SPECIFICATIONS

Functional Specifications
Adjustments/Settings
Overcurrent
Underload (dry-well)
Overvoltage
Undervoltage
Number of restarts allowed in 60
second period (rapid-cycling)
Trip Delay Times
Overcurrent
Dry-well
Restart Delay Times
Over/undervoltage
All other faults
Input Characteristics
Supply Voltage
Load Range
233-P
233-1.5-P
Frequency
Output Characteristics
Output Contact Rating-SPST
233-P
233-1.5-P
General Characteristics
Operating Temperature
Ambient
Surrounding Air
Storage Temperature
Power Consumption
Wire Gauge
Terminal Torque
Standards Passed
Electrostatic Discharge (ESD)
Safety Marks
UL
CSA
Dimensions
Weight
Mounting Methods
© 2008 SymCom, Inc. All Rights Reserved
125% of calibration point
Adjustable (70-90% of calibrated run power)
265VAC
190VAC
4
5 seconds
4 seconds
2 seconds
Manual, 2-225 minutes
230 VAC
1/3 – 3 hp
1/3 – 1.5 hp
50/60 Hz (note: 50Hz will increase all delay timers
by 20%)
3hp @ 240VAC (17 Amps max.)
1.5hp @ 240VAC (10 Amps max.)
-40° to 40°C (-40° to 104°F)
-40° to 55°C (-40° to 131°F)
-40° to 80° C (-40° to 176°F)
5 Watts (max.)
Solid or stranded 10 - 22AWG
13 in.-lbs.
IEC 1000-4-2, Level 2, 4kV contact, 6kV air
UL508
C22.2 No. 14
5.26" W x 2.93" H x 2.90" D
14 oz.
#8 screws