Mode 1 and 2
Mode
Mode 1
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
(monitoring
contents can be monitored as well.
settings)
Mode 2
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
(field settings)
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
7.2.2

To access the field setting components

See
"6.2.2 To open the outdoor unit" on
7.2.3

Field setting components

The components to make field settings are as follows:
V
TEST:
MODE
A1P
HWL:
IND
A2P
H1P
H2P
H3P
BS1
BS2
MODE
SET
X1M
X2M
Y
TEST/
MODE
IND
HWL
A2P
A1P
H1P
H2P
H3P
BS1
BS2
MODE
SET
X1M
X2M
DS1
DIP switches
BS1~BS5
Push buttons
H1P~H7P
7‑LEDs display
H8P
LED for indication during initialisation
ON ( ) OFF ( ) Flashing ( )
DIP switches
Only change the factory settings if you install a cool/heat selector
switch.
DS1‑1
COOL/HEAT selector (refer to the manual of the
cool/heat selector switch). OFF=not
installed=factory setting
DS1‑2
NOT USED. DO NOT CHANGE THE FACTORY
SETTING.
Push buttons
Use the push buttons to make the field settings. Operate the push
buttons with an insulated stick (such as a closed ball-point pen) to
avoid touching of live parts.
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1 – 2017.04
Description
page 16.
C/H SELECT
L.N.O.P. DEMAND
MULTI
MASTER SLAVE
H4P
H5P
H6P
H7P
H8P
BS3
BS4
BS5
RETURN
TEST
RESET
ON
DS1
OFF
1 2
MASTER
SLAVE
L.N.O.P.
DEMAND
MULTI
H4P
H5P
H6P
H7P
H8P
BS3
BS4
BS5
RETURN
TEST
RESET
ON
DS1
OFF
1 2
BS1
MODE: For changing the set mode
BS2
SET: For field setting
BS3
RETURN: For field setting
BS4
TEST: For test operation
BS5
RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed
7‑LEDs display
The display gives feedback about the field settings, which are
defined as [Mode-Setting]=Value.
H1P
Shows the mode
H2P~H7P
Shows the settings and values, represented in binary code
H8P
NOT used for field settings, but used during initialisation
Example:
[
-
32
+
16
+
8
+
4
+
2
+
1]
H1P
H1P H2P H3P H4P H5P H6P H7P
(H1P OFF)
(H1P flashing)
(H1P ON)
0
+
0
+
8
+
0
+
0
+
0
(H2P~H7P = binary 8)
0
+
0
+
0
+
4
+
0
+
0
(H2P~H7P = binary 4)
7.2.4

To access mode 1 or 2

After the units are turned ON, the display goes to its default
situation. From there, you can access mode 1 and mode 2.
Initialisation: default situation
NOTICE
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
Turn on the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit is
established and normal, the display indication state will be as below
(default situation when shipped from factory).
a
Power ON
b
Default situation
c
LED indication when there is a malfunction
If the default situation is not displayed after 10~12 minutes, check
the malfunction code on the indoor unit user interface. Solve the
malfunction code accordingly. First, check the communication wiring.
7 Configuration
Description
Default situation
Mode 1
Mode 2
Setting 8
(in mode 2)
Value 4
(in mode 2)
a
10~12 min
b
c
Installer and user reference guide