Y-Branches
•
Specially designed for even distribution of refrigerant
•
Each kit includes one Y-Branch for gas and one Y-Branch for liquid
•
Simply use a tubing cutter for larger line sets
•
If installed horizontally, they must be level
•
If installed vertically, they must be plumb
•
FQ01A/A is used for downstream capacities of less than 68kBtu
•
FQ01B/A is used for downstream capacities of more than 68kBtu
Headers
•
Specially designed for even distribution of refrigerant and oil
•
Each kit includes one Header for gas and one Header for liquid
•
Simply use a tubing cutter for larger line sets
•
Must be installed horizontally and they must be level
•
Liquid header is built with downward facing offset for installation next to gas header
•
FQ14/H1 is used for 4 units or less
•
FQ18/H1 is used for 8 units or less