PRODUCT REGISTRATION Thank you for purchasing the CyberPower Extended Battery Module BP48VP2U03 for your Uninterruptible Power Supply. The Extended Battery Module is designed for various CyberPower UPS systems and can be used in either rack or tower installations. The heavy gauge power cord has a plug-and-play DC connector for easy installation.
UNPACKING Inspect the unit upon receipt. The box should contain the following: (a) Extended Battery Module (b) Faceplate (c) Rail Kit CP2RAIL02, includes: 14 x M5 Pan Head Screws 2 x M5 Round Head Screws 8 x Plastic Washers (d) Management Cable 1 x BM Cable (e) Power Cords 1 x IEC C13-C14, 1-ft., (auxiliary)
Page 4
INSTALLATION Rack Installation for 4-Post Rack Use the provided M5 flat head screws to attach the brackets and provided M5 pan head screws for hanging brackets. 2. Screw the hanging rails to the rack with provided M5 pan head screws and plastic washers. 3.
BASIC OPERATION Normal Use Plug the Extended Battery Module into a grounded receptacle/wall outlet. 2. Connect the Extended Battery Module to your UPS by plugging the extended battery module connector plug into the connector socket on the rear panel of the UPS. Ensure the color coded connector plug lines up correctly with the colors in the UPS socket, such as red to red, black to black and green to green.
Page 6
BASIC OPERATION Be aware of the following statements: A. Your Extended Battery Module may be used immediately upon receipt. However, charging the battery for at least twelve (12) hours before connecting to UPS is recommended to ensure the battery reaches its maximum charge. Charge loss may occur during shipping and storage.
BATTERY REPLACEMENT Read and follow the important safety instructions before servicing the batteries. Replacement of batteries located in an operator access area. Visit CyberPower official website www.cyberpower. com or contact your dealer for more information on battery replacement. CAUTION! RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
TECHNICAL SPECIFICATIONS MODEL BP48VP2U03 INPUT Input Voltage Range 100V - 240V Input Frequency 50-60Hz Plug Type IEC 320 C14 OUTPUT Output Voltage 48 Vdc Rated Output Current 70 A Overload Protection Fuse BATTERY Battery Type Sealed Maintenance Free Lead Acid Battery...
LCD module, PowerPanel Battery Modules. Business Edition software or RMCARD UPS does not perform interface (if installed). expected runtime. Contact CyberPower Systems at: Batteries are degraded. cyberpowersystems.com for replacement batteries. Allow the Extended Battery Module to Batteries are not fully charged.
CyberPower is the warrantor under this Limited Warranty. For further information please feel free to contact CyberPower at: Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379; call us at (877) 297-6937; or submit a web ticket online at cyberpowersystems.com/support.
Need help?
Do you have a question about the BP48VP2U03 and is the answer not in the manual?
Questions and answers