Common Specifications - Omron VARISPEED F7 Datasheet

Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Common specifications

Enclosures
Model CIMR-F7Z
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110
Enclosed type - IP20)
Open chassis type -IP00
Model CIMR-F7Z
40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
Enclosed type - IP20
Open chassis type - IP00
Common specifications
Model number CIMR-F7Z
Control method
Torque characteristics
Speed control range
Speed control accuracy
Speed control response
Torque limits
Torque accuracy
Frequency range
Frequency accuracy
(temperature characteristics)
Frequency setting resolution
Output frequency resolution
Overload capacity and
maximum current
Frequency setting signal
Accel/decel time
Braking torque
Main control functions
Motor protection
Instantaneous overcurrent
protection
Fuse blown protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power loss ride
through
Cooling fin overheating
Stall prevention
Grounding protection
Charge indicator
Ambient operating temperature
Ambient operating humidity
Storage temperature
Application site
Altitude
Vibration
Varispeed F7
Available as standard
Available by removing the upper and lower cover of
enclosed type
Available as standard
Available by removing the upper and lower cover of
enclosed type
Sine wave PWM
Closed loop vector control, open loop vector control, V/f control, V/f with PG control
Heavy duty (low carrier, constant torque applications): 2 kHz carrier frequency, 150% overload for 1 minute,
Normal duty 1 (high carrier, variable torque applications): maximum carrier frequency, depending on inverter capacity,
Normal duty 2 (variable torque applications): carrier frequency reduced, continuous overload capability increased
Provided (4 quadrant steps can be changed by constant settings.) (Vector control)
0.01 to 150 Hz (Heavy Duty), 0.01 to 400 Hz (Normal Duty 1 or 2)
Heavy duty (low carrier, constant torque applications): 150% of rated output current for 1 minute
Normal duty 1 or 2 (high/reduced carrier, variable torque applications): 120% of rated output current for 1 minute
0.01 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration time settings)
Approximately 20% (approximately 125% with braking resistor option, braking transistor built into inverters of 18.5 kW or less)
Restarting after momentary power loss, speed search, overtorque/undertorque detection, torque limits, 17-speed control
(maximum), 4 acceleration and deceleration times, S-curve acceleration/deceleration, 3-wire control, auto-tuning
(rotational or stationary), dwell function, cooling fan ON/OFF control, slip compensation, torque compensation,
auto-restart after fault, jump frequencies, upper and lower limits for frequency references, DC braking for starting and stopping,
high-slip braking, advanced PID control, energy-saving control, MEMOBUS communications (RS-485/422, 19.2 kbps maximum),
2 motor parameter sets, fault reset and parameter copy function.
Heavy duty (low carrier, constant torque applications): 150% of rated output current for 1 minute
Normal duty 1 (high carrier, variable torque applications): 120% of rated output current for 1 minute
Normal duty 2 (high carrier, variable torque applications): 120% of rated output current for 1 minute,
200 class inverter: stops when main-circuit DC voltage is above 410 V.
400 class inverter: stops when main-circuit DC voltage is above 820 V.
200 class inverter: stops when main-circuit DC voltage is below 190 V.
400 class inverter: stops when main-circuit DC voltage is below 380 V.
By selecting the momentary power loss method, operation can be continued if power is restored within 2 s.
Stall prevention during acceleration, deceleration and running independently.
Illuminates when the main circuit DC voltage is approx. 10 VDC or more.
- 20 C to + 60 C (short-term temperature during transportation)
Available for option
Available as standard
Specification
higher carrier frequency possible with current derating.
120% overload for 1 minute.
1:40 (V/f control)
1:100 (open loop vector control)
1:1000 (closed loop vector control)
± 3% (V/f control)
± 0.03% (V/f control with PG)
± 0.2% (open loop vector control)
± 0.02% (closed loop vector control)
(25 C ± 10 C)
5 Hz (control without PG)
30 Hz (control with PG)
± 5%
Digital references: ± 0.01% (-10 C to +40 C)
Analog references: ± 0.1% (25 C ±10 C)
Digital references: 0.01 Hz
Analog references: 0.025/50 Hz (11 bits plus sign)
0.01 Hz
0 to +10V, -10 to +10 V, 4 to 20 mA, pulse train
Protection by electronic thermal overload relay.
Stops at approx. 200% of rated output current.
Stops for fuse blown.
increased continuous output current.
Protection by thermistor.
Protection by electronic circuits.
-10 C to 40 C (enclosed wall-mounted type)
-10 C to 45 C (open chassis type)
95% max. (with no condensation)
Indoor (no corrosive gas, dust, etc.)
1000 m max.
2
10 to 20 Hz, 9.8 m/s
max.; 20 to 50 Hz, 2 m/s
N/A
Available for option
Available as standard
2
max
N/A
271