TECHNICAL GUIDE
SUNLINE MagnaDRY™
GAS/ELECTRIC SINGLE PACKAGE
AIR CONDITIONERS
DR 180, 240 & 300
15 thru 25 NOMINAL TONS
11.0 EER (15 TONS), 10.2 EER (20 TONS),
9.7 EER (25 TONS)
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
®
DESCRIPTION
YORK Sunline MagnaDRY™ units are convertible sin-
gle package high efficiency rooftops. All models have
independent dual refrigerant circuits for efficient part
load operation. Although the units are primarily
designed for curb mounting on a roof, they can also be
slab-mounted at ground level or set on steel beams
above a finished roof.
All units include:
Powder Paint finish that meets ASTM-B-117 1000
hour salt spray standards
Two-stage cooling provided by dual independent
refrigeration circuits with expansion valves, filter-
driers, high and low pressure/loss of charge
switches and freezestats
Scroll compressors
Two-stage heating provided by dual independent
heat exchangers with aluminized steel tubes,
redundant gas valves, spark ignition with induced
draft logic
Permanently lubricated motors
Bottom or side air discharge configuration capabil-
ity (field convertible)
Belt Drive Blower Motor with high static drive
option
Manufactured under the quality standards of
ISO9001
Simplicity® Control Board
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and toolless latched doors
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and
wired
CSA agency approvals on all units
WARRANTY
One-year parts warranty
A Five-year parts warranty on the compressors
and electric heat elements
Ten-year parts warranty on the gas-fired heat
exchangers
036-21539-003-B-0305

Advertisement

Table of Contents
loading

Summary of Contents for York SUNLINE MagnaDRY DR180C/E00

  • Page 1 036-21539-003-B-0305 ® DESCRIPTION YORK Sunline MagnaDRY™ units are convertible sin- gle package high efficiency rooftops. All models have TECHNICAL GUIDE independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams SUNLINE MagnaDRY™...
  • Page 2: Table Of Contents

    036-21539-003-B-0305 TABLE OF CONTENTS DESCRIPTION ........1 LIST OF TABLES PRODUCT NOMENCLATURE.
  • Page 3 036-21539-003-B-0305 LIST OF TABLES (CONTINUED) 27 DR300 BLOWER PERFORMANCE - 25 TON 35 DR ELECTRICAL DATA - STANDARD DRIVE STANDARD DRIVE ......44 MOTOR WITH POWERED CONVENIENCE OUTLET .
  • Page 4: Product Nomenclature

    036-21539-003-B-0305 PRODUCT NOMENCLATURE Unitary Products Group...
  • Page 5 036-21539-003-B-0305 PRODUCT NOMENCLATURE - Continued 15-25T Sunline MagnaDRY™ Model Number Nomenclature Additional Options - Standard Cabinet None Phase Monitor Coil Guard Dirty Filter Switch Phase Monitor & Coil Guard Phase Monitor & Dirty Filter Switch Coil Guard & Dirty Filter Switch Phase Monitor, Coil Guard, &...
  • Page 6 036-21539-003-B-0305 Additional Options - Standard Cabinet CPC Controller, DFS, APS, Double Wall, SS Drain Pan, Phase Monitor, & Coil Guard CPC Controller, DFS, APS, Double Wall, SS Drain Pan, & Technicoat Cond Coils CPC Controller, DFS, APS, Double Wall, SS Drain Pan, & Technicoat Evap Coil CPC Controller, DFS, APS, Double Wall, SS Drain Pan, &...
  • Page 7 036-21539-003-B-0305 Additional Options - Standard Cabinet Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, &...
  • Page 8 036-21539-003-B-0305 Additional Options - Standard Cabinet Technicoat Condenser Coil, Phase Monitor, & Coil Guard Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator Coil Technicoat Evaporator Coil &...
  • Page 9 036-21539-003-B-0305 Additional Options - Standard Cabinet Simplicity Intelli-Comfort Controller, Double Wall, & Technicoat Evap Coil Simplicity Intelli-Comfort Controller, Double Wall, & Technicoat Evap and Cond Coils Simplicity Intelli-Comfort Controller, Double Wall, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Simplicity Intelli-Comfort Controller, Double Wall, SS Drain Pan, Phase Monitor, &...
  • Page 10 036-21539-003-B-0305 Additional Options - Hinged Filter Door & Toolless Access Cabinet BM SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Double Wall Double Wall &...
  • Page 11 036-21539-003-B-0305 Additional Options - Hinged Filter Door & Toolless Access Cabinet Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap.
  • Page 12 036-21539-003-B-0305 Additional Options - Hinged Filter Door & Toolless Access Cabinet Honeywell Excel 10 Controller, DFS, APS, Double Wall, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Double Wall, & Technicoat Cond Coils Honeywell Excel 10 Controller, DFS, APS, Double Wall, & Technicoat Evap Coil Honeywell Excel 10 Controller, DFS, APS, Double Wall, &...
  • Page 13 036-21539-003-B-0305 Additional Options - Hinged Filter Door & Toolless Access Cabinet UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Technicoat Evaporator Coil, Phase Monitor, &...
  • Page 14 036-21539-003-B-0305 Additional Options - Hinged Filter Door & Toolless Access Cabinet Simplicity Intelli-Comfort Controller, Double Wall, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Double Wall, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Double Wall, SS Drain Pan, &...
  • Page 15: Features

    036-21539-003-B-0305 FEATURES • Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further All models are available with a wide variety of factory- ensured by programmable minimum run times. For mounted options such as stainless steel heat exchangers, testing, the anti short cycle delay can be temporarily phase monitor, dirty filter switch, and coil guard to make them...
  • Page 16: Reheat Mode Sequence Of Operation

    When the room thermostat calls for second stage cool- ing, the RCB senses a signal through "Y1" & "Y2" and • BAS Controls - York’s Magnum series units offer factory engages circuit #1 and circuit #2 in the cooling mode. mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.
  • Page 17: Reheat Control Board

    036-21539-003-B-0305 "ALTERNATE” MODE When the room thermostat calls for second stage cool- ing, the RCB senses a signal through "Y1" & "Y2" and When the RCB detects a need for dehumidification de-energizes the HGR, which de-energizes SOL 3 and (24VAC) at "HUM" via the field supplied dehumidistat SOL 2, and energizes SOL 1.
  • Page 18: Reheat Controls - Part 1

    036-21539-003-B-0305 UNIT CONTROL REHEAT CONTROL BOARD BOARD HUMIDIFY TERMINAL REHEAT RELAY RHTB REHEAT TERMINAL BLOCK FIGURE 3 - REHEAT CONTROLS - PART 1 REHEAT SOLENOID REHEAT REHEAT SOLENOID SOLENOID UNIT CONTROL BOARD REHEAT CONTROL BOARD FIGURE 4 - REHEAT CONTROLS - PART 2 Unitary Products Group...
  • Page 19: Factory-Installed Options

    • BAS - Building Automation System Controls Simplic- The enthalpy system contains one sensor that monitors ity® INTELLI-Comfort™ CONTROL - The York® Sim- the outdoor air and determines when the air is cool plicity® INTELLI-Comfort™ control is factory installed. It enough and dry enough to provide free cooling.
  • Page 20: Field-Installed Accessories

    036-21539-003-B-0305 • SMOKE DETECTORS - (supply air & return air) The Power exhaust is not available as a field installed option. smoke detectors stop operation of the unit by interrupting • ROOF CURBS - Fourteen-inch high roof curbs provide a power to the control board if smoke is detected within the water-tight seal between the unit and the finished roof.
  • Page 21: Sound Power Rating

    036-21539-003-B-0305 TABLE 1: SOUND POWER RATING SOUND POWER (db 10 Watts) BLOWER UNIT Octave Band Centerline Frequency (Hz) dB(A) SIZE dB(A) 1,000 2,000 4,000 8,000 10Ft. 6,000 1.00 1,080 4.60 8,000 1.00 1,120 6.65 10,000 1.30 1160 12.5 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only.
  • Page 22: Cooling Capacity For Dr180

    036-21539-003-B-0305 TABLE 4: COOLING CAPACITY FOR DR180 Temperature of Air on Condenser Coil Air on Evap- orator Coil 75°F 85°F Total Total † Sensible Capacity (MBH) Sensible Capacity (MBH) Total Total Return Dry Bulb (°F) Return Dry Bulb (°F) Cap. Input Cap.
  • Page 23: Cooling Capacity For Dr240

    036-21539-003-B-0305 TABLE 5: COOLING CAPACITY FOR DR240 Temperature of Air on Condenser Coil Air on Evap- orator Coil 75°F 85°F Total Total † Sensible Capacity (MBH) Sensible Capacity (MBH) Total Total Return Dry Bulb (°F) Return Dry Bulb (°F) Cap. Input Cap.
  • Page 24: Cooling Capacity For Dr300

    036-21539-003-B-0305 TABLE 6: COOLING CAPACITY FOR DR300 Temperature of Air on Condenser Coil Air on Evap- orator Coil 75°F 85°F Total Total † Sensible Capacity (MBH) Sensible Capacity (MBH) Total Total Return Dry Bulb (°F) Return Dry Bulb (°F) Cap. Input Cap.
  • Page 25: Cooling Capacities For Dr180 At 85°F (Alternate Reheat Mode)

    036-21539-003-B-0305 TABLE 7: COOLING CAPACITIES FOR DR180 AT 85°F (ALTERNATE REHEAT MODE) AIR ON TEMPERATURE OF AIR ON CONDENSER COIL (°F): 85 EVAPORATOR COIL TOTAL TOTAL SENSIBLE CAPACITY (MBH) CAPACITY INPUT RETURN DRY BULB (°F) °F (MBH) (kW) 11.2 10.7 4500 10.5 11.2...
  • Page 26: Cooling Capacities For Dr180 At 105°F

    036-21539-003-B-0305 TABLE 9: COOLING CAPACITIES FOR DR180 AT 105°F (ALTERNATE REHEAT MODE) AIR ON TEMPERATURE OF AIR ON CONDENSER COIL (°F): 105 EVAPORATOR COIL TOTAL TOTAL SENSIBLE CAPACITY (MBH) CAPACITY INPUT RETURN DRY BULB (°F) °F (MBH) (kW) 12.6 12.2 4500 12.0 12.6...
  • Page 27: Cooling Capacities For Dr180 At 125°F

    036-21539-003-B-0305 TABLE 11: COOLING CAPACITIES FOR DR180 AT 125°F (ALTERNATE REHEAT MODE) AIR ON TEMPERATURE OF AIR ON CONDENSER COIL (°F): 125 EVAPORATOR COIL TOTAL TOTAL SENSIBLE CAPACITY (MBH) CAPACITY INPUT RETURN DRY BULB (°F) °F (MBH) (kW) 4500 14.8 14.3 5050 13.9...
  • Page 28: Cooling Capacities For Dr240 At 85°F

    036-21539-003-B-0305 TABLE 12: COOLING CAPACITIES FOR DR240 AT 85°F (ALTERNATE REHEAT MODE) AIR ON TEMPERATURE OF AIR ON CONDENSER COIL (°F): 85 EVAPORATOR COIL TOTAL TOTAL SENSIBLE CAPACITY (MBH) CAPACITY INPUT RETURN DRY BULB (°F) °F (MBH) (kW) 18.0 17.4 6000 17.1 17.9...
  • Page 29: Cooling Capacities For Dr240 At 105°F (Alternate Reheat Mode)

    036-21539-003-B-0305 TABLE 14: COOLING CAPACITIES FOR DR240 AT 105°F (ALTERNATE REHEAT MODE) AIR ON TEMPERATURE OF AIR ON CONDENSER COIL (°F): 105 EVAPORATOR COIL TOTAL TOTAL SENSIBLE CAPACITY (MBH) CAPACITY INPUT RETURN DRY BULB (°F) °F (MBH) (kW) 6000 14.5 14.1 6875 13.9...
  • Page 30: Cooling Capacities For Dr300 At 85°F

    036-21539-003-B-0305 TABLE 16: COOLING CAPACITIES FOR DR300 AT 85°F (ALTERNATE REHEAT MODE) AIR ON TEMPERATURE OF AIR ON CONDENSER COIL (°F): 85 EVAPORATOR COIL TOTAL TOTAL SENSIBLE CAPACITY (MBH) CAPACITY INPUT RETURN DRY BULB (°F) °F (MBH) (kW) 23.7 22.7 7500 22.3 23.7...
  • Page 31: Dr180 Moisture Removal - Alternate Mode

    036-21539-003-B-0305 15-Ton Moisture Removal @ 5600cfm Alternate mode @ various indoor (wet bulb/dry bulb) conditions. Outdoor Temp ºF 80/71 75/71 85/71 80/67 85/67 75/67 FIGURE 5 - DR180 MOISTURE REMOVAL - ALTERNATE MODE 15-Ton Moisture Removal @ 5600cfm Normal mode @ various indoor (wet bulb/dry bulb) conditions. Outdoor Temp ºF 80/71 75/71...
  • Page 32: Dr240 Moisture Removal - Alternate Mode

    036-21539-003-B-0305 20-Ton Moisture removal @ 7750cfm Alternate Mode @ various indoor (wet bulb/dry bulb) conditions Outdoor Temp ºF 75/71 80/71 75/67 85/71 80/67 85/67 FIGURE 7 - DR240 MOISTURE REMOVAL - ALTERNATE MODE 20-Ton Moisture Removal @ 7750cfm Normal Mode @ various indoor (wet bulb/dry bulb) conditions Outdoor Temp ºF 75/67 75/71...
  • Page 33: Dr300 Moisture Removal - Alternate Mode

    036-21539-003-B-0305 25-Ton Moisture Removal @ 8000cfm Alternate Mode @ various indoor (wet bulb/dry bulb) conditions Outdoor Temp ºF 75/67 80/71 85/71 80/67 85/67 FIGURE 9 - DR300 MOISTURE REMOVAL - ALTERNATE MODE 25-Ton Moisture Removal @ 8000cfm Normal Mode @ various indoor (wet bulb/dry bulb) conditions Outdoor Temp ºF 75/71 80/71...
  • Page 34: Altitude Correction Factors

    036-21539-003-B-0305 CFM, STATIC PRESSURE, AND POWER - ALTI- order to use the indoor blower tables for high altitude applica- tions, certain corrections are necessary. TUDE AND TEMPERATURE CORRECTIONS A centrifugal fan is a "constant volume" device. This means The information below should be used to assist in application that, if the rpm remains constant, the CFM delivered is the of product when being applied at altitudes at or exceeding same regardless of the density of the air.
  • Page 35: Altitude/Temperature Conversion Factor

    036-21539-003-B-0305 ltitude/Temperature Conversion Factor SEA LEVEL TEMPER TURE (°F) FIGURE 11 -ALTITUDE/TEMPERATURE CONVERSION FACTOR Unitary Products Group...
  • Page 36: Dr180 Blower Performance - 15 Ton Standard Drive (Cooling Only)

    036-21539-003-B-0305 TABLE 19: DR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (COOLING ONLY) 15 ton Standard Drive Blower Performance (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 6373 931 3.343 4.01 6172 899 3.058 3.67 5821 868 2.664 3.20 5591 834 2.415 2.90 5332 801 2.154 2.59 5081 769 1.859 2.23...
  • Page 37: Dr180 Blower Performance - 15 Ton High Static Drive (Cooling Only)

    036-21539-003-B-0305 TABLE 20: DR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (COOLING ONLY) 15 Ton High Static Drive Blower Performance (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 8032 1168 6.346 7.80 7765 1129 5.808 7.14 7396 1092 5.143 6.32 7225 1053 4.552 5.60 6936 1013 4.209 5.18 6573 972 3.730 4.48 6271 933 3.307 3.97...
  • Page 38: Dr180 Blower Performance - 15 Ton Standard Drive (Gas Heat)

    036-21539-003-B-0305 TABLE 21: DR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (GAS HEAT) 15 ton Standard Drive Blower Performance (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 6246 912 3.276 3.93 6049 881 2.997 3.60 5705 851 2.611 3.13 5479 818 2.367 2.84 5225 785 2.111 2.53 4979 754 1.822 2.19 0.4 5893 914 3.037 3.65 5667 882 2.777 3.33 5301 852 2.364 2.84 5055 819 2.163 2.60 4757 786 1.893 2.27 4505 755 1.628 1.95 0.6 5498 916 2.783 3.34 5257 883 2.486 2.98 4916 853 2.124 2.55 4610 820 1.938 2.33 4287 788 1.699 2.04 3999 757 1.435 1.72...
  • Page 39: Dr180 Blower Performance - 15 Ton High Static Drive (Gas Heat)

    036-21539-003-B-0305 TABLE 22: DR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT) 15 Ton High Static Drive Blower Performance (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 7871 1145 6.22 7.65 7610 1106 5.69 7.00 7248 1070 5.04 6.20 7081...
  • Page 40: Dr240 Blower Performance - 20 Ton Standard Drive (Cooling Only)

    036-21539-003-B-0305 TABLE 23: DR240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (COOLING ONLY) DR240 Standard Drive Blower Performance (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 9445 1025 6.94 8.79 9021 993 6.211 7.87 8684 962 5.59 7.08 8422 929 5.057 6.41 8028 896 4.516 5.72 7677.5 863 4.00758 5.08 0.4 9172 1027 6.629 8.40 8645 995 5.912 7.49 8282 963 5.3 6.72 8022 930 4.781 6.06 7605 897 4.259 5.40 7243 864 3.75462 4.76 0.6 8689 1028 6.283 7.96 8262 996 5.606 7.10 7869 965 5 6.34 7585 931 4.482 5.68 7160 898 3.971 5.03 7182.8 864 3.47616 4.41...
  • Page 41: Dr240 Blower Performance - 20 Ton High Static Drive (Cooling Only)

    036-21539-003-B-0305 TABLE 24: DR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (COOLING ONLY) DR240 Blower Performance (Horizontal Discharge) (High Static Option) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 10477 1118 9.15 11.64 10161 1086 8.42 10.70 9949 1056 7.76 9.86 9634 1025 7.05 8.96 9232 973 6.43 8.18 8880 956 5.74 7.30 0.4 10144 1119 8.82 11.21 9792 1088 8.06 10.24 9589 1057 7.41 9.42 9231 1025 6.75 8.58 8849 974 6.13 7.79 8473 951 5.45 6.92 0.6 9826 1121 8.58 10.91 9427 1089 7.70 9.79 9209 1058 7.08 9.00 8852 1026 6.43 8.18 8570 993 5.90 7.50 8101 955 5.18 6.58...
  • Page 42: Dr240 Blower Performance - 20 Ton Standard Drive (Gas Heat)

    036-21539-003-B-0305 TABLE 25: DR240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (GAS HEAT) DR240 Standard Drive Blower Performance (Gas heat) (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 9260 1005 6.804 8.62 8844 974 6.089 7.72 8514 943 5.48 6.94 8257 911 4.958 6.28 7871 878 4.427 5.61 7527 846 3.929 4.98 0.4 8992 1007 6.499 8.24 8475 975 5.796 7.35 8120 944 5.199 6.59 7865 912 4.687 5.94 7456 879 4.175 5.29 7101 847 3.681 4.66 0.6 8519 1008 6.16 7.81 8100 976 5.496 6.96 7715 946 4.903 6.21 7436 913 4.394 5.57 7020 880 3.893 4.93 7042 847 3.408 4.32...
  • Page 43: Dr240 Blower Performance - 20 Ton High Static Drive (Gas Heat)

    036-21539-003-B-0305 TABLE 26: DR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (GAS HEAT) DR240 Blower Performance (Gas Heat) (Horizontal Discharge) (High Static Option) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.2 10272 1096 8.98 11.4 9962 1065 8.25 10.5 9754 1035 7.61 9.67 9445 1005 6.91 8.79 9051 954 6.31 8.02 8706 937 5.63 7.16 0.4 9945 1097 8.65 11 9600 1067 7.9 10 9401 1036 7.27 9.24 9050 1005 6.62 8.41 8675 955 6.01 7.64 8307 932 5.34 6.79...
  • Page 44: Dr300 Blower Performance - 25 Ton

    036-21539-003-B-0305 TABLE 27: DR300 BLOWER PERFORMANCE - 25 TON STANDARD DRIVE DR300 Blower Performace (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.4 9550 996 7.1 9.04 8800 959 6.1 7.79 8700 950 5.9 7.53 8250 913 4.95 6.97 8050 877 4.7 5.99 7250 842 3.9 4.97 0.6 9010 997 6.6 8.43 8150 960 5.6 7.15 8010 950 5.4 6.89 7540 915 4.57 6.44 7290 879 4.2 5.33 6460 843 3.5 4.47 0.8 8430 998 6.1 7.79 7510 961 5.1 6.51 7330 952 4.9 6.25 6820 916 4.09 5.77 6480 880 3.7 4.76 5600 844 3.1 3.99...
  • Page 45: Dr300 Blower Performance - 25 Ton

    036-21539-003-B-0305 TABLE 28: DR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE DR300 Blower Performance (Horizontal Discharge) ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP 0.4 11600 1200 12.5 16.0 11175 1164 11.5 14.7 10620 1127 10.4 13.3 10500 1092 9.2 11.7 9875 1058 8.2 10.5 9100 1020 7.4 9.4 0.6 11060 1201 11.8 15.1 10600 1166 10.8 13.8 10100 1131 9.7 12.4 9980 1095 8.6 11.0 9320 1060 7.6 9.7 8920 1022 6.9 8.8 0.8 10500 1203 11.1 14.2 10100 1169 10.2 13.0 9520 1132 9.1 11.6 9360 1097 8 10.2 8600 1061 6.9 8.8 8230 1024 6.3 8.0...
  • Page 46: Static Resistances

    036-21539-003-B-0305 TABLE 29: BLOWER MOTOR AND DRIVE DATA BELT ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY MOTOR (NOTCHED) BLOWER MODEL DRIVE RANGE OUTSIDE PITCH OUTSIDE PITCH PITCH SIZE EFF. DESIG- BORE DESIG- BORE DESIG- (RPM) HP FRAME DIA. DIA. DIA. DIA. LENGTH QTY.
  • Page 47: Dr Electrical Data - Standard Drive Motor W/O Powered Convenience

    036-21539-003-B-0305 TABLE 32: DR ELECTRICAL DATA - STANDARD DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET COMPRESSORS HEATER OPTION MAX. FUSE/ MIN. OD FAN CONV MODEL BLOWER CIRCUIT BRKR VOLTAGE MOTORS OUTLET TONNAGE MOTOR AMPACITY MODEL STAGES AMPS SIZE FLA EACH AMPS EACH EACH (AMPS)
  • Page 48: Dr Electrical Data - High Static Drive Motor W/O Powered Convenience

    036-21539-003-B-0305 TABLE 33: DR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET COMPRESSORS HEATER OPTION MAX. FUSE/ MIN. OD FAN CONV MODEL BLOWER CIRCUIT BRKR VOLTAGE MOTORS OUTLET TONNAGE MOTOR AMPACITY MODEL STAGES AMPS SIZE FLA EACH AMPS EACH EACH...
  • Page 49: Dr Electrical Data - Low Airflow Drive Motor W/O Powered Convenience

    036-21539-003-B-0305 TABLE 34: DR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET COMPRESSORS HEATER OPTION MAX. FUSE/ MIN. OD FAN CONV MODEL BLOWER CIRCUIT BRKR VOLTAGE MOTORS OUTLET TONNAGE MOTOR AMPACITY MODEL STAGES AMPS SIZE FLA EACH AMPS EACH EACH...
  • Page 50: Outlet

    036-21539-003-B-0305 TABLE 35: DR ELECTRICAL DATA - STANDARD DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET COMPRESSORS HEATER OPTION MAX. FUSE/ MIN. OD FAN CONV MODEL BLOWER CIRCUIT BRKR VOLTAGE MOTORS OUTLET TONNAGE MOTOR AMPACITY MODEL STAGES AMPS SIZE FLA EACH AMPS EACH EACH (AMPS)
  • Page 51: Outlet

    036-21539-003-B-0305 TABLE 36: DR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET COMPRESSORS HEATER OPTION MAX. FUSE/ MIN. OD FAN CONV MODEL BLOWER CIRCUIT BRKR VOLTAGE MOTORS OUTLET TONNAGE MOTOR AMPACITY MODEL STAGES AMPS SIZE FLA EACH AMPS EACH EACH...
  • Page 52: Outlet

    036-21539-003-B-0305 TABLE 37: DR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET COMPRESSORS HEATER OPTION MAX. FUSE/ MIN. OD FAN CONV MODEL BLOWER CIRCUIT BRKR VOLTAGE MOTORS OUTLET TONNAGE MOTOR AMPACITY MODEL STAGES AMPS SIZE FLA EACH AMPS EACH EACH...
  • Page 53: Physical Data

    036-21539-003-B-0305 TABLE 38: PHYSICAL DATA MODELS DR 180 DR 240 DR 300 CENTRIFUGAL BLOWER (Dia. x Wd.) 15x15 18x15 EVAPORATOR BLOWER FAN MOTOR HP 5/7.5 7.5/10 15.0 ROWS DEEP EVAPORATOR FINS PER INCH 13.5 COIL FACE AREA (Sq. Ft.) 20.52 PROPELLER DIA.
  • Page 54: Unit Dimensions Dr180, 240

    036-21539-003-B-0305 ECONOMIZER / MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail Y) BLOWER MOTOR BLOWER BLOWER ACCESS COMPARTMENT ACCESS ACCESS 80- 9/32 COMPRESSOR ACCESS (Auxillary) (See detail X) 48- /4 DOT PLUG (For pressure drop reading) GAS OR ELECTRIC HEAT ACCESS...
  • Page 55: Unit Dimensions (Rear View)

    036-21539-003-B-0305 FIGURE 13 -UNIT DIMENSIONS (REAR VIEW) NOTE: Units are shipped with the bottom duct openings cov- ered. An accessory flange kit is available for connect- ing side ducts. For bottom duct applications: Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers.
  • Page 56: Unit Dimensions Dr180, 240

    036-21539-003-B-0305 E C O N O M I Z E R M O T O R I Z E D P O W E R E X H A U S T D A M P E R S U P P L Y A I R R A I N H O O D R A I N H O O D C O M P A R T M E N T...
  • Page 57: Four And Six Point Loads

    036-21539-003-B-0305 FIGURE 17 -FOUR AND SIX POINT LOADS TABLE 41: FOUR AND SIX POINT LOADS 4 Point Loads (lbs) Operating Unit Size Weight 180 Gas 2850 240 Gas 3150 1026 1026 300 Gas 3250 1058 1058 180 Elec 2650 240 Elec 2950 300 Elec 3050...
  • Page 58: Roof Curb Duct Openings

    036-21539-003-B-0305 25-1/4" FIGURE 18 -UNIT ROOF CURB DIMENSIONS FIGURE 19 -ROOF CURB DUCT OPENINGS DIMENSION FIGURE 20 -CUT AWAY OF ROOF CURB The 2” space between the ducts allows for “jumping” an existing roof joist. The 58-1/2” overall dimension of the ducts allows duct- work penetration between roof joists that are spaced on 72”...
  • Page 59 036-21539-003-B-0305 THERMOSTAT ( RCB ) TERMINALS REHEAT CONTROL BOARD TERMINAL BLOCK DEHUMIDISTAT TO REMOTE SENSOR 2ET04701324 IF USED Electronic programmable Thermostat 2ET0770010024 ( includes subbase). Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set-back position.
  • Page 60: Guide Specifications

    The units shall be factory wired, piped, Units shall be manufactured by York International Unitary charged with R-22 refrigerant and factory tested prior to ship- Products Group in an ISO 9001 certified facility.
  • Page 61 036-21539-003-B-0305 REFRIGERANT COMPONENTS Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation Compressors: down to 0 °F. Shall be Scroll compressors internally protected with Control board shall monitor each refrigerant safety internal high-pressure relief and over temperature switch independently.
  • Page 62 036-21539-003-B-0305 STANDARD LIMITED WARRANTIES • HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet • Compressor 5 Years altitude. • Heat Exchanger 10 Years • HIGH ALTITUDE - PROPANE GAS - Contains orifices •...
  • Page 63 036-21539-003-B-0305 Unitary Products Group...
  • Page 64 Subject to change without notice. Printed in U.S.A. 036-21539-003-B-0305 Copyright © 2005 by Unitary Products. All rights reserved. Supersedes: 036-21539-003-A-1104 Unitary 5005 Norman Products York Group Drive 73069...

Table of Contents