Advertisement
The Renogy Pure Sine Wave Power Inverter delivers superior performance for remote off-grid applications, capable of producing cleaner, smoother, and more reliable electricity for a user's electronic needs.
The Renogy Power Inverters output a pure sine wave similar to the waveform of the grid power. In a pure sine wave, the voltage rises and falls in a smooth fashion with very low harmonic distortion and cleaner utility-like power.
This gives users stable enough power to operate tools, fans, lights, computers, and other electronics without any interference. Pure sine wave inverters are in many cases more efficient, allowing users to use less energy and allow for more device capability. The main advantage to pure sine wave inverters is that they are used to operate sensitive electronic devices that require a high quality waveform with little harmonic distortion. Almost any electronic device could be powered using a pure sine wave inverter.
The Renogy Pure Sine Wave Battery Inverters will be shipped wi th inverter cables and a space for powering the inverter on or off.
Inverter Model | Gauge |
700W | 6 AWG 3ft |
1000W | 4 AWG 3ft |
2000W | 4 AWG*2 3ft |
3000W | Does not include |
Wired remote control
List dimensions | 2.875 x 2.3125 x 0.9375in, 73 x 58.7 x 23.8mm |
Thickness | 0625in, 1.5mm |
Wire length | Approx 19.8ft |
Key Parts
LEFT | Middle | Right |
Neutral (N) | Ground(G) | Live(L) |
Alarm —If there is a buzzing sound, the battery is low. The user should reduce the AC load, charge the battery, and check the DC cable for excessive losses.
You are advised to select a wire diameter corresponding to a copper nose that is less than or equal to 4mm.
KEY PARTS
Make sure inverter is in the off position before connecting anything.
Do not over-torque or over tighten the terminals. This could potentially damage the unit.
Refer to the technical specifications for max wire sizes on the controller and for the maximum amperage going through wires.
Never install the inverter in a sealed enclosure with flooded batteries. Gas can accumulate and there is a risk of explosion.
Ensure installation follows the following guidelines:
The inverter should never be mounted vertically on a vertical surface since it would present a hazard for the fan opening which is crucial for cooling the inverter.
For this Renogy inverter, the battery bank will be 12 volts direct current (12 VDC)
Example | |
A Microwave oven = 700 Watts 12V battery bank | 700 Watts to run microwave oven using the batteries as if it was a 12VDC microwave requires 58 Amps 700 Watts/12 Volts = 58 Amps |
Load Operation = 3 hours | Now that amps have been determined, the amp-hours need to be determined. The microwave will be used for approximately 3 hours a day. 58 Amps * 3 hours = 174 Ah |
At least a 174 Ah battery must be selected in order to use the 700-Watt microwave at 3 hours a day. However, determining a battery size is also dependent on the battery that is able to handle repeated discharge/charge cycles. |
This is just an example. Actual quantities vary by battery capacity and rates of discharge.
To power the microwave in the example, the user must use an inverter that is at least 1000 watts, if not more.
If available, the chassis ground lug should be connected to a ground point such as a vehicle chassis or boat grounding system. In fixed locations, connect the ground lug to earth ground. The connections to ground must be tight and against bare metal. Grounding is highly recommended for both when using the inverter in a mobile application, such as an RV, or in a building.
Recommended wire material: insulated copper strand wire
Recommended wire size:
The Renogy Pure Sine Wave Inverters are suitable for 12V battery bank systems ONLY. Not following the minimum DC requirement will cause irreversible damage to the unit.
Be careful of the positive and negative poles. Reversing the poles might cause permanent damage to the inverter. It will surely blow the internal fuse.
Damage to the Renogy inverters due to reverse polarity is NOT covered by warranty.
The input terminals of the inverters have large capacitors connected to them. Once a positive and negative wire are connected to the terminals, it will complete the circuit, and commence drawing a heavy current momentarily. As a result, there may be a sparking occurring even if the inverter is in the off position. To minimize sparking, it is recommended that the user have the appropriate size wire feeding into the inverters and/or install an external fuse leading into the inverter.
For your safety, it is recommended to use a battery fuse.
Model | RNG-INVT-70012V-P2 | RNG-INVT-100012V-P2 | RNG-INVT-200012V-P2 | RNG-INVT-300012V-P2 |
![]() | 700 W | 1000 W | 2000 W | 3000 W |
Battery Fuse | 100 A | 150 A | 250 A | 400 A |
Assuming proper battery connection, the inverter is now ready for use.
Avoid switching on the inverter with the load (electronic devices) already switched on. This may trigger an overload since some electronic devices have an initial high power surge to start.
When switching off the inverter, turn off the electronic devices first. Although the inverter is off, the capacitors will still have a charge, so the DC and AC terminals must be disconnected if altering the circuitry.
A ground-fault circuit interrupter, or GFCI, is a device that help protect people from electric shocks by de-energizing a circuit or portion of a circuit within an established period of time when a current to ground exceeds some predetermined value that is less than that required to operate the overcurrent device (circuit breaker or fuse) of the supply circuit. GFCIs are usually required in wet or damp locations.
While the inverter is equipped with a GFCI, it is recommended to install an external GFCI where you can manually test the circuit.
The following table lists GFCIs that meet the specifications and will function properly when they are connected to the AC Outlets of the inverter.
Tested GFCI M odels | |
Manufacturer | Model Number |
Leviton | GFNT2 |
Hubbell | GFP1305 |
Hubbell | GF15WLA |
Risk of electrical shock. Use only ground-fault circuit inter rupters [receptacle (s) or circuit breaker(s)] compatible with your P2 inverter.
Risk of electric shock. Use only class A ground-fault circuit-interrupter [receptacle (s) or circuit breaker(s)]. Other types may fail to operate properly when connected to this unit.
GFCIs shall be installed in a recreational vehicle's wiring system to protect all branch circuits.
Indicator | Potential Issue | Troubleshoot |
Alarm beeps | Input voltage is below 10.5V | Keep input voltage above 10.5V |
Input voltage is above 16.0V | Keep input voltage below 16.0V | |
Fault LED Lit, inverter shut down and alarm on | Input voltage is below 10V | Keep input voltage above 10V |
Input voltage is above 16.5V | Keep input voltage below 16.5V | |
Inverter overheats | Allow inverter to cool down | |
Check for adequate ventilation | ||
Reduce the load on inverter | ||
Operating equipment draws too much power | Use a higher wattage inverter or use a lower powered device | |
Inverter is short circuited | Disconnect the inverter and turn off the ON/OFF switch to reset | |
Yellow LED Lit - Inverter shut down | GFCI tripped | Disconnect appliances and turn off the ON/OFF switch to reset |
Fusing is a recommended in PV systems to provide a safety measure for connections going from panel to controller and controller to battery. Remember to always use the recommended wire gauge size based on the PV system and the controller.
NEC Maximum Current for different Copper Wire Sizes | |||||||||
#AWG | 16 | 14 | 12 | 10 | 8 | 6 | 4 | 2 | 0 |
Max. Current | 10A | 15A | 20A | 30A | 55A | 75A | 95A | 130A | 170A |
Model | RNG-INVT-70012V-P2 | RNG-INVT-100012V-P2 | RNG-INVT-200012V-P2 | RNG-INVT-300012V-P2 |
Continuous Power | 700 W | 1000 W | 2000 W | 3000 W |
Input Voltage | 12V DC | |||
Output Voltage | 115V AC | |||
Peak surge | 1400 W | 2000 W | 4000 W | 6000 W |
Efficiency | > 90% | |||
Frequency | 60Hz | |||
Total harmonic distortion (THD) | < 3% | |||
No load current draw | < 0.8A | < 1.0A | < 2.0A | < 2.5A |
Battery low alarm | 10.5V ± 0.5V DC | |||
Battery low shutdown | 10.0V ± 0.5V DC | |||
Over voltage shutdown | 16.5V ± 0.5V DC | |||
Cooling fan | Thermally controlled | |||
AC output sockets | 2 | 2 | 3 | 3 |
USB power port | 5V/2.1A | |||
Power output control | AC On/Off Switch | |||
Dimensions | 12.2×7.4×3.3 in | 12.9×6.8×3.3 in | 17.8×8.6×4 in | 18.9×9×4 in |
Net weight (approximate) | 5.6 lb | 6.0 lb | 11.7 lb | 12.5 lb |
Certification | ETL Listed to UL 458 and CSA 22.2 NO 107.1-01 | |||
Wired remote control | ||||
List dimensions | 2.875 x 2.3125 x 0.9375in, 73 x 58.7 x 23.8mm | |||
Thickness | 0625in, 1.5mm | |||
Wire length | Approx 19.8ft |
This manual contains important safety, installation, and operating instructions for the inverter. The following symbols are used throughout the manual:
Indicates a potentially dangerous condition. Use extreme caution when performing this task.
Indicates a critical procedure for safe and proper operation of the inverter.
Indicates a procedure or function that is important to the safe and proper operation of the inverter.
Renogy reserves the right to change the contents of this manual without notice.
US
2775 E Philadelphia St, Ontario, CA 91761, USA
909-287-7111
www.renogy.com
CN
苏州高新区科技城培源路1号5号楼-4
400-6636-695
https://www.renogy.cn
JP
https://www.renogy.jp
CA
https://ca.renogy.com
AU
https://au.renogy.com
UK
https://uk.renogy.com
DE
https://de.renogy.com
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Renogy 700w, 1000w, 2000w, 3000w - Power inverter Manual
Advertisement
Need help?
Do you have a question about the 700w and is the answer not in the manual?
Questions and answers