Connecting the NT Support Tool

3-3

Connecting the NT Support Tool

28
grounding points. We recommend grounding the shield at one end, as shown in
the following diagram.
Signal lines
Host
RS-422A/485
shield
In order to install the system program in the NT21, or to transmit screen data
created with the NT Support Tool to the NT21, the NT21 must be connected to a
personal computer with an RS-232C cable.
The NT21 connects with the RS-232C cable from a personal computer at serial
port A. When the host is connected at serial port B, the connection with the host
can be maintained as it is while the NT21 is connected to the RS-232C cable
from a personal computer.
However, when a bar code reader is being used, it must be disconnected, so that
the RS-232C cable can be connected, since they both use serial port A.
Communication Conditions
The communication conditions are automatically set when the system installer
and NT Support Tool are started.
Recommended Connector Cable
Use the cable indicated below.
• CV500-CN228 (length: 2 m), made by OMRON
(D-SUB 9-pin, male ⇔ D-SUB 25-pin, male)
• XW2Z-S001 (conversion cable), made by OMRON
(D-SUB 25-pin, female ⇔ half pitch 14-pin, male)
• XW2Z-S002 (length: 2 m), made by OMRON
(D-SUB 9-pin, male ⇔ D-SUB 9-pin, female)
For details on making a connector cable, refer to Appendix E Making the Cable
for Connecting a PC (page 199).
NT-AL001
RS-232C
NT21
Connect to the
terminal block's
FG terminal.
RS-232C
NT21
RS-232C
NT21
Serial port A
(RS-232C, 9-pin)