Fault Warning Display And Alarm - CyberPower CPS3000PIE User Manual

Cyberpower systems emergency power system user manual
Table of Contents

Advertisement

Step 3: Press and hold the toggle for 4 seconds. When the icons blink, the value of each
item can be changed by slightly pressing the toggle.
Step 4: To save the value and return to general mode, press and hold the toggle for 4
seconds.
Note: If the machine is left idle for over 30 seconds during setup, it will turn off the
backlight and return to general mode automatically.
Note: If user wants to return to general mode without saving changes, there are
two methods:
1. Wait for the backlight to turn off
2. Press and hold the "Display" toggle for 10 seconds

FAULT WARNING DISPLAY AND ALARM

1.
Overheat Protection:
EPS overheat:The output of the machine is removed and the LCD display shows the
temperature exceeds 70℃ (157℉). FAULT Icon lights as well.
2. Over-voltage Protection:The output of the machine is removed. Over Load and
FAULT Icon lights on the LCD display.
3. Battery Missing:A long beep is heard and Battery Icon flashes。
4. The following table shows each corresponding warning message on the LCD display
and the alarm action when the machine output is off:
LCD Warning
Display
Fault Icon
>70
Over Load Icon.
Fault Icon
Alarm
Rapid Beep
High Temperature
Output-Off
Over 70℃
Long Beep
Over Load Output-Off -
Load exceed the rating of
EPS.
11
Condition
CPS3000PIE
Solution
Check fans function and
air vent clearances.
Check total load to
confirm the rating of EPS.