Configuring the Master

3-4

Configuring the Master

Opening the Master DTM
Configuration Interface
Master Address
Unit Number
3-4-1

Setting the Master Parameters

Master Setup Tab
After configuring all the slave DTMs, the CS1/CJ1W-PRM21 Master DTM
must be configured. In order to open the Master DTM Configuration Interface
do either one of the following.
• Select the CS1/CJ1W-PRM21 Master DTM in the Network view and dou-
ble-click the left mouse button.
• Select the CS1/CJ1W-PRM21 Master DTM in the Network view, and
right-click the mouse. From the context menu, select Configuration.
The DTM Configuration User Interface is shown below.
In the first tab, the device address and the unit number must be set. The
device address can be set in the range from 0 to 125.
The setting of the unit number is required to setup communication with the
Unit through CX-Server. The setting in the user interface must match the set-
ting made with the rotary switch on the front of the Unit.
Note The device address is normally assigned automatically. Only in the case
where there are other devices in the network which have the same address,
the device address of the CS1/CJ1W-PRM21 Master DTM may need to be
changed.
After making the changes, select the Save button in the lower right corner of
the user interface to accept the changes. Next select the Master Setup tab, to
display the Master Setup options.
The Master Setup tab defines
• the behaviour of the Master Unit, when the PLC CPU switches its mode
between RUN / MONITOR and PROGRAM mode.