Page 1
U0753484_2451_EN_1 24/05/2023 MAINTENANCE MANUAL LOGIC AIR 8-10 Air/water heat pump Monobloc system To be safety stored by the user for reference by installers.
150 mm 1500 mm 200 mm 3000 mm 300 mm 3500 mm 400 mm M = 300 mm Max 500 mm N = 500 mm Max 600 mm - 4 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB. >> If Outdoor fan motor is normal, replace Main PCB. BLACK WHITE BLACK WHITE - 10 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 11
>> Check if indicated value swings berween AC30v and AC130V at outdoor unit terminal 2 - 3. >> If it is abnormal, replace Controller PCB. BLACK WHITE BLACK WHITE LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 11 -...
Page 12
>> If abnormal condition is found, correct it. Check Point 2 : Replace Main PCB If Check Point 1 do not improve the symptom, replace Main PCB of outdoor unit. - 12 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 13
Check if temporary voltage drop was not generated. Change Main PCB. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 13 -...
Page 14
Check Point 3 : Replace Inverter PCB Replace Outdoor unit Inverter PCB. Check Point 4 : Replace Main PCB If Check Point 1~3 do not improve the symptom. Change Main PCB. - 14 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 15
Outdoor unit Inverter PCB while the compressor stops. Forecast of cause: 1. Outdoor unit Inverter PCB failure Check Point 1 : Replace Inverter PCB Replace Outdoor unit Inverter PCB. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 15 -...
Page 16
Main PCB P15 :3-4 voltage value =5V Remove the thermistor from Main PCB, check the voltage. If the voltage does not appear, replace Main PCB and execute the check operation again. - 16 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 17
Main PCB P10 :1-3 voltage value =5V Remove the thermistor from Main PCB, check the voltage. If the voltage does not appear, replace Main PCB and execute the check operation again. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 17 -...
Page 18
Main PCB P15 :1-2 voltage value = Remove the thermistor from Main PCB, check the voltage. If the voltage does not appear, replace Main PCB and execute the check operation again. - 18 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 19
Main PCB P5 :1-3 voltage value =5V Remove the thermistor from Main PCB, check the voltage. If the voltage does not appear, replace Main PCB and execute the check operation again. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 19 -...
Page 20
Remove the thermistor from Inverter PCB, check the voltage 1 2 3 1 2 3 P700 If the voltage do not appear, replace Inverter PCB and execute the check operation again. - 20 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 21
1 2 3 4 5 6 Expansion valve temperature thermistor (PA1: 4-6) If the voltage do not appear, replace Main PCB, and excecute the check operation again. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 21 -...
Page 22
Remove the thermistor from Supply PCB, check the voltage 1 2 3 1 2 3 If the voltage do not appear, replace Supply PCB and execute the check operation again. - 22 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 23
Check the complete insulation of grounding. Check Point 3 : Replace Inverter PCB If Check Point 1, 2 do not improve the symptom, change Inverter PCB. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 23 -...
Page 24
Change Inverter PCB, and execute the check operation again. Type of contact Characteristics of pressure switch (P770) Pressure switch 4.2 0.1MPa Contact : Short Open Pressure Contact : Open Short 3.2 0.15MPa - 24 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 25
>> 2pin (White) - 3pin (Black) Voltage is refer to the following graph. Voltage (V) Pressure (MPa) I I f the voltage is not correct, replace Pressure sensor. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 25 -...
Page 26
If Check Point 1, 2 do not improve the symptom, change Main PCB. Check Point 4: Replace Compressor If Check Point 3 do not improve the symptom, change Compressor. - 26 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 27
If Check Point 3 do not improve the symptom, change Main PCB. Check Point 5: Replace Compressor If Check Point 3 do not improve the symptom, change Compressor. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 27 -...
Page 28
If the voltage is not correct, replace Inverter PCB. Check Point 5 : Replace Main PCB If Check Pint 1~4 do not improvethe symptom, replace Main PCB. - 28 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 29
Check if the pump is blocked, and correctly supplied between PCB and Pump else >>Replace the condenser circulation pump. Check Point 2 : If error is still displayed after restarting >>Replace ODUM Hydraulic PCB and Main PCB . LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 29 -...
Page 30
Check Point 4 : Check the discharge temp. thermistor Discharger temp. thermistor characteristics check (Check by disconnecting thermistor from PCB. Refer to the Troubleshooting 9) Check Point 5 : Check the refrigerant amount Leak check - 30 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 31
Check Point 4 : Check the compressor temp. thermistor Compressor temp. thermistor characteristics check (Check by disconnecting thermistor from PCB. Refer to the Troubleshooting 9) Check Point 5 : Check the refrigerant amount Leak check LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 31 -...
Page 32
Check Point 6 : Check the suction pressure sensor Suction pressure sensor characteristics check (Characteristics of Suction pressure sensor, ) Check Point 7 : Check the refrigerant amount Leak check - 32 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 33
Check Point 3 : Check the Heatsink temperature thermistor Heatsink temperature thermistor characteristics check (Check by disconnecting thermistor from PCB) Refer to the Troubleshooting 11 Check Point 2 : Replace Inverter PCB Replace Inverter PCB LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 33 -...
Page 34
-> Replace the the flow rate sensor Else replace the condenser circulation pump. If error is still displayed -> Replace ODUM Hydraulic PCB and Main PCB - 34 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 35
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse. If the symptom does not change by above Check 3, replace Main PCB. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 35 -...
Page 36
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding. >> If the symptom dose not change by above check 1,2 replace main PCB of outdoor unit. - 36 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 37
Is there any objet which obstruct the fan rotation ? Check if vibration noise by loose bolt or contact noise of piping is happening Is Compressor looked ? >> Check Compressor (Outdoor Unit error code) LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 37 -...
(Refer to the next page). >> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.) Replace Compressor - 38 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 39
Compressor. Resistance Value : % at 20°C Check Point 3 : Replace Main PCB If the symptom does not change with above Check 1, 2, replace Main PCB. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 39 -...
Page 40
, there is a possibility of inside clogged. In this case, replace Strainer. Pipe (In) Pipe (Out) Pipe (In) Pipe (Out) - 40 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 41
(wire color) 1 (Red) DC voltage (Vm) No function No function 4 (Black) 5 (White) Control voltage (Vcc) 6 (Yellow) Speed command (Vsp) 7 (Brown) Feed back (FG) LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 41 -...
** Acoustic power level @standard rating cond. (EN 14511-2) A7W55 outdoor unit. *** When the outdoor temperature continuously exceeds 35°C, DHW heating is done by the water heater heating element. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 43 -...
fl oor fl ow/ return temps responsibility into question Service station high return temp (infrared thermometer) *Not required and not shown on the device. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 45 -...
Page 46
Disconnect the compressor relay and the condenser connection. Measure the resistance value at the points shown on the illustration, and then compare the values observed with those in the table. Single phase type Multimeter Resistor 1 MOhm or more Main PCB - 46 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 48
Too : Heat exchanger temperature Defrost Too(n-1) : Too value of 5min ago Too10 : Too value at 10 min later from operation start OT : Outdoor temperature - 48 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
• Move the sensor between the exchanger blades to a place where the exchanger is iced up. • If all these points have been checked, replace the outdoor controller board. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 49 -...
3-way valves. Wait 3 minutes, turn the power on and perform a • If an error occurs, recover the refrigerant from service port. Sign “ - 50 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
► Right service panel removal Unscrew the 5 screws. ► Top panel removal Unscrew the 4 screws. Unscrew the 7 screws. - 54 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
► Main PCB removal Unscrew the 4 screws. Remove the connectors and the wires. Press the 4 locking spacers to remove the PCB. - 56 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Place the hook in front of the triangle mark. Remove the 3 connectors. Unscrew the screw. Remove all connectors and wires. Press the 4 locking spacers to remove the inverted PCB. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 57 -...
Remove the connectors and wires. Press the 4 locking spacers to remove the hydronic circuit PCB. ► Control box unit removal Unscrew the 5 screws. Unscrew the 2 screws. - 58 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 59
Unscrew the 2 screws. Remove the binders. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 59 -...
Fan motor removal Remove the fan nut and the fan propeller. Cut the binders. Loose the clamps to remove the fan motor lead wire. Unscrew the mounting screws. LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN - 61 -...
Cut the binders to remove the isolation. Push the hook to remove the thermistor (outdoor temperature). Remove the thermistor (EEV). ► 4-way valve coil removal Unscrew the mounting screw. Remove the solenoid coil. - 62 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Tighten the fl are part gripping it (Tightening torque:12 1.5N m). PRESSURE SWITCH 100°C Do the static electricity measures. 3-WAY VALVE (GAS) 120°C 3-WAY VALVE (LIQUID) 120°C - 70 - LOGIC AIR 8-10 / Maintenance Manual / 2451 - EN...
Page 72
are in conformity with the relevant Union harmonized directives and regulations: are in conformity with the requirements of the relevant UK legislation: - Low Voltage Directive (LVD) - 2014/35/EU - Electrical Equipment (Safety) Regulations 2016 - S.I. 2016 No. 1101 - Machinery Directive - 2006/42/EC - Supply of Machinery (Safety) Regulations 2008 - S.I.
Need help?
Do you have a question about the LOGIC AIR 8 and is the answer not in the manual?
Questions and answers