continued A . Rail won’t arm (Green Insert LED won’t turn ON / Horn sounds immediately or after a delay) y When trying to arm, the rail goes into alarm immediately after momentary egress times out or after a short delay after the momentary egress times out .
Page 35
PE80 Series 59- Electroguard Delayed Egress Exit Device (DEED) Installation Instructions 17 - Troubleshooting, continued Refer to the following table and notes for an explanation of each LED’s function . Diagnostic LEDs Function ON - Latch bolt is retracted Yellow (Latch Bolt Status) OFF- Latch bolt is extended ON- Rail Push Bar is depressed .