Download Print this page
CyberPower CA50A48V2 User Manual
CyberPower CA50A48V2 User Manual

CyberPower CA50A48V2 User Manual

Cyberpower systems power supply kit user's manual

Advertisement

Quick Links

User's Manual
for CS36A12V2
Bundled Kit
(CA50A48V2 + CS36D12V)
IMPORTANT SAFETY WARNINGS
(SAVE THESE INSTRUCTIONS)
This manual contains important instructions regarding the installation and operation of this device.
Read this manual thoroughly before attempting to unpack, install or operate this device
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area free of conductive contaminants. (Please see specifications for
acceptable temperature and humidity range.)
CAUTION! T
o reduce the risk of electric shock, do not remove the cover except to service the
battery. No user serviceable parts are inside except the batter
y.
CAUTION!
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to the instructions.
CAUTION!
This unit must be wall mounted. Do not use the unit unless it is mounted correctly.
INTRODUCTION
The CS36A12V2 provides increased flexibility and cost effectiveness by separating the power supply
unit (CA50A48V2) from the battery back up unit (CS36D12V). The power supply plugs into a 110/120Vac
outlet. It converts the power to 48Vdc, which is then fed through a power cord to the battery back up unit.
The battery back up unit feeds 12Vdc to the ONT.
SYSTEM BLOCK DIAGRAM
ONT
CA50A48V2
CS36D12V
Power Supply
Battery Back Up
110/120Vac
48Vdc
12Vdc
INSTALLATION
Carefully follow these instructions during the installation of this device:
1.) Carry out the installation in a safe area that is free of excessive dust and has adequate airflow.
2.) Screws must be appropriate for total weight of the UPS unit and the mounting surface material.
3.) Do not operate the UPS where the temperature and humidity are outside the specified limits.
(Refer to specifications in this manual.)
OVERVIEW (CA50A48V2)
1
1. Power Connector
2
3
6
Compartment Cover
7
2. Strain Relief Lip
3. 2 Pin IDC Connector
4. Power LED Indicator
5. Screw Hole
6. Keyhole Screw Slot
7. Cable Channel
8. Input Power Cord (8 ft.)
4
5
8
CA50A48V2 Front
CA50A48V2 Back
OVERVIEW (CS36D12V)
1
1. Battery Compartment Cover
2
2. Control Buttons
(Alarm Silence / Battery
Emergency Use)
3
3. LED Indicators
4
(Auxiliary Power Source /
Replace Battery / Battery
5
Power / System Status)
4. Battery Compartment
6
CS36D12V Front
5. 9 Pin Conductor Compartmemt
Cover
6. Battery Release Latch
7. Interconnection & Power Cable
Channel
7
8. Keyhole Screw Slot
9. Pass Through Hole for
8
Interconnection & Power Cable
9
CS36D12V Back
CA50A48V2 Installation Guide
Step 1:
Step 2:
Step 3:
a. Open the power connector
a. Install output power cable to the 2
a. Place screw in keyhole screw slot
compartment cover.
position IDC connector (red wire
and tighten half way.
to positive, black wire to negative).
b. Slide unit so that the screw rests
b. Thread the power cable along the
against the narrow end of the slot.
back of the power connector cover.
c. Place second screw into the screw
Wrap the power cable around the
hole and tighten securely.
strain relief lip. Insert the cable
d. Tighten keyhole slot screw securely.
through one of the cable slots to
e. Close the power connector
exit the compartment.
cpmpartment cover.
c. Insert the power cable into one of
the cable channels on the back of
the unit.
NOTE :
Please use appropriate size screws to mount the CA50A48V2 on the wall.
NOTE :
Recommended screw size: Self-tapping screw M4x20L (Truss head)
CS36D12V Installation Guide
A
a
b
Step 1:
Step 2:
a. Press the battery cover release latch (A) and
a. Insert the power and interconnection cables
slide the cover to remove.
into the back cable channel. Feed the
b. Remove the 9 pin connector compartment
cable end into the 9 pin connector
cover by pulling outward.
compartment.
b. Securely mount the unit on the wall with 2
mounting screws.
NOTE :
Please use appropriate size screws to mount the CS36D12V on the wall.
NOTE :
Recommended screw size: Self-tapping screw M4x20L (Truss head)
Fig.1
Vin +
Vin -
Vout +
Vout -
Signal Return
On Battery
a
Replace Battery
c
Missing Battery
c
Low Battery
b
Step 3:
Step 4:
a. Remove protective shipping terminal covers from
a. Install both power and interconnection cables to
the battery if necessary.
the 9 position IDC connector.
b. Connect the battery cable leads to the appropriate
(See case for the pin assignments.)
terminals; red to postive, black to negative.
b. Close the 9 pin connector compartment cover.
c. Insert the battery into the battery compartment.
c. Close the battery cover.
d. Install the 9 position IDC connector to the unit (see Fig.1).
The UPS battery charges when it is connected to utility power. The battery charges
fully during the first 24 hours of normal operation. Do not expect full battery run
capability during this initial charge period.
Operation Guide
Start-Up: Plug the CA50A48V2 power supply into AC power. The unit is now ready to be placed into
service. The CS36D12V has four LED indicators and two control buttons. The table below
lists the functions of each.
LED Indicators
Indicator
Color
Condition
Alarm Silence Button
Blue
Press and hold the button for 1 second to silence the audible alarm.
Battery Emergency
Blue
Press and hold the button to activate emergency battery capacity.
Use Button
Auxiliary Power Source
Green
Indicates that an external power source with adequate voltage
(12Vdc) is connected to the CS36D12V.
Replace Battery
Red
Battery replacement required. Alarm will beep once every 15 minutes.
Battery Power
Green
Indicates the battery is supplying the power. At 45% battery capacity,
this LED will flash and then alarm will beep 4 times per minute.
System Status
Green
Indicates normal mode of operation.
Status LED, Alarm & Communication Signals
Condition
Status LED
Alarm
Interface
Description
Normal
System LED On
All communication
Condition normal; AC power load, charges battery.
signals in Low state
Battery is connected and in good condition.
ON Battery
Battery LED On
Open
48V input failure or loose connection between
power supply and battery board; battery is supplying
the power.
Replace Battery
Replace Battery
1/2 sec beep
Open
Every 45 days, the unit will automatically initiate a
LED On
every 15 min
battery test. The test lasts 16 hours. if the battery
needs to be replaced, an alarm signal will be sent to
the Central Office.
Battery Missing
None, only
Open
Approximately 6 seconds after battery removal, the
ON sees
system initiates battery detection routine. Upon
alarm
failure, an alarm signal will be sent.
Low Battery
Battery LED Flash
1/2 sec beep
Open
When battery capacity is < 45% (approximately
every 15 sec
12Vdc), unit signals low battery.
Battery Type
The battery is a standard sealed lead acid battery rated at 12Vdc / 7.2Ah. If required, the battery may be
replaced with an approved 12Vdc / 7Ah battery.
Batteries are considered HAZARDOUS WASTE and must be disposed of properly.
Most retailers that sell batteries collect used batteries for recycling.
Auxiliary Power Connection (AUX)
Connection point for customer-supplied DC input voltage (12Vdc). At 45% remaining capacity, the
CS36D12V switches from internal battery to external source. The auxiliary power source supplies power
to the load (ONT) in the event of 48V input voltage failure and a battery capacity of <45%.
Maintenance Mode
Maintenance mode determines remaining useful battery life. During the 16 hour test, the battery is
discharge to determine its state. The unit measures the rate of change in the battery charge. If the rate of
discharge is excessive, the battery replacement indicator is activated.
The CS36D12V enters the maintenance mode approximately once every 45 days.
In the event that the CS36D12V is in the maintenance mode and an AC failure occurs, maintenance
mode will cease and the CS36D12V will supply the power to the load.
FCC NOTICE:
This equipment has been tested and found to comply with the limit for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: (1) Reorient or relocate the receiving antenna.
(2) Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. (4) Consult the dealer or an
experienced radio/TV technician for help.
CAUTION: Signal cables must be used with this device to ensure compliance with Class B FCC limits.
CAUTION: Any changes or modifications could void the authority granted by the FCC to operate this equipment.
CS36D12V Battery Replacement
Fig.2
c
A
Step 1:
Step 2:
a. Press battery cover catch (A) and slide the cover to the left
a. Replace battery cable on the new battery.
to remove.
b. Place the new battery into battery compartment.
b. Remove the battery connector (see Fig.2).
c. Close the battery cover.
c. Remove the battery strain release latch to remove battery.
Specification
Model
CA50A48V2
CS36D12V
Input
Voltage Range
120Vac
48Vdc
Frequency Range
50 / 60Hz
Output
Output Voltage (Normal)
48Vdc
12Vdc
Output Voltage (Battery Mode)
10.5 ~ 20Vdc
Output Power Max
48W
34W
Ripple
less than 200 mV
Connector Type
Insulation Displacement Connector (IDC)
Battery
Battery Type
Sealed, Maintenance Free Lead-Acid Battery
Numbers of Battery
7.2Ah / 12V
Auxiliary Input Power
12Vdc / 1.3mm COAX Power Jack
Warning Diagnostics
AC Power
Auxiliary Power Source /
Indicators
Replace Battery /
Battery / System
Alarm
AC Fail / Replace Battery
Replace Battery /
Low Battery
Management
Communication Interface
Signal Retun / On Battery /
Replace Battery / Missing
Battery / Low Battery
Physical
Maximum Dimensions (L*W*D)
5.94 x 2.65 x 1.56 in
6.89 x 6.75 x 3.47 in
Weight (lb)
0.77lb
1.51lb
Environment
-4 o F ~ +115 o F (-20 o C ~ +46 o C)
Operating Temperature
Operating Humidity
0 - 95% noncondensing within enclosure
Max Operating Elevation
10,000ft (3,000m)
Max Storage Elevation
50,000ft (15,000m)
-4 o F ~ +113 o F (-20 o C ~ +45 o C)
Storage Temperature
K01-3612000-03

Advertisement

loading

This manual is also suitable for:

Cs36d12vCs36a12v2