2.3 Inverter Safety

• The voltage and frequency at the connecting point should meet the on-grid requirements.
• Additional protective devices like circuit breakers or fuses are recommended on the AC
side. Specification of the protective device should be at least 1.25 times the AC rated output
current.
• Make sure that all the groundings are tightly connected. When there are multiple inverters,
make sure that all the grounding points on the enclosures are equipotential bonding.
• The alarm can be cleared automatically if the inverter triggers a fault for less than 5 times
within 24 hours. The inverter will shutdown for protection after the 5th electric arc fault.
The inverter can operate normally after the fault is solved.
• BACK-UP function is not recommended if the PV system is not configured with batteries.
Otherwise, the risk in system power usage is beyond the equipment manufacturer's
warranty scope.
• All labels and warning marks should be visible after the installation. Do not cover, scrawl,
or damage any label on the equipment.
• Warning labels on the inverter are as follows:
High-temperature hazard. Do
not touch the product under
operation to avoid being burnt.
Read through the user manual
before any operations.
High-temperature hazard. Do
not touch the product under
operation to avoid being burnt.
CE marking
Grounding point.
WARNING
DANGER
3
02 Safety Precaution
Delayed discharge. Wait
5 minutes after power off
until the components are
completely discharged.
Potential risks exist. Wear
proper PPE before any
operations.
Do not dispose of the inverter
as household waste. Discard
the product in compliance with
local laws and regulations,
or send it back to the
manufacturer.