Control circuit

Type
No.
S1
Forward run/stop command
S2
Reverse run/stop command
S3
S4
Multi-step speed reference 1
S5
(Master/auxiliary switch)
S6
Multi-step speed reference 2
S7
Jog frequency reference
SC
SN
SP
Digital input power supply
+V
A1
A2
Multi-function analog input
Analog reference common
AC
Shield wire, optional ground line
E(G)
M1
M2
M3
M4
MA
MB
MC
Multi-function analog output
FM
AC
Multi-function analog output
AM
R+
MEMOBUS communications input
R-
S+
MEMOBUS communications output
S-
IG
Note:
1.The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1
for S6 and multi-step speed setting 2 for S7.
2.Do not use this power supply for supplying any external equipment.
3.When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode.
Internal heatsink
55 ˚C
45 ˚C
320
Signal name
*1
External fault input
*1
Fault reset
*1
Auxiliary frequency reference when
*1
*1
Digital input common
Digital input neutral
15 V power output
Frequency reference
connection point
Running signal
(1NO contact)
Zero speed
Zero level (b2-01) or below when ON
Fault output signal
(frequency output)
Analog common
0 to 10 V, 10V = 200% of the inverter
(current monitor)
Signal common
Remove the upper and lower covers
for the models of 15 kW or less in
200 V and 400 V classes.
Upper cover
Upper part air
temperature
-10 to 55 ˚C
Heatsink
Open chassis
type inverter
Lower cover
Inverter inlet
temperature
-10 to 45 ˚C
Peripheral
temperature 40 ˚C
Cover MTG screw
Function
Forward run when ON; stopped when OFF.
Reverse run when ON; stopped when OFF.
Fault when ON.
Reset when ON
ON.
Multi-step setting 2 when ON.
Jog frequency when ON.
+24 VDC power supply for digital inputs
15 V power supply for analog references
0 to +10 V/100%
4 to 20 mA/100%
0 V to +10 V/100%
0 to 20 mA/100%
Operating when ON.
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
0 to 10 V, 10 V=100%
output frequency
rated current
For 2-wire RS-485, short R+ and S+ as well as R- and S-.
When using open chassis type inverters of 200 V/400 V
22 kW or more, secure spaces for eyebolts and wiring
of the main circuit.
Upper cover
50 mm or more
Heatsink
30 mm or more
50 mm or more
Lower cover
photocoupler isolation
Functions are selected by
setting H1-01 to H1-05.
24 VDC, 250 mA max.
15 V (max. current: 20 mA)
0 to +10 V (20 k )
4 to 20 mA (250
Function is selected by
0 V to +10 V (20 k )
setting H3-09.
0 to 20 mA (250
Multi-function
contact outputs
1 A max. at 250 VAC
1 A max. at 30 VDC
Multi-function analog
output 1
0 to +10 V max. ±5%
Multi-function analog
output 2
Differential input,
photocoupler isolation
Differential input,
photocoupler isolation
120 mm or more
30 mm
120 mm or more
or more
Side spaces
Top and bottom spaces
Frequency inverters
Signal level
24 VDC, 8 mA
*2
)
)
Relay contacts
contact capacity:
*3
2 mA max.
Air
Air