Omron GRT1-PNT - DATASHEET 2 Operation Manual page 49

Profinet io communication unit
Table of Contents

Advertisement

Setting up the PROFINET IO network
2-5-4
Establishing the PROFINET IO network
This section describes how to create, connect to and configure the PROFINET
IO network using the CX-ConfiguratorFDT software and the Device DTMs.
1 Select the Network Components (see previous section) and build network.
2 Connect the Personal Computer to the ethernet network.
-
The PROFINET Scan Tool to assign the IO Device names can only
operate connected to the ethernet network.
-
The parameter settings and monitoring of the GRT1 Slice I/O Units is
done directly on the ethernet network.
3 Start the CX-ConfiguratorFDT software. Install the appropriate GSD files
and DTMs for the connected IO Devices.
4 Configure the system to communicate with PLC / Profinet IO Controller.
Add the PROFINET IO Controller as parent to the network.
Set IP address in DTM.
Set IP address in on-line by using the Network Scan View.
Confirm the on-line connection by putting the DTM on-line.
5 Build up the network within CX-ConfiguratorFDT. Add the IO Devices to the
Tree of the network by drag-dropping from the Device Catalogue. Assign
the modules for each individual IO Device.
6 Allocate the modules of the IO Devices to the intended PLC memory areas.
7 Download the configuration to the Unit.
8 Confirm proper operation. Checking the Monitoring GUI of DTM and LED
status of the Unit.
Section 2-5
37