Self-Diagnosis
Non-fatal Errors
Programming
LEDs on Master
Console LEDs
TR/
TEST
ERR
OK
REMOTE I/O
lit
not lit
ERR
lit
not lit
lit
not lit
not
not lit
lit
lit
not lit
lit
---
lit
---
I/O VER ERR
flash
not lit
flash
not lit
/not
lit
Fatal Errors
Programming
LEDs on Master
Console LEDs
TR/
TEST
ERR
OK
I/O SET ERR
flash
not lit
/lit
78
LEDs on
Slave
END
LINE
TR/
ERR
RS
ERR
ERR
CHK
lit
not
lit
not lit lit
lit
not
not
not
not lit not lit/lit
lit
lit
lit
---
not
lit
lit
lit
not
not
lit
not lit lit
lit
lit
---
lit
lit
not lit lit
---
not
not
not lit ---
lit
lit
---
not
---
---
lit
not
not lit flash
not lit lit
lit
---
not
lit
litt
lit
LEDs on
Slave
END
LINE
TR/
ERR
RS
ERR
ERR
CHK
---
not
lit
lit
lit
Remote
Cause
Terminal LEDs
POWER TR/
ERR
lit
Transmission line
broken.
not
CPU Unit error in
lit
Slave or Remote
Terminal.
lit
lit
Master or Slave
I/O bus error.
lit
CPU Unit error in
Master.
lit
Transmission line
shorted.
---
Power not
supplied to Slave.
not lit
not
Power not
lit
supplied to
Remote Terminal.
---
I/O Unit added to
or removed from
Master, Slave, or
Remote Terminal.
lit
lit
Remote Terminal
using same word
as PC. Same
Slave unit number
or same Remote
Terminal word
number set twice.
Remote
Cause
Terminal LEDs
POWER TR/
ERR
lit
lit
Input and Output
specifications are
incorrect for I/O
Units on Slave
Racks or for
Remote
Terminals.
Section 7-1
Correction
Correct
transmission line.
Replace Slave or
Remote Terminal.
Check Slave I/O
units on Slave and
Rack.
Replace Master.
Correct
transmission line.
Supply power to
Slave.
Supply power to
Remote.
Check I/O table on
Programming
Console and
correct if
necessary. If I/O
table is Ok,
correct I/O
configuration.
Correction
Check I/O table on
Programming
Console and
correct if
necessary. If I/O
table is OK,
correct I/O Unit
configuration.