AUTO ADDRESS
NOTE
•
Indoor Units will auto address randomly selecting the Main Indoor Unit
•
Main Indoor unit can be changed using the wired controller or wireless remote.
Setting the Main indoor unit
•
For wired controllers, set the Main indoor unit within the controllers settings menu
•
For wireless controllers:
1. Set Mode to Fan
2. Set Temp to 86°F or 30°C Press Down/Up 3 times quickly. UC will display on
indoor unit; this sets the unit to be the main unit.
CONTROLLER WIRING
•
Wired Controller wiring 18/2 stranded
•
Connects to H1/H2 terminals on corresponding indoor unit
•
Can control multiple indoor units when wired in a daisy chain configuration as shown below
•
Controller needs to be set to control multiple units. Refer to Controller Installation Instructions.
GRE E M ULTIPRO QUICK STA RT GUIDE
| 4
Need help?
Do you have a question about the MULTIPRO GMV-V WL/C-T Series and is the answer not in the manual?