To Connect The External Outputs - Daikin VRV 5-S RXYSA8AMY1B Installation And Operation Manual

Table of Contents

Advertisement

8 HP
X1M
X3M
b
a
c
a
Interconnection cable
b
Power supply cable
c
Cable tie
WARNING
Do NOT strip the outer cable jacket lower than the fixation
point on the stop valve attachment plate.
5 For RXYSA8: Choose one of the two possibilities to route the
cables through the frame:
8 HP
2
1
b
b
a
a
a
Interconnection cable
b
Power supply cable
6 Remove the selected knockout holes by tapping on the
attachment points with a flat head screwdriver and a hammer.
7 Install a cable protection in the knockout hole:
▪ It is recommended to install a PG type cable gland in the
knockout hole.
▪ When you do not use a cable gland, protect the cables with
vinyl tubes to prevent the edge of the knockout hole from
cutting the wires:
A
B
a
c d
b
e
A
Inside of the outdoor unit
B
Outside of the outdoor unit
a
Cable
b
Bush
c
Nut
d
Frame
e
Tube
8 Route the cables out of the unit.
9 Reattach the service cover. See
unit" [ 4  27].
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1B – 2024.02
10-12 HP
X1M (A1P)
a
X1M
c
b
c
10+12 HP
b
a
"14.2.2  To close the outdoor
17 Electrical installation
10 Connect an earth leakage circuit breaker and fuse to the power
supply line as specified in
components" [ 4  37].
wiring
17.5

To connect the external outputs

SVS and SVEO output
The SVS and SVEO outputs are contacts on terminal X2M.
The SVS output is a contact on terminal X2M that closes in case a
leak is detected, failure or disconnection of the R32 sensor (located
in the SV unit or indoor unit).
The SVEO output is a contact on terminal X2M that closes in case of
occurrence of general errors. See
Overview"  [ 4   47] for errors that will trigger
and
"22.1.1  Error codes:
this output.
Outdoor output connection requirements
Voltage
220~240 V
Maximum current
0.5 A
Wire size
Only use harmonised wiring providing double
insulation and suitable for the applicable
voltage.
2-core cable
Minimum cable section of 0.75 mm²
NOTICE
Do NOT use the outputs as a power source. Instead, use
each output to energize a relay that controls the external
circuit.
WHT
BLK GRY PPL
X2M
SVEO
SVS
c
a
b
a
SVEO output terminals (1 and 2)
b
SVS output terminals (1 and 2)
c
Cable to SVS output device (example)
Example:
X2M
1
b
(SVS)
2
a
a
SVS output terminal
b
Relay
c
AC power supply 220~240 V AC
d
External alarm
INFORMATION
Sound data about the refrigerant leakage alarm are
available in the technical data sheet of the user interface.
E.g. the BRC1H52* controller generates an alarm of 65 dB
(sound pressure, measured at 1  m distance from the
alarm).
"17.2  Specifications of standard
Overview" [ 4  15]
"8.1 Error codes:
c
d
Installation and operation manual
39