Omron WS02-9094G - V1.0 Operation Manual page 144

Table of Contents

Advertisement

Number
Message
02
PROFIBUS I/O Data exceeds
memory range
03
Slaves should have unique
addresses
04
DTM cannot be added to the net-
work, it is not a PROFIBUS device
DTM
05
Max. number of slaves configured.
New slave cannot be added
06
Slave address overlap detected.
New address assigned: [new
address]
07
Invalid data set received from a
slave DTM. Slave parameter
changes ignored
08
Set Parameters failed. Slave can-
not be configured
09
No slaves assigned. Download
aborted
10
Slave(s) has no modules. Down-
load aborted
11
Configured EM bank (banks) is
not available in the connected
PLC.Download aborted
12
Connected unit is busy. Download
aborted
13
Slave configuration too big
14
Maximum number of modules
exceeded
15
PROFIBUS Master is not in cor-
rect mode. Please set the PROFI-
BUS Master in one of the following
modes: STOP, CLEAR or OPER-
ATE.
16
Master Unit indicated failure of Set
Device Station Address.
17
'New address' and/or 'Ident num-
ber (hex)' are/is empty.
Description
Input / Output area exceeds memory
range (combination of start address
and length).
Unique bus addresses must be
assigned for each slave.
The slave DTM cannot be con-
nected, e.g. if adding HART device
DTM.
DTM can not be added, since the
master has already the maximum
number of slaves (125) assigned.
Changing the address of an existing
slave results in an address overlap.
An internal error has occurred pre-
venting the master DTM to obtain
the slave's parameter set.
An internal error has occurred pre-
venting the master DTM from set-
ting/changing the slave's bus
address.
No slaves have been assigned to the
master. At least one slave must be
assigned.
A slave (or slaves) has no modules.
The configured EM bank (banks) are
not available in the connected PLC.
Unit is busy with parameter storage. Retry download when parameter
The total number of configured
parameter bytes and configuration
bytes does not fit into the FINS mes-
sage for downloading.
The total number of configured I/O
modules over all allocated slave
devices can not exceed 4000.
The Set Device Station Address
command can not be executed
because the PROFIBUS Master is
not in correct mode, i.e. the Master
Unit is OFFLINE.
When sending Set Device Station
Address command, one of the fol-
lowing problems occurred:
• The slave has deactivated this
service.
• The slave has not responded to
the request.
• The slave does not have sufficient
memory space for the request
data.
No data is entered in the New
Address and Ident Number fields.
Appendix
Correction
Change the configuration to be
within the memory area and retry
download.
Change the addresses of the slaves
and ensure no duplicates are
present. Retry download.
Avoid using non-PROFIBUS DP
DTMs.
Do not add any more DTMs. If more
are still needed, a second PROFI-
BUS Master Unit on the same PLC
system may be solution.
Automatically recovers.
Add a new slave DTM into the net-
work (or change the modules of the
existing slave) with correct slave
parameter set.
Non recoverable. Master DTM tries
to assign a new bus address to the
slave DTM, but the slave DTM's
database is locked.
Retry download when at least one
slave has been assigned.
Retry download when modules have
been added to the slave(s) having
no modules.
Change the configuration to use only
memory areas available in the PLC
and retry download.
storage has finished.
Reduce the configuration.
Do not add any more modules to the
configuration.
Set the PROFIBUS Master into one
of the following modes: STOP,
CLEAR or OPERATE.
• Check target Slave device on the
PROFIBUS network.
• Check specified Slave address.
• Check Slave timeout parameter
Fill-in both the 'New address' and the
'Ident number (hex)' fields.
129