User Guide | Testing and startup guide, type AK-PC 782B
16. AK-PC 782B oil reservoir
setup
© Danfoss | Climate Solutions | 2024.02
Open ST500, press
, then select "Oil management"
There are three options for the oil
Reservoir level switch:
None = a level switch is de ned and the input
has a physical jumper that remains in place.
The emptying sequence repeats inde nitely as
de ned by the settings shown on the next page.
Only high = the level switch indicates the
Reservoir is full and starts the emptying
sequence. Once the level drops below the
switch the sequence stops until the high
level switch is activated again.
Low & High = the emptying sequence starts
when the high level switch activates and
continues until the low level switch is activated
BC479936513201en-000101 | 17