Page 2
Fike products. Do not use any Fike products for any application for which it is not intended. Fike shall not be in any way liable for any damages or losses incurred by you or third parties arising from the use of any Fike product for which the product is not intended by Fike.
1. IDENTIFICATION 1.1. General The Fike Explosion Pressure Detectors are designed to continuously measure the pressures inside the protected hazards. The extremely fast response time of the Ceramic pressure detector allows the Explosion Protection Controller (EPC) to take more than one million samples every second. Using the same instantaneous speed, this information is then processed to determine if the pressure change is that of a developing explosion.
1.2.1.2. 29945023-C-S (not FDA approved) The marking of the detector is laser printed on the side of the detector housing. The 29945023-C-S label looks as follows: Doc. P/N 8.8517.00.6 PAGE / 5 Rev. December, 2019...
1.2.2. Cerex (G/D) – Explosion Protection Ceramic Pressure Detector ‘Gas’ 1.2.2.1. P/N 2994502201-C-S (FDA approved) and 29945022-C-S (not FDA approved) The marking of the detector is laser printed on the side of the detector housing. The 2994502201-C-S label looks as follows:...
T 85 °C 1.4. Hazardous Area Information 1.4.1. Cerex (D) – Explosion Protection Ceramic Pressure Detector ‘Dust’ This detector is suitable for installation in: Dust Ex areas: installation into zone 21 (and 22) and wetted parts in contact with zone 20.
1.5. Scope of Supply The detector is supplied in a folded carton box, and includes the following parts: Detector assembly including cable to be routed to a Fike junction box. Plastic protection cap, to be removed before installation.
1.6. Dimensions 1.7. Technical Specifications Dust (D – black cable) Hybrid (G/D – blue cable) Type 2994502301-C-S 2994502201-C-S Sensing principle Capacitive Ceramic Detection range ± 300 mbarg Overpressure 4 bar Deflagration overpressure 12 bar Vacuum resistance Full vacuum Process connection G 1”...
2. WIRING INSTRUCTIONS The Ceramic Pressure Detector shall only be connected to the Fike EPC (Explosion Protection Controller) in accordance with following instructions. When connecting devices with explosion protection certificates, please comply with national standards, warnings and wiring diagrams listed in the additional explosion protection documentation accompanying these Operating Instructions.
2.2. Intrinsically Safe Connection to EPC 2.2.1. Single Wire Diagram (Schematic) Notes: To ensure a solid functionality the cable length between detector and barrier may not exceed 50m. Intrinsic safe transducer barrier + black cable + EPC placed outside Ex-zone. ...
For more information, please contact your nearest Fike representative and/or EPC Manual E06-051-x. 4. MAINTENANCE Caution: If assistance is needed, contact Fike for instructions, before performing any maintenance or service work on the Fike Explosion Protection Equipment and/or System. PAGE / 12 Doc.
These inspections are to be performed by Fike Service Engineers or personnel trained and certified by Fike to do so. To perform an inspection, it is important to first obtain all pertinent data that relates to the system being inspected.
6. DE-COMMISSIONING PROCEDURE / CHECK-LIST De-commissioning should only be performed by a Fike qualified Service Engineer, who has been assigned to prepare and complete the de-commissioning of the Explosion Protection System. Each step in a listed procedure must be adhered to and completion/acceptance of a listed form is mandatory. In the case of non-compliance, the observed discrepancy must be corrected before completion of the system de- commissioning.
8. REPAIR AND RETURN AUTHORISATION Any component that is to be returned to Fike must be approved for return prior to shipment. In order for the returned component to receive the correct attention (credit, repair, replacement) either under warranty or at the owner's expense, a Shipping Label for prearranged return authorization must be provided by Fike.