These models must use system builder or selection software for additional charge amount.
•
GMV-V36WL/C-T(U)
•
GMV-V48WL/C-T(U)
•
GMV-V60WL/C-T(U)
START UP
•
Power on all indoor units
•
All should display AO on unit display and/or wired controller
•
Units without a display likely don't have power
•
Any units displaying CO, have a communication error
DEBUG PROCESS
•
Locate the four buttons on the outdoor board SW1 through SW4
•
Note the display. It will cycle status codes.
•
Likely says OF and AO
•
Note the display. It will cycle status codes.
•
Likely says OF and AO
•
Press and hold SW3 for 5 seconds
•
Displays 01 and ON
•
Do nothing until 04 is flashing
•
Number of indoor units
•
If it matches, press SW3
•
If it doesn't, check indoor units
Please note: The display may only show a steady "04" if four indoor units are communicating.
•
Unit continues until 10
•
Unit starts and checks if shutoff valves are open
•
When the display reads 12 and AP (flashing)
•
If additional refrigerant still needs to be added be prepared to add charge before moving forward.
•
Press SW3
GR EE M ULTIPRO QUICK STA RT GUID E
| 1 4