ADDITIONAL REFRIGERANT CHARGE
For These Models
•
GMV-24WL/C-T(U)
•
GMV-28WL/C-T(U)
•
GMV-36WL/C-T(U)
•
GMV-48WL/C-T(U)
•
GMV-60WL/C-T(U)
•
Use only the liquid line for calculating additional refrigerant charge.
•
Only 1/4" and 3/8" are used.
•
Multiply each length by the ounces per foot in the chart!
•
10.5 ounces per indoor unit over two. If two or less, ignore this additional amount.
•
Add the total for 1/4", the total for 3/8" and the indoor unit amount.
•
Length of 1/4" times 0.24 Oz per Foot
•
Length of 3/8" times 0.58 Oz per Foot
•
Add those two numbers together.
•
Add 10.5 Ounces per IDU over two
Example:
Total Liquid Line Length of 1/4" :
Total Liquid Line Length of 3/8":
Total Number of Indoor Units (Subtract 2):
Total Additional Refrigerant Charge:
Quantity
Multiply
45'
18'
3
GR E E MU LT I PRO QU IC K STA RT G U ID E
Subtotal
.24
11oz
.58
10oz
10.5
10.5oz
31.5oz