Y-Branches
Specially designed for even distribution of refrigerant
Each kit includes one Y-Branch for gas and one Y-Branch for liquid
Simply use a tubing cutter for larger line sets
If installed horizontally, they must be level
If installed vertically, they must be plumb
FQ01A/A is used for downstream capacities of less than 68kBtu
FQ01B/A is used for downstream capacities of more than 68kBtu
Headers
Specially designed for even distribution of refrigerant and oil
Each kit includes one Header for gas and one Header for liquid
Simply use a tubing cutter for larger line sets
Must be installed horizontally and they must be level
Liquid header is built with downward facing offset for installation next to gas header
FQ14/H1 is used for 4 units or less
FQ18/H1 is used for 8 units or less