1. Overview
Thank you for purchasing Inovance MD880 series active line module.
The MD880-40D series low-voltage and low-power active line module features high power density, compact
structure, and high reliability. It has a voltage class of 400 V, with rated power ranging from 64 kW to 271 kW. The
power module, filter, controller, and detection unit of the line module are delivered separately to be integrated by
customers.
This user guide describes product information, installation instructions, and electrical connection. If you have any
question concerning the product function or performance, contact Inovance for technical support.
■ Document Acquisition
The user guide is not delivered together with the product. To purchase the user guide, contact the sales personnel.
2. Product Information
■ Model
Figure 1 Model description
■ Specifications and model selection
Table 1 Specifications and selection of MD880-40D series active line module
Application without overload
Active line module
Power module model
model
I
I
I
S
P
N
N
max
N
N
A
A
A
kVA
kW
ac
dc
dc
MD880-40D-0094-4
MD880-40M-0094-4
94
107
140
65
64
MD880-40D-0149-4
MD880-40M-0149-4
149
170
221
103
102
MD880-40D-0183-4
MD880-40M-0183-4
183
209
272
127
126
MD880-40D-0299-4
MD880-40M-0299-4
299
342
444
207
205
MD880-40D-0395-4
MD880-40M-0395-4
395
452
587
274
271
I
:
Rated input (AC)/output (DC) current
N
I
: Maintaining the max. output current for at least 10s (every 300s) upon start
max
S
: Apparent power
N
P
: Rated output power
N
I
: Continuous output current in applications with light overload
Ld
P
: Output power in applications with light overload
Ld
I
: Continuous output current in applications with heavy overload
Hd
P
: Output power in applications with heavy overload
Hd
P
: Total loss of active line module
loss
Model
AC fuse
0094-4
DC fuse
AC fuse
0149-4
DC fuse
AC fuse
0183-4
DC fuse
AC fuse
0299-4
DC fuse
AC fuse
0395-4
DC fuse
■ Technical Data
Item
AC input voltage
*19012241A00*
Input frequency
Degree of voltage
19012241A00
Basic
unbalance
performance
Output voltage
Overload capacity
Operating efficiency
1
Power factor
Basic
performance
Total harmonics THD
Ambient temperature
Relative humidity
Operating
environment
Altitude
Storage temperature
Storage
Storage humidity
Vibration resistance
Mechanical
data
IP rating
Safety performance
Cooling method
Protective
Protective functions
functions
3. Electrical Wiring
The following figure shows the electrical wiring of MD880-40D series active line module integrated
kit.
Application
Application
Thermal
FROM-
Air
HSVM1
with light
with heavy
design
volume
overload
overload
power
I
P
I
P
P
Ld
Ld
Hd
Hd
loss
m
/h
3
A
kW
A
kW
kW
dc
dc
103
62
81
48
1.60
178
164
98
128
77
2.55
297
201
120
157
94
3.15
331
328
197
256
154
5.12
420
433
260
339
203
6.77
700
Table 2 Fuse selection
Type
Model (SINOFUSE)
Specifications
Quantity
RS306-1-W1Z-125A690V
125 A, 690 V
3
RS306-1-W1Z-160A690V
160 A, 690 V
2
RS306-1-W1Z-200A690V
200 A, 690 V
3
RS306-1-W1Z-250A690V
250 A, 690 V
2
RS306-1-W1Z-250A690V
250 A, 690 V
3
RS306-1-W1Z-315A690V
315 A, 690 V
2
RS306-1-W1Z-400A690V
400 A, 690 V
3
RS306-1-W1Z-450A690V
450 A, 690 V
2
RS306-1-W1Z-550A690V
550 A, 690 V
3
RS306-1-W1Z-630A690V
630 A, 690 V
2
Name
Specifications
400 V system: 380 VAC to 415 VAC, ±10% (-15%, < 1 min)
47 Hz to 63 Hz
±3% of rated voltage at most
400 V system: 540 VDC to 720 VDC
Light overload: Operating continuously for 1 min every 5 min upon 110% ILd
Heavy overload: Operating continuously for 1 min every 5 min upon 150% IHd
More than 97%
> 0.99 (at rated power with full load)
THDI < 5% (rated power)
THDU < 5% (Rsc > 20)
-10℃ to +40℃ , derating required for temperatures between 40℃ to 50℃
5% to 95%, without condensation
≤ 1000 m: derating not required
> 1000 m: derating required
Max.: 4000 m
-40° C to +70° C
5% to 95%, without condensation
Compliant with vibration class 3M4 in GB/T4798.3
Steady-state sinusoidal vibration: 2–9 Hz, 3 mm
9–200 Hz, 10 m/s
2
Impact: 100 m/s
, 11 ms
2
Module: IP00
Cabinet: IP21
Compliant with EN 61800-5-1
Forced air cooling (AF), compliant with EN 60146 for the module;
Natural cooling for the reactor
Providing protection against short circuit, overcurrent, overload, overvoltage,
undervoltage, phase loss, three-phase unbalance, and overtemperature
AC input
Buffer
KM2
contactor
control
40D buffer units
Fault
output
Buffer contactor
Main contactor
Main
KM1
contactor
control
Reactor feedback signal
Buffer contactor
control
Reset signal
Stop control
Main contactor feedback signal
Start control
E-stop
Figure 3 Electrical wiring
2
Table 3 List of deliverables
No.
Name
HOFM-30 optical fiber
Connected to HCU through the SLOT to provide multiple optical fiber interfaces
1
extension module
for HCU.
Connected to line module U1 through the electrical interface to be used as the
2
HCU controller module
controller for MD880-40D.
Connected to the HCU through the network cable to perform parameter setting,
SOP-20 smart
3
software programming, start/stop control, and communication relay on the
operating panel
active line module (including the operating panel base).
4
Main contactor
Used to control switch-on/off of the three-phase incoming cables.
Reactor on the power
5
Small reactor of LCL filter
grid side
Reactor on the line
6
Large reactor of LCL filter
module side
7
Active line module
Power module of the active line module
8
Buffer components
Providing DC bus buffer circuit for the active line module
9
Capacitor module
Three-phase capacitor module
Synchronous voltage module to collect incoming voltage for the active line
10
HSVM-10
module
◆ T
able 2 lists recommended fuse models.
◆ Table 3 lists the deliverables. Components not listed are to be configured by customers.
◆ The terminal block is not available for the capacitor module of the bolt fixing terminal. Perform
NOTE
wiring based on the label of the copper busbar.
4. Technical Data for Installation
■ Dimensions of the line module
1) H3
Figure 4 H3 dimensions (unit:mm)
Structure
Line module model
H3
MD880-40M-0094-4
2) H4
Figure 5 H4 dimensions (unit:mm)
Structure
Line module model
MD880-40M-0149-4
H4
MD880-40M-0183-4
DC bus (+)
DC bus (-)
3
Description
Wiring hole diameter
M6
Wiring hole diameter
M10

Advertisement

loading
Need help?

Need help?

Do you have a question about the MD880-40D Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Inovance MD880-40D Series

  • Page 1 Relative humidity 5% to 95%, without condensation Operating The MD880-40D series low-voltage and low-power active line module features high power density, compact ≤ 1000 m: derating not required environment structure, and high reliability. It has a voltage class of 400 V, with rated power ranging from 64 kW to 271 kW. The Altitude >...
  • Page 2 Damage caused by operations not following the instructions in the user guide e. Damage caused by peripheral faults (for example, external device faults) 3. The maintenance fee is charged according to the latest Maintenance Price List of Inovance. 4. For service issues, contact Inovance agent or Inovance directly.

This manual is also suitable for:

Md880-40d-0094-4Md880-40d-0149-4Md880-40d-0183-4Md880-40d-0299-4Md880-40d-0395-4