Omron WIRED REMOTE I-O System Manual page 64

Rack pcs
Table of Contents

Advertisement

Remote Terminal
Switches
Pins 1 to 5: Word Setting
Pin 6: Output HOLD/STOP Mode
54
Remove the switch cover to access the DIP switch and terminator switch. Set
these as shown below. The switch cover is in a slightly different position on
G72C Remote Terminals.
Pins 1 to 6
Word numbers are computed as binary numbers with pins 1 through 5 repre-
senting the one's place though the 16's place. For example, turning on all five
pins would set word 31, i.e., 2
Pin 5 must be set OFF for all Remote Terminals, in C120 Systems, i.e., the
highest word that can be set is 15.
The word actually allocated to a Remote Terminal depends on the PC that
controls it and is computed as shown in the following table.
PC
C120 and C500
C1000H and C2000H
C200H
OFF: STOP mode
ON: HOLD mode
Transmission errors for Remote Terminals are the same as those for Slaves.
+
ON (right):
OFF (left):
0
1
2
3
4
+ 2
+ 2
+ 2
+ 2
Allocated word
Same as switch setting
32 x word multiplier of Master + switch setting
Switch setting + 200
All output words set to OFF for transmission errors.
All output words retain status for transmission errors.
Section 4-2
Terminator
All others
= 1 + 2 + 4 + 8 + 16 = 31.