EVCO S.p.A. | EVY Cold STANDARD | Instruction sheet ver. 1.0 | Code 104YCSE103 | Page 1 of 5 | PT 03/24
EVY Cold STANDARD
I
ENGLISH
-
controllers for normal or low temperature units
-
power supply 115... 230 Vac
-
3 analogue inputs for configurable PTC, NTC or Pt 1000 probes
-
door switch digital input
-
3 multi-purpose digital inputs
-
management of variable capacity PWM compressors (Embraco, Secop and Tecumseh),
rather than variable capacity compressors or 0-10 V modulating fans
-
6 digital outputs (electro-mechanical relays)
-
main relay 16 A res. @ 250 Vac or 30 A res. @ 250 Vac (according to the model)
-
sealed relays compliant with the standard EN 60079-15
-
alarm buzzer
-
TTL MODBUS slave port for the EVconnect app or the EPoCA remote monitoring system
-
hot or cold mode regulation
Models available
Purchasing code
Number of relays
Capacity of main relay
EVY216LN9
6
16 A res. @ 250 Vac
EVY236LN9
6
30 A res. @ 250 Vac
EVY236LN9XFT
6
30 A res. @ 250 Vac
1
MEASUREMENTS AND INSTALLATION
Measurements are expressed in mm (inches). Front installation on a plastic or metal panel
(with elastic holding flaps).
N.B.
The metal panel must be between 0.8 and 1.5 mm (1/32 and 1/16 in) thick, while the
plastic panel must be between 0.8 and 3.4 mm (1/32 and 1/8 in)
INSTALLATION PRECAUTIONS
-
ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section
-
do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks
-
in compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
3
FIRST-TIME USE
1.
Carry out the installation following the instructions given in the section MEASUREMENTS
AND INSTALLATION.
2.
Power up the device: an internal test will start up.
The test normally takes a few seconds; when it is finished, the display will switch off.
3.
Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use:
PAR.
DEF.
PARAMETER
SP
0.0
setpoint
P0
1
type of probe
P2
0
temperature measurement unit
d1
0
type of defrost
Next check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION,
without powering up the device.
6.
To perform the configuration upload or download, connect the EVJKEY programming
key.
To activate real-time functions, connect the EVlinking RS-485 EVIF23TSX converter.
To control the device using the EVconnect app, connect the EVlinking BLE EVIF25TBX
module then synchronise it with the app.
To control the device using the EPoCA monitoring system or a third-party MODBUS TCP
system:
-
connect the EVlinking Wi-Fi EVIF25TWX module to the device and then to a local
Wi-Fi network
-
connect the EVlinking RS-485 EVIF24TSX converter to the device then to an IoT
EV3 Web gateway or EVD Web. Next connect this to a free Ethernet port of a
router or an Ethernet hub connected to a local network.
7.
Power up the device again.
4
USER INTERFACE AND MAIN FUNCTIONS
Controllers for refrigerated cabinets and display units
2
ELECTRICAL CONNECTION
N.B.
- use cables of an adequate section for the current running through them
- to reduce any electromagnetic interference, locate the power cables as far away as possible from the signal cables
- port for remote indicator is only available in model EVY236LN9XFT
Manag. of remote indicator
no
no
yes
PRECAUTIONS FOR ELECTRICAL CONNECTION
- if using an electrical or pneumatic screwdriver, adjust the tightening torque
- if the device is moved from a cold to a warm place, humidity may cause condensation to form inside. Wait for about an hour before switching on the power
- make sure that the supply voltage, electrical frequency and power are within the set limits. See the section TECHNICAL SPECIFICATIONS
- disconnect the power supply before carrying out any type of maintenance
- do not use the device as a safety device
- for repairs and further information, contact the EVCO sales network
4.1
Switching the device on/off
1.
If the device is switched on, the display will show the P5 value (default "cabinet or product
temperature"); if the display shows an alarm code, see the section ALARMS.
LED
ON
compressor on
MIN... MAX.
evaporator fans on
r1... r2
0 = PTC
1 = NTC
heating active
2 = Pt 1000
0 = °C
1 = °F
defrost or pre-drip ac-
0 = electric
1 = hot gas
tive
°F
2 = compressor stopped
temperature displayed
in Fahrenheit
°C
temperature displayed
in Celsius
clock active
AUX
auxiliary load 1 on
%
percentage
generated by analogue
output displayed
device off
energy saving active
overcooling
heating active
alarm active
HACCP saved
not displayed
cabinet light on
connection
EVconnect
EPoCA remote
toring system
If Loc = 1 (default) and 30 s have elapsed without the keys being pressed, the display will
show the "Loc" label and the keypad will lock automatically.
4.2
Unlocking the keypad
Touch a key for 1 s: the display will show the label "UnL".
4.3
Setting the setpoint (if r3 = 0, default)
Check that the keypad is not locked.
1.
2.
3.
If POF = 1 (default), touch the ON/STAND-BY key for 4 s
OFF
FLASHING
compressor off
compressor protection active
evaporator fans off
evaporator fans off active
heating not active
demisting on or door heaters on
defrost or pre-drip not
- defrost delay active
active
- dripping active
-
setpoint being set
-
setpoint being set
clock not active
date, time and day of current week
being set
auxiliary loads 1 and 2
auxiliary load 2 on
off
of
power
-
- slow: low humidity function ac-
tive
- rapid: high humidity function
active
device on
device being switched on/off
energy saving not ac-
-
tive
or
over-
overcooling
or
over-
-
heating not active
alarm not active
compressor maintenance request
HACCP
alarm
no HACCP alarm saved
new HACCP alarm saved
or no saved HACCP
alarm not displayed
cabinet light off
cabinet light on from digital input
with
no connection
-
app
or
moni-
Touch the SET key
Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default "-40... 50")
Touch the SET key (or take no action for 15 s)
4.4
Setting the 0-10 V evaporator fan speed for normal operation (percentage 0-
10 V output; available if Ao1... Ao3 = 3 and F30 = 0)
Check that the keypad is not locked.
1.
Touch the SET key twice
Touch the UP or DOWN key within 15 s to set the value within
2.
the limits F31 and F32 (default "50... 100")
3.
Touch the SET key (or take no action for 15 s)
4.5
Activating manual defrost (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1.
Touch the DEFROST key for 2 s
If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 or d2b threshold.
4.6
Manually activating/deactivating the overcooling, overheating and energy-
saving functions
Check that the keypad is not locked.
1.
Touch the DOWN key.
FUNCTION
CONDITION
overcooling
r5 = 0, r8 = 1 and defrost
not activated
overheating
r5 and r8 = 1
energy saving
r5 = 0 and r8 = 2 (default)
If u1c... u6c = 16, the evaporator fans will operate at this speed during the energy-saving
function.
If u1c... u6c = 18, the condenser fans will operate at this speed during the energy-saving func-
tion.
4.7
Manually switching the cabinet light on/off (if u1c... u6c = 5)
1.
Touch the CABINET LIGHT key
4.8 Silencing the buzzer (if u9 = 1, default)
Touch a key.
If u1c... u6c = 11 and u4 = 1, the alarm output is deactivated.
5
ADDITIONAL FUNCTIONS
5.1
Setting the date, time and day of the week (available when the EVlinking RS-
485 EVIF23TSX converter, the EVlinking BLE EVIF25TBX module or the EVlink-
ing Wi-Fi EVIF25TWX module is connected)
N.B.
-
do not disconnect the device from the mains in the two minutes after setting the
date, time and day of the week
-
if the device communicates with the EVconnect app or the EPoCA remote monitor-
ing system, the date, time and day of the week will automatically be set by the
smartphone or tablet
Check that the keypad is not locked.
1.
Touch the ADDITIONAL FUNCTIONS key
2.
Touch the UP or DOWN key within 15 s to select the label "rtc"
Touch the SET key: the display will show the label "y" followed
3.
by the last two figures of the year
4.
Touch the UP or DOWN key within 15 s to set the year
CONSEQUENCE
the setpoint becomes "setpoint -
r6", for the r7 time
the setpoint becomes "setpoint +
r6", for the r7 time
the setpoint becomes "setpoint +
r4", for the HE2 time at the most