Generic Slave Device Dtm - Omron WS02-9094G - V1.0 Operation Manual

Table of Contents

Advertisement

Generic Slave Device DTM

1,2,3...
Monitoring
1,2,3...
2-5

Generic Slave Device DTM

1. Select the DTM in the Network view and right-click the mouse to display
the context menu.
2. Select Download Parameters from the menu, to initiate a download. A
communication channel through the CIF driver will be opened.
Alternatively, the following can be done.
Select the DTM in the Network view and press the Download button in the
toolbar to start the download process.
Note In case the driver assignment has not been done prior to attempting the
download, an error message will be displayed.
For monitoring, an online connection with the Unit must be made first. To
achieve this perform the following sequence.
1. To go on line, perform one of the following actions.
• Select the DTM in the Network view.
• Select the Device - Go Online option from the main menu, or the DTM
context menu, or
• Select the
2. A communication channel will be opened through the CIF Driver. The
name of the DTM in the Network view, will turn to Italic font, to indicate that
the Unit is on-line.
3. From the context menu, select the Diagnosis option. The DTM's Diagnos-
tics User Interface will be displayed.
Most of the current PROFIBUS DP slave devices are supplied with a GSD file
in order to allow a configurator to setup a configuration for that particular slave
device. OMRON's Generic Slave Device DTM is provided to allow integration
of the GSD file based configuration options into an FDT Container application,
like CX-Profibus.
The GSD files are stored in a separate sub-directory under CX-Profibus.
Upon updating the Device Catalogue, the Generic Slave Device DTM will
scan this sub-directory and present an entry in the Device Catalogue for each
of the GSD files found.
Upon adding the GSD based slave device to the network, an instance of the
Generic Slave Device DTM will be made in the PC memory, which will read
the GSD file contents. The instance of the Generic Slave Device DTM will pro-
vide the user interface necessary to make the settings for the associated
slave device.
button from the Tool Bar.
Section 2-5