Page 1
USER MANUAL MultiFlex RCB/RCB-P Rooftop Controller Installation and Operation User Manual...
Page 2
Copeland 1065 Big Shanty Road NW, Suite 100 Kennesaw, GA 30144 USA 770-425-2724 • 1-800-829-2724 www.copeland.com Email: ColdChain.TechnicalServices@copeland.com...
TABLE OF CONTENTS 1 OVERVIEW OF THE MULTIFLEX RCB ......................1 1.1 Differences Between the MultiFlex RCB and the MultiFlex RTU....................1 1.1.1 MultiFlex RCB-P (Pulse) Board....................................1 1.2 The RCB’s I/O Points ....................................1 1.3 Independent System Control ................................1 2 MOUNTING AND POWERING ......................... 2 2.1 Snap-Track Installation..................................2...
Page 4
6.7.3 Economization Stand-Alone Operation................................22 6.7.4 Summer/Winter Season and Occupied/Unoccupied Scheduling......................22 6.7.5 Other Stand-Alone Operation....................................22 6.8 Sensor Failures ....................................23 7 THE MULTIFLEX RCB E2 INTERFACE....................... 24 7.1 Adding/Deleting an RCB ..................................24 7.1.1 Adding an RCB..........................................24 7.1.2 Deleting an RCB ......................................... 24 7.2 Associating an RCB with a Zone Application ..........................25...
Page 5
TABLE OF CONTENTS 8 THE MULTIFLEX RCB HAND-HELD INTERFACE ................... 30 8.1 RCB Hand-Held Terminal Status Screens........................... 30 8.2 RCB Opening Screens ..................................30 8.3 RCB Main Menu....................................30 8.4 Status Menu ......................................31 8.5 Control Menu.......................................34 8.5.1 Control Menu - Setpoints......................................35 8.6 Inputs........................................40...
Copeland space temperature sensors, supply and return air E2 BX building control system. The MultiFlex RCB is capable temperature sensors, and fan and compressor proofs. Its of controlling heat and cool stages, fans, humidification and eight relay outputs, rated 2.0 amps max, are used for...
Figure 2-3 - Exploded View — MultiFlex RCB The MultiFlex RCB has an output sub-board that plugs to the top of the base board. Typically, these boards are shipped with the output board pre-installed on the board using stand- offs, so no additional hardware setup should be necessary.
Refer to Section 2.3.1 Choosing Transformer Sizes for center tap usage. Copeland supplies a wide variety of 24VAC transformers with varying sizes and either with or without center taps. Table 2-1 shows the transformer sizes and whether they are center-tapped or non-center-tapped.
2.3.2 MultiFlex RCB Power Wiring 2.3.3 Wire Types and Maximum Distances The MultiFlex RCB boards can be connected to any of the For powering I/O boards, use only the listed wire types from center-tapped transformers mentioned in Table 2-1, Table 2-3. Three-conductor non-shielded cables are the...
Battery-backed memory is enabled by the ENABLE BATTERY jumper (JP5) located at the bottom right corner of the input board layer (Figure 2-7). This jumper is shipped from Copeland in the DISABLE position. The jumper should be set to the ENABLE position (UP) before installation.
The I/O Network Although the MultiFlex RCB can operate as a stand-alone controller, it relies on an E2 unit for advanced features such as remote dial-in/dial-out, logging, and alarm control. All MultiFlex boards and controllers use an RS485 network connection to communicate with E2 site controllers.
3.1.2.1 Numbering the MultiFlex RCB 3.1.4 Setting the Terminating Resistance Jumpers The MultiFlex RCB is a unique board type on the RS485 Network by the Copeland controllers. Each RCB that will be All MultiFlex boards and other RS485 devices have a set of...
Figure 4-1 - MultiFlex RCB Input Locations The MultiFlex RCB has 16 combination analog/digital outputs for connection to all analog and digital sensors, transducers, switches, and other input types typically used in a rooftop HVAC unit application. The input type and function for each point must be programmed in the RCB software by the installer.
Smoke In DIG-ON/OFF Smoke alarm input for system shutdown during fire. 4.1.1 Wiring Sensors to the MultiFlex RCB 4.1.1.2 Sensor Wiring Types Specific wiring types are required for each type of sensor Wiring an input to the input points on a MultiFlex board used with E2 or RMCC.
AC1 and AC2. This can only be done with sensors that keep the 24VAC signal isolated from its DC output signal (such as Copeland Dewpoint Probe, P/N 203-1902). If the output signal is not isolated from the 24VAC input, you must use a separate transformer.
Figure 4-5 - MultiFlex RCB Output Locations The MultiFlex RCB has eight relay outputs for connection to all outputs that are typically present for a rooftop unit. Figure 4-5 shows the location of the RCB outputs, and Table 4-2 describes the devices that can be assigned to these points. The relay output type and function for each point must be programmed in the RCB software by the installer.
4.2.1 Wiring Outputs to Points The MultiFlex RCB has Form C relay contacts. Figure 4-6 shows how to wire the three-terminal Form C contact. One wire of the two-wire connection should always be connected to the middle terminal. The second wire must either be connected to the N.C.
Figure 4-7 - MultiFlex RCB Analog Output Locations The MultiFlex RCB analog outputs are 0-+10VDC points used for controlling variable-position economizers, mod heat and cool stages, and variable-speed fans. The maximum output current for each point is 10 milliamps. Figure 4-7 shows the location of the analog outputs.
Introduction to Zone Control Though RCBs may be used as stand-alone rooftop unit controllers, when used with Copeland E2 BX building controllers, they may be networked together in groups called zones. Zones are groups of rooftop boards and applications (ARTC, RCBs and/or AHU (air handling units) that share the same heating, cooling, and dehumidification setpoints, as well as other control parameters.
E2 front panel. • The ability to remotely access RCBs from UltraSite32 or If you have properly set up all MultiFlex RCB boards on this Site Manager, and to back up, restore, and offline program RCB configuration along with E2 site E2’s I/O Network, you can view the status of the I/O Network...
Note you may choose the Zone application the controller that the MultiFlex RCB application must be configured to may be associated with. communicate with an RCB-P by setting the RCB Type Move the cursor to the AHU Zone field you wish to parameter to Pulse under the Setup screen.
7.4.1 RCB-P Pulse Control Setpoints Setup To set up the MultiFlex RCB application to communicate with an RCB-P, set the RCB Type parameter to Pulse. When setting up an RCB you should go through each screen to check the function of each parameter and determine if you will need to change the value to accommodate the way you want the RCB to operate.
The MultiFlex RCB Hand-Held Interface The MultiFlex RCB Hand-Held Terminal interface allows you to view status of the rooftop HVAC systems and configure setpoints directly on the board. If you are using RCBs separate from a central E2 system, the Hand-Held Terminal will be the only programming interface you may use.
1-16) etc.) defaults to a type value of TEMP, indicating the sensor is a Copeland temperature sensor. However, if using LM235-based temp sensors, this field may be changed to LM-235 TMP. KW INPUT - The KW Input input type may be set to either POWER- KW (analog 0-5VDC watt transducer) or PULSE-CNT (pulse accumulation type KWH input).
The values chosen by default for the PID constants are the recommended settings for use in HVAC control. It is not recommended you alter these values without assistance from Copeland. I: The I field is the PID’s integral gain. This is a multiplier that affects the...
10 8IO Combination Input/Output Board input type dip switches 10 Heat Differential 19 power connections for sensors 10 Heating 17 HHT interface. See MultiFlex RCB, HHT interface. Humidification control 19, 20 ARTC dehumidification during stand-alone 22 I/O Network...
Page 52
Software overview 15 stand-alone operation 22 dehumidification control 19 status LEDs 14 fan control 18 temperature control 15 Humidification control 19 MultiFlex RCB-P (Pulse) Board 1 outside air control 20 reversing valve wiring 22 sensor failures 23 Network humidity 23 RS485 I/O...
Page 54
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Copeland reserves the right to modify the designs or specifications of such products at any time without notice.
Need help?
Do you have a question about the MultiFlex RCB and is the answer not in the manual?
Questions and answers