Web Guiding System Installation and Operating Manual ekr CON 600 ekr CON 600 net Application with Wide Array Edge Sensors MD.547.EN.01 Translation of the Original Manual...
Page 2
BST GmbH Remusweg 1 D-33729 Bielefeld Tel.: +49 (0) 521 400 70 0 Fax: +49 (0) 5206 999 999 E-Mail: info@bst.group Internet: www.bst.group This documentation is protected by copyright. The translation as well as reproduction and distribution in any form is forbidden without the approval...
Checking Correct Connection.................. 25 8 Commissioning.................... 26 Safety Instructions ...................... 26 Requirements...................... 27 Performing the Material Setup ................... 27 9 Operation ...................... 28 Safety Instructions ...................... 28 Operation Display ....................... 28 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Page 4
10.3.1 Cleaning the Wide Array Edge Sensor Housing............ 36 11 Troubleshooting.................... 37 12 Accessories and Spare Parts ................ 38 12.1 Order Address ...................... 38 12.2 Accessories........................ 38 Index........................ 39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
These instructions and all other applicable documents are a com- ponent of the product and must be handed over to the operating company of the system. ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 5/39...
Operations using the keys are indicated by the following symbols: Press key ①. ► Press key ① or key ②. ► Press key ① and key ② at the same time. ► 6/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Installation and commissioning manual MD.541 ekr CON 600, ekr CON 600 net The latest version of these instructions can be obtained in all available languages at: www.bst.help ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 7/39...
CON 600, ekr CON 600 net web guiding controller before working with or on the system. 8/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Wide array edge sensor 1 Wide array edge sensor 2 Fig. 1: ekr CON 600, ekr CON 600 net controller with wide array edge sensors The wide array edge sensors are connected to the CAN bus inter- face of the controller as Sensor 1 or Sensor 2 using a special con- nection box.
(38 mm and 101 mm) and various measuring ranges (30 mm to 467 mm) (see Infrared Wide Array Edge Sensors IR SEN 400 ... 409, page 16). 10/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
The web of material should be placed in the middle of the sensor fork (in the middle between the two measuring transducers) for optimum guiding results. ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 11/39...
Signification the LED The sensor has detected no web edge. The sensor has detected one web edge. GREEN The sensor has detected two web edges. 12/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Guiding to the right web edge Web center-line guiding with two wide array edge sensors Web center-line guiding Web center-line guiding with one wide array edge sensor ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 13/39...
0 to +75 °C during operation Storage temperature 0 to +75 °C Protection category IP 40 Noise emission < 70 dB Housing dimensions See dimensional drawing RoHS conformity * in preparation 14/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Page 15
Fig. 4: Dimensions of the ultrasonic wide array edge sensors US SEN 300 ... 309 Sensor Dimension US SEN 300 US SEN 301 US SEN 302 US SEN 303 US SEN 304 US SEN 305 US SEN 306* US SEN 307 US SEN 308* US SEN 309 * in preparation ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 15/39...
0 to +75 °C during operation Storage temperature 0 to +75 °C Protection category IP 40 Noise emission < 70 dB Housing dimensions See dimensional drawing RoHS conformity * in preparation 16/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Page 17
Fig. 5: Dimensions of the infrared wide array edge sensors IR SEN 400 ... 409 Sensor Dimension IR SEN 400 IR SEN 401 IR SEN 402 IR SEN 403 IR SEN 404 IR SEN 405 IR SEN 406 IR SEN 407 IR SEN 408* IR SEN 409* * in preparation ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 17/39...
CAN bus connection to the controller Cable diameter = 7 mm min. bend radius = 70 mm = Fixing dimensions Fig. 6: Dimensions of the connection box 18/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Observe the following Conditions: ► Ambient Conditions Permissible values Storage temperature 0 ... 75 °C (+32 ... +167 °F) Air humidity 5 ... 90 % , non-condensing ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 19/39...
■ Minimum clearance of 100 mm to electro-magnetic fields ■ (energy sources or high voltage lines) No sources of heat in the immediate vicinity ■ 20/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Page 21
(in the middle between the two measuring transducers). Minimize vertical fluctuations (flutter) of the web of material ► within the sensor measuring range. ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 21/39...
1. Add the threaded boreholes M3 to the machine frame accord- ing to the picture. 2. Using four screws M3, attach the connection box to the machine frame. 22/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Please also read and follow all safety instructions contained in ► the operating manual for the ekr CON 600, ekr CON 600 net controller (document number MD.542). ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 23/39...
CON 600 Connection box Connection box Wide array edge sensor 1 Wide array edge sensor 2 Fig. 9: Connection diagram for wide array edge sensors 24/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
(Sensor 1, Sensor 2) depending on the sensor type: Sensor type Text displayed Ultrasonic wide array edge sensor WdeArUS US SEN 300 … 309 Infrared wide array edge sensor WdeArIR IR SEN 400 … 409 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 25/39...
Commissioning This manual only describes the steps that are required to commis- sion wide array edge sensors on the ekr CON 600, ekr CON 600 net controller. Any further necessary commissioning work is described in the installation and commissioning manual for the ekr CON 600, ekr CON 600 net controller (document number MD.541).
(see Performing the Material Setup, page 32). During the material setup the controller is automatically adjusted to the properties of the material to be scanned. ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 27/39...
The appearance of the operation display depends on the number of connected wide array edge sensors. Operation with one wide array edge sensor Fig. 11: Operation with one wide array edge sensor (connected as Sensor 1) 28/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Page 29
Fig. 12: Operation with one wide array edge sensor (connected as Sensor 2) Operation with two wide array edge sensors Fig. 13: Operation with two wide array edge sensors ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 29/39...
The numeric value indicates the current position of the right web edge in the sensor measuring range. The displayed ③ value is based on the center of the sensor measuring range (position 0). 30/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Page 31
Edge 2 Measuring range (e.g. 162 mm) Edge 1 Edge 2 Measuring range (e.g. 162 mm) Edge 1 Edge 2 Measuring range (e.g. 162 mm) ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 31/39...
(material within the sensor measuring range). After recording the signal levels the microprocessor uses the two values to calculate the opacity of the material. 32/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
(Sensor 1 here). 6. Completely clear the selected sensor’s scanning area (no material in the sensor scanning area). 7. Press the > button. ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 33/39...
Page 34
The bar indicator shows the dark value measured. 11. Press the button. The dark value will be saved. The material setup for the selected sensor is completed. The setup menu is displayed. 34/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Never use cleaning agents containing solvents, not even with ► intensive soiling, unless the respective cleaning agent is explicitly listed in the instructions. Follow the cleaning instructions. ► ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 35/39...
Clean carefully using a dry, clean and soft cloth (e.g. glasses ► wipe). Use a commercially available liquid cleaner in event of intensive ► soiling. Perform the material setup after cleaning. ► 36/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
The web edge to be scanned is located outside the Correct the position of the wide array edge ► measuring range of the wide array edge sensor. sensor across the web running direction. ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 37/39...
131 994 Cable extension 5 m Connection of wide array edge sensors (CAN bus) 131 995 Cable extension 10 m 168 176 Spiral cable 0.5 m / 2 m 38/39 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors...
Function ............ 32 Types.............. 10 performing ............. 33 Operating manual Distribution ............ 5 Latest version........... 7 Storage............. 5 Operation display Display of the edge position ...... 31 ekr CON 600, ekr CON 600 net – Application with Wide Array Edge Sensors 39/39...