Module Specifications

This table lists a subset of the module specifications. For a complete list of specifications, see the FLEX 5000 Module Specifications Technical Data, publication 5094-TD001.
5094-OF4IHS and 5094-OF4IHSXT 4-channel Isolated Current/Voltage/HART Safety Output Module Specifications
Attribute
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max
Enclosure type rating
Output range, voltage
Output range, current
Backplane power (BP) voltage
Backplane power (BP) current, max
Sensor actuator power (SA) voltage range
Sensor actuator power (SA) current, max
Isolation voltage
TB keying
Wire size
Insulation stripping length
Terminal base
TB torque
North American temp code
UKEX/ATEX temp code
IECEx temp code
Corrosion resistance classification
Safety integrity level

Additional Resources

For more information on the products that are described in this publication, use these resources. You can view or download publications at rok.auto/literature.
Resource
FLEX 5000 Modules Specifications Technical Data, publication
FLEX 5000 Analog Isolated Current/Voltage/HART Standard and Safety I/O Modules
User Manual, publication
5094-UM007
FLEX 5000 Terminal Base Assembly Modules Installation Instructions,
publication
5094-IN010
FLEX 5000 Shield Bar Product Information, publication
Industrial Automation Wiring and Grounding Guidelines, publication
Product Certifications website,
rok.auto/certifications
FLEX 5000 Analog 4-channel Isolated Current/Voltage/HART Safety Output Modules Installation Instructions
5094-OF4IHS and 5094-OF4IHSXT
-40 °C ≤ Ta ≤ +70 °C (-40 °F ≤ Ta ≤ +158 °F)
70 °C (158 °F)
None (open-style)
±10V DC
0...10V DC
0...5V DC
0...20 mA
4...20 mA HART
15V DC
100 mA
18...32V DC
260 mA
250V (continuous), Basic Insulation Type, System to Field
SA to channel, SA to FE
Channel to channel, Channel to FE
2
0.34...2.5 mm
(22...14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.)
insulation max
Screw-type TB:
2
• 0.34...2.5 mm
(22...14 AWG) =12 mm ± 1 mm (0.47 ± 0.04 in.)
Spring-type TB:
2
• 0.34...1.5 mm
(22...16 AWG) = 10 mm ± 1 mm (0.39 ± 0.04 in.)
2
• 2.5 mm
(14 AWG) = 15 mm ± 1 mm (0.59 ± 0.04 in.)
5094-MB and 5094-RTB3I (assemble to make 5094-TB3I)
5094-MB and 5094-RTB3IS (assemble to make 5094-TB3IS)
5094-MBXT and 5094-RTB3IXT (assemble to make 5094-TB3IXT)
5094-MBXT and 5094-RTB3ISXT (assemble to make 5094-TB3ISXT)
Screw-type TB: 0.4 N•m (3.5 lb•in)
Spring-type TB: Not applicable
T4
T4
T4
5094-OF4IHS – ISA S71.04 G2
5094-OF4IHSXT – ISA S71.04 G3
SIL 3, PLe, Cat. 4
Description
5094-TD001
Provides FLEX 5000 EtherNet/IP adapters and FLEX 5000 I/O module specifications.
Provides guidelines to install, configure, and operate the FLEX 5000 analog HART modules.
Provides guidelines to install FLEX 5000 terminal base assemblies and accessories.
5094-PC002
Provides specifications for the shield bar and jumper accessories.
1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 5094-IN017B-EN-P - August 2022