Summary of Contents for Rockwell Automation Allen-Bradley PowerFlex 4
Page 1
PowerFlex 4 Adjustable Frequency AC Drive Bulletin Number 22A Firmware Revision 7.xxx User Manual Original Instructions...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Page 3
PowerFlex 4 Adjustable Frequency AC Drive User Manual, publication 22A-UM001J-EN-E. Description of New or Updated Information See Pages Minimum Enclosure Volume column and new footnotes added Drive, Fuse & Circuit Breaker Ratings topic updated Electronic Motor Overload Protection description updated Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 4
Attention statement added to Multiple Digital Input Connections wiring example Parameter P043 [Motor OL Ret] added Attention statement added to parameter A082 [DB Resistor Sel] External Comm Options, Compact I/O added to Table 20 Modbus function code 16 added Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Similar PowerFlex 4 drive sizes are grouped into frame sizes to simplify spare parts ordering, dimensioning, and so on. A cross reference of drive catalog numbers and their respective frame sizes is provided in Appendix Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
1 minute. If this condition is unacceptable, the bus regulator must be disabled (see parameter A117). In addition, installing a properly sized dynamic brake resistor will provide equal or better performance in most cases. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
1.5 (2.0) 1.5 (2.0) 2.2 (3.0) 12.0 2.2 (3.0) 3.7 (5.0) 17.5 3.7 (5.0) Position 12 of the Catalog Number now indicates drive type. All PowerFlex 4 drives are equipped with RS-485 communication. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local, or otherwise for the proper installation of this drive or associated equipment.
-10 °C (14 °F) IP30/NEMA 1/UL Type 1 Use Mounting Option B 50 °C (122 °F) IP20/Open Type Use Mounting Option B Rating requires installation of the PowerFlex 4 IP30/NEMA 1/UL Type 1 option kit. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
2. Pull the jumper completely out of the drive chassis. 3. Tighten the screw to keep it in place. Figure 1 – Jumper Location (A Frame Shown) Important: Tighten screw after jumper removal. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
(PE) must be connected to system ground. Ground impedance must conform to the requirements of national and local industrial safety regulations and/or electrical codes. The integrity of all ground connections should be periodically checked. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
AC supply systems and be permanently installed and solidly grounded (bonded) to the building power distribution ground. Ensure that the incoming supply neutral is solidly connected (bonded) to the same building power distribution ground. Grounding must not rely on Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
• Bulletin 140M/140MT can be used in single and group motor applications. • Bulletin 140M/140MT can be used up stream from the drive without the need for fuses. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
For the same reason, if a drive sharing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will help minimize the possible shock hazard from “cross coupled” power leads. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 19
Division I and II 75 °C or 90 °C (167 °F or 194 °F) three bare copper grounds in contact with shield RHH/RHW-2 • PVC copper grounds on 6 mm (10 AWG) and smaller Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 20
If it is necessary to disconnect power to the motor with the drive outputting power, an auxiliary contact should be used to simultaneously disable drive control run commands. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Torque 3.3 mm (12 AWG) 0.8 mm (18 AWG) 1.7…2.2 N•m (16…19 lb•in) 5.3 mm (10 AWG) 1.3 mm (16 AWG) Maximum/Minimum sizes that the terminal block accepts. These sizes are not recommendations. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
(PE) terminal and are designed to greatly reduce common mode interference. ATTENTION: Driving the 4…20 mA analog input from a voltage source could cause component damage. Verify proper configuration prior to applying input signals. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
To improve noise immunity, the I/O terminal block Common must be connected to ground terminal/protective earth. If using the RS-485 (DSI) port, I/O Terminal 16 should also be connected to ground terminal/protective earth. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 24
0…10V In (3) Not Active P038 (input impedance = 100 kΩ) or potentiometer wiper. For 0…10V In or 4…20 mA In. Electronically isolated with Analog Common – – analog inputs from digital I/O. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Wire R2/R3 Relay Output (SRC) to I/O Terminals 5 & 11. A051 [Digital In1 Sel] = 3 “Aux Fault” A055 [Relay Out Sel] = 10 “Above Anlg V” A056 [Relay Out Level] = % Voltage Trip PTC (hot) × 100 Trip PTC (hot) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 26
Run Reverse inputs are Each digital input draws 6 mA. closed at the same time, an undetermined state could occur. 2-wire SNK Control - Internal supply (SNK) Run FWD/Run REV Stop-Run Forward Stop-Run Reverse Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 27
P037 [Stop Direction Direction Mode]. I/O Terminal 03 determines direction. +24V Common Each digital input draws 6 mA. 3-wire SNK Control - Internal supply (SNK) Reversing Stop Start Direction Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 28
I/O Terminal 14 common together for all drives. I/O Terminal 14 common and I/O Terminal 13 (potentiometer wiper) should be daisy chained to each drive. All drives must be powered up for the analog signal to be read correctly. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
A071…A073 [Preset Freq 1…3]. A051 / A052 Preset Inputs Active Start and Direction commands come from P036 [Start Source]. Run as specified by P038 [Speed Reference]. Start and Direction commands come from P036 [Start Source]. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 30
Speed is controlled determined by the active Preset Frequency. by [Preset Freq x] See A070…A073 [Preset Freq 0…3] A051 or A052 = 4 page P039 [Accel Time 1]/P040 [Decel Time 1] are used. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
• Use of line filters in ungrounded systems is not recommended. • Conformity of the drive with CE EMC requirements does not guarantee an entire machine installation complies with CE EMC requirements. Many factors can influence total machine/installation compliance. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
First Environment Unrestricted Distribution installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and the EMI filter. Integral EMI filters are available on 240V, 1-phase drives. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 33
Installations on a public low voltage power network may require additional external harmonic mitigation. • Other drive ratings meet the current harmonic requirements of EN61000-3-2 without additional external mitigation. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
(I/O Terminals 01 and 11) to allow starting from the keypad. If the control scheme is changed to Sink (SNK), the jumper must be removed from I/O Terminals 01 and 11 and installed between I/O Terminals 01 and 04. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Basic Program Group Consists of most commonly used programmable functions. Advanced Program Group Consists of remaining programmable functions. Fault Designator Consists of list of codes for specific fault conditions. Displayed only when fault is present. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
This key is always active. Controlled by parameter P037 [Stop Mode]. Viewing and Editing Parameters The last user-selected Display Group parameter is saved when power is removed and is displayed by default when power is reapplied. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 38
If pressing Esc does not change the display, then d001 [Output Frequency] is displayed. Press Enter or Sel to enter the group menu. The Basic Program Group (page 46) contains the most commonly changed parameters. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
1, the feature is on or the condition is true. Some parameters are marked as follows. = Stop drive before changing this parameter. = 32-bit parameter. Parameters marked 32-bit will have two parameter numbers when using RS-485 communications and programming software. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Anlg In 0-10V Hi A111 Anlg In 4-20mA Lo A112 Anlg In 4-20mA Hi A113 Slip Hertz @ FLA A114 Process Time Lo A115 Process Time Hi A116 Bus Reg Mode A117 Comm Write Mode A118 Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Output voltage present at terminals T1, T2, and T3 (U, V, and W). Values Default Read Only Min/Max: 0/Drive Rated Volts Display: 1 VAC d005 [DC Bus Voltage] Present DC bus voltage level. Values Default Read Only Min/Max: Based on Drive Rating Display: 1 VDC Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 42
The output frequency scaled by A099 [Process Factor] or by A115 [Process Time Lo] and A116 [Process Time Hi]. Output Process Process Freq Factor Display Values Default Read Only Min/Max: 0.00/9999 Display: 0.01/1 Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 43
The stop input must be present in order to start the drive. When this bit is a 1 the drive can be started. When this bit is a 0 the drive will stop. Values Default Read Only Min/Max: Display: Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 44
[Control SW Ver] Main Control Board software version. Values Default Read Only Min/Max: 1.00/99.99 Display: 0.01 d017 [Drive Type] Used by Rockwell Automation field service personnel. Values Default Read Only Min/Max: 1001/9999 Display: Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 45
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA). Values Default Read Only Min/Max: 0.0/100.0% Display: 0.1% d024 [Drive Temp] Present operating temperature of the drive power section. Values Default Read Only Min/Max: 0/120 °C Display: 1 °C Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Related Parameters: d001, d002, d013, P034, A078, A111, A113, A115 Stop drive before changing this parameter. Sets the highest frequency the drive will output. Values Default 60 Hz Min/Max: 0/240 Hz Display: 1 Hz Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 47
On firmware revisions 1.03 and later, once a stop input is received, the start command must transition from high to low to high for the drive to start. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 48
DC Injection Braking Stop with Auto Shutoff • Standard DC Injection Braking for value set in A080 Brake Time] • Drive shuts off if current limit is exceeded. Stop input also clears active fault. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 49
Maximum Freq Accel Rate Accel Time Values Default 10.0 Secs Min/Max: 0.0/600.0 Secs Display: 0.1 Secs P035 [Maximum Freq] Speed P039 or A067 P040 or A068 Time [Accel Time x] [Decel Time x] Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 50
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor overload counter is saved at power-down and restored at power-up. A change to this parameter setting resets the counter. Options 0 “Disabled” (Default) 1 “Enabled” Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
A valid start overrides this command. 12 “Jog Reverse” Drive accelerates to A078 [Jog Frequency] according to A079 [Jog Accel/Decel] and ramps to stop when input becomes inactive. A valid start overrides this command. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 52
Enables the output to be controlled over network communications by writing to A056 [Relay Out Level]. (0 = Off, 1 = On.) 21 “NonRec Fault”” Value set in A092 [Auto Rstrt Tries] is exceeded. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 53
Maximum Freq Accel Rate Accel Time Values Default 20.0 Secs Min/Max: 0.0/600.0 Secs Display: 0.1 Secs P035 [Maximum Freq] Speed P039 or A067 P040 or A068 Time [Accel Time x] [Decel Time x] Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 54
EEPROM memory. If the ESC key is used before the Enter key, the frequency will return to the original value following the normal accel/decel curve. Values Default 60.0 Hz Min/Max: 0.0/240.0 Hz Display: 0.1 Hz Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 55
Display: 0.1 Hz A079 [Jog Accel/Decel] Related Parameters: A051, A052, A078 Sets the acceleration and deceleration time when a jog command is issued. Values Default 10.0 Secs Min/Max: 0.1/600.0 Secs Display: 0.1 Secs Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 56
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliary mechanical braking device must be used. ATTENTION: This feature should not be used with synchronous or permanent magnet motors. Motors may be demagnetized during braking. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 57
Total Time = 10 + 5 = 15 Seconds Target/2 1/2 S Curve Time Accel Time 1/2 S Curve Time 2.5 Seconds 10 Seconds 2.5 Seconds Total Time to Accelerate = Accel Time + S Curve Time Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 58
1/2 [Motor NP Volts] Settings 5-14 % P032 [Motor NP Hertz] A088 [Maximum Voltage] Sets the highest voltage the drive will output. Values Default Drive Rated Volts Min/Max: 20/Drive Rated Volts Display: 1 VAC Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 59
Sets the carrier frequency for the PWM output waveform. The chart below provides derating guidelines based on the PWM frequency setting. Important: Ignoring derating guidelines can cause reduced drive performance. Values Default 4.0 kHz Min/Max: 2.0/16.0 kHz Display: 0.1 kHz Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 60
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate application. Do not use this function without considering applicable local, national and international codes, standards, regulations or industry guidelines. Options 0 “Disabled” (Default) 1 “Enabled” Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 61
0.0/(Drive Rated Amps × 2) Min/Max: Display: 0.1 Amps A099 [Process Factor] Related Parameter: d010 Scales the value displayed by d010 [Process Display]. Output Process Process Freq Factor Display Values Default 30.0 Min/Max: 0.1/999.9 Display: Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 62
[Fault x Code]) A101 [Program Lock] Protects parameters against change by unauthorized personnel. Options 0 “Unlocked” (Default) 1 “Locked” A102 [Testpoint Sel] Used by Rockwell Automation field service personnel. Values Default Min/Max: 0/FFFF Display: 1 Hex A103 [Comm Data Rate]...
Page 63
Important: Power to drive must be cycled before any changes will affect drive operation. Options 0 “RTU 8-N-1” (Default) 1 “RTU 8-E-1” 2 “RTU 8-O-1” 3 “RTU 8-N-2” 4 “RTU 8-E-2” 5 “RTU 8-O-2” Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 64
Analog inversion can be accomplished by setting this value larger than A113 [Anlg In4-20mA Hi] or by setting A051…A052 [Digital Inx Sel] to option 26 “Anlg Invert”. Values Default 0.0% Min/Max: 0.0/100.0% Display: 0.1% Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 65
Controls the operation of the drive voltage regulation, which is normally operational at decel or when the bus voltage rises. See the Attention statements on page 9 for important information on bus regulation. Options 0 “Disabled” “Enabled” (Default) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 66
Do not create a program that frequently uses configurable outputs to write parameter data to NVS unless A164 [Comm Write Mode] is set to option 1. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Stop Mode P037 Basic Program Drive Temp d024 Display SW Current Trip A098 Advanced Program Drive Type d017 Display Testpoint Data d019 Display Elapsed Run Time d018 Display Testpoint Sel A102 Advanced Program Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 68
Chapter 3 Programming and Parameters Notes: Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Non-resettable This type of fault may require drive or motor repair, or is caused by wiring or programing errors. The cause of the fault must be corrected before the fault can be cleared. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
(Type 2) that indicate possible drive component malfunction are not resettable. Caution should be used when enabling this feature, since the drive will attempt to issue its own start command based on user selected programming. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Check the motor and external wiring has been detected at one or to the drive output terminals for a more of the drive output grounded condition. terminals. page 69 for a description of fault types. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 72
F122 I/O Board Fail Failure has been detected in the 1. Cycle power. drive control and I/O section. 2. Replace drive if fault cannot be cleared. page 69 for a description of fault types. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Source] to option 0 “Keypad”. • Set parameter A051…A052 [Digital Inx Select] to option 5 “Local” and activate the input. I/O Terminal 01 “Stop” input is None Wire inputs correctly and/or install not present. jumper. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 74
Verify settings A051…A052 [Digital Inx Select]. • Check P038 [Speed Reference] for the source of the speed reference. Reprogram as necessary. • Review the Speed Reference Control chart on page Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 75
Digital input is incorrectly None Check input wiring. See Figure wired. Motor wiring is improperly None Switch two motor leads. phased for reverse. Reverse is disabled. None Check A095 [Reverse Disable]. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH. Typical designations include; Type CC - KTK-R, FNQ-R Type J - JKS, LPJ Type T - JJS, JJN Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 79
When using a Manual Self-protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 80
200% Overload capability for up to 3 seconds Electronic Motor Overload Provides class 10 motor overload protection Protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A) (2). UL 508C File 29572. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
22A-D1P4N104 22A-D1P4F104 3-phase 0.75 2.3 A 22A-D2P3N104 22A-D2P3F104 No Filter 4.0 A 22A-D4P0N104 22A-D4P0F104 6.0 A 22A-D6P0N104 22A-D6P0F104 8.7 A 22A-D8P7N104 22A-D8P7F104 Replacement Plate drives are also available. Contact factory for ordering information. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 84
29 W 1321-3R-12-B Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. See the 1321 Power Conditioning Products Technical Data, publication 1321-TD001. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 85
Description Frame Catalog Number IP30/NEMA 1/UL Type 1 Kit Field installed kit. Converts drive to IP30/NEMA 1/ 22-JBAA UL Type 1 enclosure. Includes conduit box with 22-JBAB mounting screws and plastic top panel. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 86
Compatibility: Microsoft Windows 7, Windows 10, and Windows Server 2019 package) You can download DriveTool SP software package at rok.auto/pcdc. Requires Connected Components Workbench software version 20.01.00 or earlier. Requires Connected Components Workbench software version 20.01.00 or later. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 89
Accessories and Dimensions Figure 9 – PowerFlex 4 Flange Mount Drives Dimensions are in millimeters and (inches). Frame A 92.8 54.7 (3.65) (2.15) (6.89) (5.71) (8.27) Frame B 94.3 63.1 (3.71) (2.48) (9.61) (8.43) (9.84) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 90
Dimensions are in millimeters and (inches). Frame A (0.31) (4.49) (0.21) (7.68) (7.05) 97.5 (3.84) (0.31) (0.63) (1.93) (3.86) (5.12) Frame B (5.71) 23.5 (0.26) (0.93) (7.76) (8.27) (8.86) 98.5 (3.88) (0.21) (0.30) (0.55) (1.22) (1.93) (3.86) (6.30) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 91
Dimensions are in millimeters and (inches). Frame A 104.8 (4.13) (3.62) (1.97) (3.46) (0.24) (6.42) (5.98) (6.89) 81.5 (3.21) (0.21) (3.15) Frame B (4.92) (4.41) (3.15) (3.46) (0.37) (7.56) (7.09) (8.03) (3.78) (0.21) (3.94) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 92
AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 AK-R2-030P1K2, AK-R2-120P1K2 Figure 13 – Recommended External Brake Resistor Circuitry 3-phase AC input (Input contactor) M R (L1) S (L2) T (L3) Power off Power on Power source DB resistor thermostat Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 94
Figure 16 – Frame B EMC Line Filters Dimensions are in millimeters and (inches). Catalog Numbers: 22-RF012-BS, 22-RF012-BL (Series B); 22-RF018-BS; 22-RF021-BS, 22-RF012-BL (1.97) (3.94) 29.8 (3.07) (1.17) (8.54) (9.02) (8.50) 17.8 5.5 (0.22) (0.70) 24.0 (0.94) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 95
Catalog Number: 22-RF025-CL (2.36) (5.12) (3.54) (1.26) (11.69) (12.17) (11.69) 5.5 (0.22) (0.67) (1.18) Important: The piggyback mounting option cannot be used with frame B PowerFlex 4 drives and frame C EMC line filters. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 96
Accessories and Dimensions Figure 18 – Remote (Panel Mount) HIM Dimensions are in millimeters and (inches). Catalog Number: 22-HIM-C2 17.6 (0.69) (4.09) (8.66) 2.9m (3.07) (2.60) (7.64) (4.92) 60.5 (2.38) 19.1 (1.50) (0.75) (0.19) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 97
Dimensions are in millimeters and (inches). Catalog Number: 22-HIM-C2S (0.98) (3.66) (7.09) (2.64) (2.36) (6.06) 19.1 (3.03) (0.75) (0.19) 23.5 (0.93) Important: The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 98
Accessories and Dimensions Figure 20 – NEMA Type 1 Bezel Dimensions are in millimeters and (inches). Catalog Number: 22-HIM-B1 11.1 (0.44) (3.66) 25.2 (0.99) (7.09) (2.64) (2.36) (6.06) 19.1 (3.03) (0.75) (0.19) 23.5 (0.93) Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
RS-485 (DSI) Protocol PowerFlex 4 drives support the RS-485 (DSI) protocol to allow efficient operation with Rockwell Automation peripherals. In addition, some Modbus functions are supported to allow simple networking. PowerFlex 4 drives can be multi-dropped on an RS-485 network using Modbus protocol in RTU mode.
Page 100
Only pins 4 and 5 on the RJ45 plug should be wired. The other pins on the PowerFlex 4 RJ45 socket must not be connected because they contain power, and so on. for other Rockwell Automation peripheral devices. Wiring terminations on the master controller will vary depending on the master controller used and “TxRxD+”...
+1. For example, Logic Command may be register address 8192 for some master devices (for example, ProSoft 3150-MCM SLC™ Modbus scanner) and 8193 for others (for example, PanelView™). Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
A xxx.x decimal value where the decimal point is fixed. For example, a decimal 8451 “123” equals 12.3 Hz and “300” equals 30.0 Hz. Returns the same data as Reading (03) Parameter d001 [Output Freq]. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
For example, a decimal “1” is used to address Parameter d001 [Output Freq] and decimal “39” is used to address Parameter P039 [Accel Time 1]. Additional Information Visit www.rockwellautomation.com/en-us/products/hardware/ allen-bradley/vfd.html for additional information. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
• If two peripherals will be powered up at the same time, one must be configured as the “Master” and connected to the Master port (M) and the other must be connected as the “Slave” and connected to the Slave port (S). Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Customer supplied RJ45 male-to-RJ45 male cables with wires connected at pins 4 and 5 only. Both the master (M) and slave (S) ports on the RJ45 splitter Cable operate as standard RS-485 ports in this configuration. Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 108
Appendix D RJ45 DSI Splitter Cable Notes: Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 111
System Grounding, 14 Block Diagram, 24 I/O, 22 I/O Examples, 25, 28 Terminal Block Potentiometer, 25 I/O, 23 Power, 18 Power, 21 PTC Example, 25 Three Wire Control, 25, 28 Two Wire Control, 25, 28 Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 112
Index Notes: Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 113
PowerFlex 4 Adjustable Frequency AC Drive User Manual Rockwell Automation Publication 22A-UM001L-EN-E - September 2024...
Page 114
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, Compact I/O, Connected Components Workbench, DriveExecutive, DriveTools, expanding human possibility, PanelView, PowerFlex, Rockwell Automation, SLC, and TechConnect are trademarks of Rockwell Automation, Inc.