Connecting to the RS-232C Port at the Host
Port 1
m
m+1
m+1
m+2
m+3
Connecting to a CPU Unit
44
located on the front panel. Set each switch with a flat blade screwdriver so that
the values or symbols in the setting value window agree with the following.
CS1W-SCU21
SCU21
RUN
ERC
SD1
RD1
CJ1W-SCU41
Allocation DM Area Settings for CPU Unit
Settings are written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocated DM Area (PC Setup) of the CPU
Unit. After the settings are written, they become effective by turning the power
ON, restarting the Unit, restarting the communication port, or execution of the
STUP instruction.
The following table shows the words allocated in the DM Area and the settings.
Allocated DM word
Port 2
m+10
m+11
m+11
m+12
m+13
CV-series and CVM1/CV-series (-EVj) CPU Units
CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2
PC Setup
When connecting to a CVM1/CV-series CPU Unit, set the following communica-
tion conditions for the PC Setup.
Item
Baud rate
Stop bits
Parity
Data length
Unit #
*1 Set the Host Link baud rate at 9,600 bps or 19,200 bps with the memory
switch at the NT21. For details, refer to Setting the Host Link Method (page
127).
Either set PC Setup directly from a Programming Device (e.g., SYSMAC Sup-
port Software), or transmit the PC Setup made at a Programming Device to the
CPU Unit.
For details on the PC Setup, refer to the SYSMAC CVM1/CV500/1000/2000 Op-
eration Manual: Ladder Diagrams (W202-E1-j).
RDY
ERH
SD2
RD2
UNIT
Set the unit number to 0 through F so
F E
1 0
No.
that it will not duplicate the numbers
C
used in other Units.
Set the unit number to 0 through F so
that it will not duplicate the numbers
used in other Units.
Value
Value
Host Link mode, 2 stop bits, even parity, data
8000
length 7 bits
0000
Baud rate 9,600 bps.
0007
Baud rate 19,200 bps.
0000
Transmit delay time 0 ms.
0000
No CTS control Unit No.0 for Host Link
Set the same baud rate as set at the NT21
2 stop bits
Even
ASCII 7 bits
00
Section
m = DM30000 + 100 × unit number
Settings
Settings
Setting at Host
(*1)
4-1